Phoenix Advanced pressure monitor II Installation guide

Type
Installation guide
Advanced Pressure Monitor II
and Central Display Rough-In
Installation Guide
Printed in USA
Copyright 2011, 2012, 2013
Phoenix Controls
Accel, Phoenix, Phoenix Controls, Usage Based Controls, UBC, Celeris, Theris, Traccel, Zone Presence
Sensor and ZPS are registered trademarks, and LabPro, MacroServer, MicroServer and Neutralizer
are trademarks of Honeywell International, Inc.
Phoenix Controls products are covered by one or more of the following U.S. patents:
5,251,665 5,304,093 5,545,086 D642894
and other patents pending.
The material in this document is for information purposes only and is subject to change without
notice. Phoenix Controls assumes no responsibility for any errors or for consequential damages that
may result from the use or misrepresentation of any of the material in this publication.
BACnet is a registered trademark of the American Society of Heating, Refrigerating, and Air-
Conditioning Engineers (ASHRAE).
iii
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
Table of Contents
Section 1. Advanced Pressure Monitor II Rough-In Installation
1.1 Required Parts to be Supplied by the Installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Parts Included with Your Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Installation Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 Wiring Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.2 Wiring Triple Gang Electrical Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.3 Plumbing Rough-In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.4 Use of External Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.5 Remote Annunicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Plumbing (Finish). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5.1 Power, Labeled POWER, L1, L2, Ground Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.2 Analog Output, Labeled ANL OUT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.3 Analog Input, Labeled DOOR, INPUT2, INPUT1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.3.1 Measuring Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.4 Optional Remote Transducer Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.5 Relay and Annunciator Output, Labeled RELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5.6 Optional Remote Annunciator Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5.7 Third Party Remote Annunciator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.5.8 Completing the Finish Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 2. Fitting an APM2 in an APM100 Enclosure
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.1 What Is Included In Your Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.1.1 Not Included - Tools You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.1 Turn Off Power To the APM100 Unit And Remove It From The Wall . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.2 Ensure Existing APM1 Enclosure Is Prepared For APM2 Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2.3 Attach the Base APM2 Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2.4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.5 Remotely Switching Alarm Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.6 Modified Pressure Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.2.7 Complete the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 3. APM2 Central Display Rough-In Installation
3.1 Required Parts to be Supplied by the Installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Parts included with Your Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3 Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3.1 Wiring Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.3.2 Wiring Triple Gang Electrical Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
iv
MKT-0262 MPC-1748 Rev 02/13
Table of Contents
3.4.1 Power, Labeled POWER, L1, L2, Ground Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.4.2 Completing the Finish Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section 4. Ancillary Product Specifications
4.1 Model 264 Pressure Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Model 267 Pressure Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3 Remote Annunciator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4 Pressure Pickup Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.5 Phoenix Recommended Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.5.1 MS/TP Specifications for Alternate Cable Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Advanced Pressure Monitor II Rough-In Installation
Required Parts to be Supplied by the Installer
1
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
Section 1. Advanced Pressure Monitor II Rough-In
Installation
For the Advanced Pressure Monitor II (APM2) to be installed correctly, the rough-in phase of the project must
be completed properly. This section will outline the specific considerations the General Contractor must pay
attention to so that the final wiring and commissioning will go smoothly.
During rough-in installation, the field wiring and plumbing can be run in the walls and routed between the
triple gang electrical box, the Building Management System (BMS), door contact switch, remote sensors (if
applicable) power supply, earth ground and so on.
If you’re installing the APM2 monitor, continue to to Section 1.1 Required Parts to be Supplied by the Installer.
If you’re installing the APM2 Central Display, refer to APM2 Central Display Rough-In Installation on page 19.
1.1 Required Parts to be Supplied by the Installer
The following is a list of parts required and supplied by the installer for the APM2:
Triple gang-double deep electrical box (RACO 697 or Appleton M3-350), quantity 1
Green grounding screw, quantity 1
Power (18 AWG recommended) and signal wiring (22 AWG recommended), as needed. Refer to Phoenix
Recommended Cables on page 33.
