Kutai DSP-10 Owner's manual

Type
Owner's manual
KUTAI ELECTRONICS INDUSTRY CO., LTD.
TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw
Headquarters : No.3, Ln. 201, Qianfu St., Qianzhen Dist., Kaohsiung City 80664, Taiwan
DSP-10
Genset Multi-Function Display Module
Model DSP-10 is a small integrated digital display showing
Voltage, Amp, Hz, and Hour Meter. It can be used
individually or jointly with a GCU-10 (Automatic Engine
Control Module) and a GCU-11R (Relay Module); jointly they
reduce cost, and installation time, simplifying equipment set
up.
This attractive little display is multitalented and its uses are
only limited by your imagination. It is equipped with DIN
terminal plugs that improve serviceability. The DSP-10
display can be used in any number of applications where
accurate reading of Voltage, Amps and Hertz are needed.
Front Panel Layout and Operation
DSP-10 Display panel
has three four Digits
bright LED’s that
shows (RMS) Voltage -
Amps Hertz Hour
Meter and Battery
Voltage. The operator
can change the display
to be fixed or cycling
from phase to phase
by simply using the
button next to each
display.
To change the display mode, press the button next to it. See
diagram.
Running Hour (Hr) Reset
To reset the Engine Running Hour to zero, press (Func)
button on the front panel until the (Hr) mode is displayed, and
then press (V) + (A) button together for 5 seconds erasing the
EEPROM and the hour meter back to zero.
Rear Panel Layout
Recommended Cut-Out 66 66 ± 0.5 mm
Voltage and Current Adjustment (If Need)
In the back of the DSP-10 module we have 4 push buttons for
voltage V & V and current A & A adjustment.
The Module comes factory tested and calibrated and
normally no changes are necessary. But if any modifications
are required, follow the procedures below.
Voltage Adjustment
(Please use and accurate RMS Voltmeter as your
reference)
1. Start the generator. Set your reference AC voltage using
your Voltmeter.
2. Select the desire phase you need to re-calibrate using the
front display V button on the display and hold.
3. Repeatedly press V) or V on back of module to
adjust the displayed voltage equivalent to your voltmeter.
4. Release the front V button. The LED display will flash
continuously for 5 seconds.
5. After for 5 seconds then the system will automatically
record the new setting and return to normal.
6. If the display shows FAIL the setting is invalid, and step
3 must be repeated.
Current Adjustment Procedure
(Please use Standard RMS Current meter for readings)
1. Set the dip switches to the correct CT in use.
2. Start the generator. And wait for the generator to stabilize.
3. Slowly add load to the genset until maximum rated load
current is reached for the CT in use.
4. Select desire phase current to calibrate using the front A
button.
5. Repeatedly press A or A on the back panel to
adjusts the displayed current to its equivalent on the
current meter.
6. Release the front A button. The LED on the display will
flash continuously for 5 seconds.
7. After 5 seconds the system will automatically record the
new setting and return to normal.
8. If the panel display shows FAIL then the previous
setting is invalid, please return to step 5.
L
23
L
12
L
31
VL
23
L
12
L
31
V
L
23
L
12
L
31
VL
23
L
12
L
31
V
L23 Fix Mode
L31 Fix Mode
L12 Fix Mode
Cyclic Mode
Setting The CT Value
Set the 5 pin dip switch for the CT (Current Transformer) and
the system phase you are using.
DIP Switch Setting Reference Diagram
50/5A
100/5A
150/5A
200/5A
250/5A
300/5A
400/5A
500/5A
600/5A
800/5A
1000/5A
1200/5A
1500/5A
1600/5A
2000/5A
3000/5A
Programmer Table =ON =OFF
System Phase select 5
= 3 Phase
5
= 1 Phase
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Current Transformer (CT)
Specification
DESCRIPTION
9.0 36 Vdc
10 500 Vac (Ph-Ph)
50/60 Hz
Above 2.5VA
5A
3000A / 5A
-20 to 60 ˚C
Under 90 %
Under 2W
179 g +/- 2%
Three Phase System Standard Wiring Diagram
Single Phase System Standard Wiring Diagram
Please link to http://www.kutai.com.tw for detailed manual
LOAD
CT-L3
GL2
Battery
+
N
L3
Emergency Stop
Accessory
J3-10
L1L3 L2
J3-1 J3-3J3-2
NV+
J3-4 J3-11
V-
J3-12
F2
0.5A0.5A
F3
0.5A
F1
"ON"
Stop
Start
Pre-Heat
J3-5 J3-6 J3-8J3-7 J3-9
35A
35A
F4
35A 35A
Pre-Heat
Start
Stop
Temp SW
OIL SW
Remote Start
AUX. Alarm
J1-5
J4-8J4-1 J4-3J4-2
L2 L1L3
J1-6 J1-2J1-4
J4-5J4-4 J4-6 J4-7
V+V-
J2-8J2-9 J1-1 J1-2
J2-12 J2-13
K
J2-15J2-14
LK
L
J4-9J4-13 J4-12 J4-10 J4-11
J1-4J1-6 J1-7
5A
J2-11 J2-10
5A5A 5A
J2-13J1-3 J2-8J2-12 J2-9
L3
N
GCU-10 GENERATOR CONTROL UNIT
Governor
Electronic
Idle Control
Idle control
J2-15J2-14
5A
L1
K L
CT-L1
CT-L2
L1
L2
GCU-11R
DSP-10 Meter
Advance Terminals
For DSP-11 Module
F2F3 F1
J4-1 J4-3J4-2
GCU-11R
J4-5J4-4 J4-6 J4-7
35A35A 35A
"ON"
Stop
Start
Pre-Heat
J3-6J3-5 J3-9J3-7 J3-8
35A
F4
J4-9
Pre-Heat
J4-13 J4-12
Start
Stop
J4-10 J4-11
Temp SW
OIL SW
Emergency Stop
Remote Start
AUX. Alarm
J1-5
DSP-10 Meter
J1-6
L3
J1-4 J1-2
L1L2
J2-12
J2-8
V+
J2-9
V-
J1-1 J1-2
J2-15
K L
CT-L1
GCU-10 GENERATOR CONTROL UNIT
5A5A 5A5A
J1-4J1-6 J1-7 J2-11 J2-10 J1-3 J2-13 J2-8J2-12 J2-9
L2
L1
Electronic
Governor
Idle Control
Idle control
5A
J2-15J2-14
Advance Terminals
For DSP-11 Module
Accessory
Battery
+
LOAD
L2
GL1
J3-10
J4-8
L1L2
J3-3J3-2J3-1
V-V+
N
J3-4 J3-12J3-11
0.5A0.5A 0.5A
  • Page 1 1