Wattstopper
®
HID Bi-Level Control Modules
Installation Tech Note
No: 25356 – 12/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: DM-105
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
DANGER—HIGH VOLTAGE
EQUIPMENT DAMAGE, PERSONAL
INJURY AND DEATH CAN RESULT
FROM IMPROPER PROCEDURES
AND INSTALLATION.
HIGH VOLTAGE FROM ORIGINAL CAPACITOR
MUST BE SAFELY DISCHARGED.
CUSTOM CAPACITOR WIRING FOR DM-105
For product description, operation, installation, mounting and low-voltage wiring, see the Installation Instructions
provided with the HID Bi-Level Control Module.
Ballast Wiring
For wiring to standard capacitors ordered from WattStopper, refer to the wiring diagrams in the installation instruction manual for the HID
Bi-Level Control Module.
For CUSTOM CAPACITOR wiring, note the terminal designations on your capacitor then follow the instructions below.
Low Value
Common
High Value
CUSTOM
Capacitor
DM-105
HID Control
White/Blue
White
White/Orange
1. Connect WHITE/BLUE wire from the DM-105 control module to the Low Value terminal on the bi-level capacitor.
2. Connect WHITE wire from the DM-105 control module to the Common terminal on the bi-level capacitor;
• From the same terminal complete the connection to the ballast with the WHITE wire.
3. Connect WHITE/ORANGE wire from the DM-105 control module to the High Value terminal on the bi-level capacitor.