0.25" (6 mm) O.D. flame retardent polyethelyne control tubing (such as CPChem UL 1820)—to run from
the room(s) to the APM2 (maximum 250 feet [76.2 meters] length)
NOTE: Less that 10% or 10 feet (1.6 meters) of total control tubing can be used in a vertical rise. Maintain
tubing run on the same floor as the APM2.
T-connectors
NOTE: Phoenix Controls recommends no more than five (5) T-connectors in a single run going to any
APM2.
EMT conduit (if required by local code)
•24 Vac Transformer
Door switch SPDT or SPST—normally open, as required
Remote pressure transducers, as needed
Remote Annunciators, as needed
The following is a list of part required and supplied by the installer for the Remote Annunciator and Pressure
Pickup Port:
Single gang electrical box, as needed
0.25" (6 mm) O.D. flame retardent polyethelyne control tubing (such as CPChem UL 1820)—to connect
between the Pressure Pickup Port and the APM2
2
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Parts Included with Your Order
1.2 Parts Included with Your Order
The following are parts that are included in your order:
Advanced Pressure Monitor II (APM2), including factory calibrated differential pressure sensor, quantity 1
APM2 Faceplate, quantity 1
Pressure Pickup Port (quantity 0, 1 or 2 - depending on order configuration)
0.25" O.D. Tubes, Silicone, with integrated springs and attached brass barbed couplings, quantity 2
Mounting screws, 6-32 x 1/2 Phillips head, quantity 5
Mating Electrical Connectors, Phoenix contact MC plug kit, quantity 1 with 3 green and 2 black connec-
tors
1.3 Installation Overview
Each APM2 consists of a room pressure pick-up, a reference space pressure pickup and a room pressure
monitor panel, which houses a differential pressure sensor.
The two pressure pickup ports are installed in single gang electrical boxes, which are placed in the room
walls.
Standard 0.25" (6 mm) O.D. flame retardent polyethelyne control tubing (such as CPChem UL 1820),
maximum 250 feet (76.2 meters) length, is run within the wall from the sensors to the monitor panel. In
some code jurisdictions, the tubing must be in EMT conduit. Tubing and conduit is provided by others.
NOTE: Less that 10% or 10 feet (1.6 meters) of total control tubing can be used in a vertical rise. Maintain
tubing run on the same floor as the APM2.
Install in a triple gang-double deep electrical box (RACO 697, Appleton M3-350 or equivalent).
Secure the triple gang-double deep electrical box to the stud(s) by using the mounting hole in the side of
the electrical box (see figure below for mounting hole location). Drive the mounting screws from the inside
of the electrical box into the wall studs to prevent sharp objects from protruding into the electrical box.
Ensure the mounting is level and flush to the wallboard surface.
Advanced Pressure Monitor II Rough-In Installation
Installation Overview
3
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
Figure 1-1. Wall Mount Installation Overview
1.3.1 Wiring Recommendations
All circuits must conform to the requirements of an NEC Class 2 (dry) circuit.
Use multiple transformers instead of larger transformers when more than 100 VA is required.
Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit
disconnect.
•Refer to Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types.
Use stranded wire for ease of installation.
Follow good wiring practices:
Locate cables away from sources of electrical interference (EMI/RFI).
Do not run signal or communication cable in the same conduit or wire way as power cables.
If signal cable must cross power cables place these at a 90-degree angle.
Shield or drain wires, if required, should be wrapped with insulating tape to prevent contact with exposed
conductors or contacts.
Maintain a consistent color code or polarity all the way through the wiring system.
Power supply and signal isolation on I/O devices vary from manufacturer to manufacturer. Verify the
wiring device manufacturers recommendations for isolating power and signal common connections and
maintain polarity.
Local and national electrical codes take precedence.
Single Gang
Electrical Box
1/4" x .170 Tube Barb
(Conduit between
sensors and monitor
panel may be required.)
Reference
Pressure Pickup
Room
Pressure Pickup
APM2
NOTE: Connecting tubing and electrical
boxes are field-supplied.
Triple Gang Double Deep
Electrical Box
APM2 Faceplate
APM2
Rough-in Electrical Box
- Raco 697
- Appleton M3-350
Electrical Box
Mounting Hole
WALL MOUNT DIMENSIONS
Triple gang double deep electrical box—5.625" (220 mm) W x 3.5" (114.3 mm) H x 3.5" (63.5 mm) D
Single gang electrical box—2" (51 mm) W x 3" (76 mm) H x 3.5" (63.5 mm) D*
* Dimensions are approximate.
