Analogue Values
Normal 16
Reverse Polarity 15**
Trouble 4*
Power Supply 2**
Note: *A UL listed end-of-line resistor is available at Apollo, Part no. 44251-146
Remarque: * Une résistance de fin de ligne répertoriée UL est disponible chez Apollo, réf. 44251-146
2
WIRING INSTRUCTION
Fig. 1 Fig. 2
INSTALLATION
This product must be installed in accordance with the applicable NFPA standards, local codes and
jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report
an alarm condition. Apollo America Inc. is not responsible for devices which are improperly installed,
maintained and tested.
Before installing this product, check the continuity, polarity and insulation resistance of all wiring. Check
that wiring is in accordance with the fire system drawings and conforms to all applicable local codes
such as NFPA 72.
1. Mount the electrical box as required and install all cables for termination.
2. Terminate all cables in compliance with local codes and regulation. Ensure that cable shield/
earth continuity is maintained and no short occurs with the back box(see Fig. 3 and 4 for
wiring instructions)
3. Set the address on dip switch of the unit as shown on page 4.
4. Install the wire separator provided.
5. Gently push the completed assembly towards the mounting box and verify wiring and
address. Align the fixing holes.
6. Secure the module to the electrical box with provided screws. Do not over tighten screws.
7. Place the face plate over the module and secure with provided screws.
8. Commission the module.
TECHNICAL INFORMATION COUNT.
3
Notification Appliance Circuit (NAC)
Wiring Styles Supervised power limited Class A and Class B
End-of-Line resistors* 47k Ω
External Supply Connected between Vext+ and Vext- Monitored
input (DC Voltage Supplies Only)
Max (NAC) Regulated 24V DC, 2A. Use a regulated power
limited dc supply that is listed for fire protection
applications. The maximum number of connected
devices must be within the output rating.
Max (Speakers) 70.7V rms, 500 mA with wire supervision
capability as per NFPA requirements. The
speakers used must be UL listed for fire
protection applications.
Refer to fire control panel literature for details on
how to achieve audio and visual synchronization.
Notes: *Notification appliance circuit short/open circuit or group address. Analogue Values need to be tested
with each individual compatible UL listed panel for compatibility.
**These Values are exclusive to monitoring Mode
Remarques: * Court-circuit de circuit d'appareil de notification / circuit ouvert ou adresse de groupe. Les
valeurs analogiques doivent être testées avec chaque panneau homologué UL compatible individuel
pour la compatibilité.
** Ces valeurs sont exclusives au mode de surveillance
Note: ‘X’ denotes unused terminals.
Remarque: "X" désigne les terminaux inutilisés.
Separate incoming and outgoing wire at every terminal
Do not loop Ne pas boucler
Class A | Fig. 3
Note: Power Supply needs to be installed within 20 feet and in conduit for Class A.
Remarque: le bloc d'alimentation doit être installé à moins de 20 pieds et dans un conduit pour la classe A.
WARNING: DISCONNECT POWER BEFORE OPENING
AVERTISSEMENT: COUPER LE COURANT AVANT D'OUVRIR
CAUTION –
•
When Making Installation, Route Field Wiring Away From Sharp Projections, Corners, and Internal
Components
•
A minimum of 1/4 inch space is required between Power Limited and Non-Power Limited circuits
while wiring.
MISE EN GARDE –
•
Lors de la pose, acheminer le câblage extérieur de manière à éviter les arêtes vives, les coins et les
composants internes
•
Un espace minimum de 1/4 pouce est requis entre les circuits à puissance limitée et non limitée
lors du câblage.
WARNING: ELECTRICAL SHOCK HAZARD
AVERTISSEMENT: RISQUE DE CHOC ELECTRIQUE
Normal + Ground Fault 19