5. Transport, packaging and storage
5.1 Transport
Check the frost protection thermostat for any damage that may have
been caused during transportation. Obvious damage must be reported
immediately.
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during trans-
port (e.g. change in installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage:
Storage temperature: -30 ... +70 °C
Protect frost protection thermostat from moisture and dust.
6. Commissioning, operation
Installation and mechanical connection
The ambient temperature at the frost protection thermostat housing
(with the test loop) must be at least 2 °C above the selected set point.
If this cannot be guaranteed (e.g. outdoors or in exposed areas), the
housing and test loop must be installed inside the air handling unit.
The capillary tube must be mounted on the downstream side of the
heating coil (and on the upstream side in the case of cooling coils).
It should be looped diagonally across the heat exchanger pipes at a
distance of approx. 5 cm and should cover the entire area evenly. For
test purposes, it is recommended to have a loop of approx. 60 cm
directly beneath the housing outside the entry to the duct. To prevent
damage to the capillary tube, a minimum bending radius of 20 mm
must be ensured. Mounting can be made easier by using capillary tube
clamps (optional accessories).