4
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Installation Overview
Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into
the terminal block, and tighten the terminal.
•Test the wire connection by pulling on each conductor.
WARNING: Wiring must be performed by a licensed electrician according to local and state codes.
1.3.2 Wiring Triple Gang Electrical Box
USE ONLY THE KNOCKOUTS ON THE TOP OR BOTTOM AT THE BACK OF THE ROUGH-IN
ELECTRICAL BOX. The front knockouts will be inaccessible once the APM2 is installed. Strain relief and seal
box as required.
NOTE: Install power and signal wires into separate knockouts to avoid noise.
Figure 1-2. Wiring in the Triple Gang Electrical Box
1.3.3 Plumbing Rough-In
If the internal pressure sensor will be used, then typically a Pressure Pickup Port is installed in the monitored
room and another one is installed in the reference area (typically a hallway). 0.25" nylon tubing is typically used
to bring the pressure signal from this point of measurement to the pressure inputs on the back of the APM2.
Install a single gang electrical box anywhere inside the room, typically high on the wall in an inconspicuous area.
This will be used for the room pressure signal (room monitor pressure port labeled HIGH). Run 0.25" tubing
from this electrical box to the triple gang box that the pressure monitor will be mounted to in the finish stage
of the installation.
CAUTION: Be careful in running the tubing in a way that the tube is protected from being damaged by being cut
or penetrated by screws or nails or being crimped so that the pressure signal integrity is affected. Do
not tighten strain reliefs so that they crimp the tubing. Tape the open ends of the tubes closed to
prevent contamination of the inside of the tubing.
Install a second single gang box on the corridor, ante room or other reference pressure area. This will be used
for the low pressure side or reference side pressure signal. This will be run to the triple gang box and connected
to the APM2 pressure port labeled LOW.
Advanced Pressure Monitor II Rough-In Installation
Installation Overview
5
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
If an external sensor will be used then run the pressure signals (room and reference) to the remote transducer.
Figure 1-3. Pressure Pickup Port Installation
1.3.4 Use of External Transducers
The APM2 has the option to use the internal pressure sensor or external pressure transducers (ordered
separately). If external pressure sensors are being used then no tubing needs to be run into the electrical box.
Instead the remote pressure transducer will be separately mounted, plumbed and wired. Only the wire for the
analog output of that transducer(s) will be run to the APM2. If two rooms are being monitored, you have the
choice to use the internal pressure sensor and an external (remote) transducer for the second room, or two
external remote transducers may be used and wired to the analog inputs in the back of the unit.
NOTE: See Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types.
Layout the system in terms of wiring:
Power: 24 Vac, 9 VA
Annunciator/relay: remote alarm wiring if being used
Analog output: 0-5 or 0-10 Vdc or 4-20 mA.
Analog Input wiring: there are two analog inputs that can be used to bring signals from remote pressure
transducers
Digital Input: the digital input can be used as a door status indication, these would be wired to a door switch
mounted in the door jamb.
Once the installation has been planned, locate and mount the electrical box and bring all tubing, power, earth
ground, analog input, digital input, relay/annunciator, analog output communications wiring into the triple
gang box.
6
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Plumbing (Finish)
1.3.5 Remote Annunicator
If an remote annunciator will be used, then mount a single gang electrical box in the desired location and run
wires to it.
Figure 1-4. Remote Annunciator
1.4 Plumbing (Finish)
Use the following procedure for all room types positive, negative or neutral.
The biggest problem that can occur during plumbing is kinking of the often stiff nylon 0.25" tubing that is used
for running pressure signals from the APM2 to the monitored spaces. To prevent buckling and collapse of this
stiff tubing inside the electrical box, use the supplied soft silicone tubing with integrated springs and tubing
adapters to transition from the field tubing to the pressure fittings on the APM2.
Green LED
Red LED
Acknowledge
Switch
Audible
Alarm
Soft Silicon
Tubing with
Integrated
Springs
7
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Wiring
THIS PAGE INTENTIONALLY LEFT BLANK.
Attach pressure tubing as follows:
1. Install the supplied silicone tube (with integrated spring) and attached barbed tube adaptor onto the end of
the 0.25 field tubing. Thread the tubes, with installed adaptor, through the conduit opening at the bottom
of the electrical box.
2. Next push the open end of the soft silicone tubing onto the APM2 pressure tube port labeled "HIGH".
3. For the most pressure stable operation, a Pressure Pickup Port installed in the reference pressure area is also
recommended. In this case, install the Pressure Pickup Port in a hallway or reference space.
4. Next push the open end of the soft silicone tubing onto the APM2 pressure tube port labeled "LOW".
1.5 Wiring
Figure 1-5. Rear View of the APM2 (BACnet) Showing Wiring and Plumbing Connections
ANALOG (ANL) OUTPUT
COM COM
mA Current Output (4-20 mA)
Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door
DI Digital Input
COM COM Analog Input2
IN2 Analog Input2 (0-5, 0-10Vdc)
+15 15 Vdc
COM COM Analog Input1
IN1 Analog Input1 (0-5, 0-10Vdc)
+15 15 Vdc
Earth Ground
L1 24 Vac
L2 24 Vac
HIGH or room pressure tubing
contacts here
LOW or reference pressure tubing
connects here
POWER
RELAY
COM COM
+15 +15 Vdc
NO Normally Open
RC Relay COM
NC Normally Closed
COM BACnet APM2-xx-ENG-BAC Products
B (+)
A (-)
GND
REAR VIEW
8
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Wiring
Figure 1-6. Rear View of the APM2 (Analog) Showing Wiring and Plumbing Connections
The back of the APM2 has electrical connectors labeled with their function. The mating electrical connectors
(supplied) are color coded and labeled with the matching function.
1.5.1 Power, Labeled POWER, L1, L2, Ground Symbol
Starting with the 3 pin Power connector:
1. Connect the 24 Vac lines to L1 and L2.
2. Connect a ground wire, GND, from the ground lug to the GND on the connector.
3. Install Connector.
The APM2 operates at 18-32 Vac, 50/60 Hz and consumes 2.6 W nominal, 9.6 W max.
1.5.2 Analog Output, Labeled ANL OUT
If using the analog output and want Voltage output, connect to the terminals labeled VDC and COM.
If using the analog out and want a 4-20 mA signal, connect to terminals labeled mA and COM. Connect this
output to the BMS system or other monitoring device.
ANALOG (ANL) OUTPUT
COM COM
mA Current Output (4-20 mA)
Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door
DI Digital Input
COM COM Analog Input2
IN2 Analog Input2 (0-5, 0-10Vdc)
+15 15 Vdc
COM COM Analog Input1
IN1 Analog Input1 (0-5, 0-10Vdc)
+15 15 Vdc
Earth Ground
L1 24 Vac
L2 24 Vac
HIGH or room pressure tubing
connects here
LOW or reference pressure tubing
connects here
POWER
RELAY
COM COM
+15 +15 Vdc
NO Normally Open
RC Relay COM
NC Normally Closed
COM NOT AVAILABLE
B (+)
A (-)
GND
REAR VIEW
Advanced Pressure Monitor II Rough-In Installation
Wiring
9
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
1.5.3 Analog Input, Labeled DOOR, INPUT2, INPUT1
There are two analog inputs available for remotely mounted transducer inputs. These are INPUT1 and
INPUT2.
A 15 Vdc (14.8 to 15.2) excitation is available to power up to two transducers. They can source 90 mA max.
combined. It is labeled as +15 on the connectors.
If using this to power a remote transducer, connect this to the positive excitation terminal of the transducer.
1.5.3.1 Measuring Analog Inputs
There are three potential analog inputs that can be measured, 0-5, 0-10 and 4-20 mA.
For 0-5 or 0-10 Vdc inputs connect the positive (+) output of the transducer to terminal labeled IN1, con-
nect the common output of the transducer to the terminal labeled COM.
For 4-20 mA loops install a 250 ohm resistor between the terminals labeled In1 or IN2 (whichever input
youre going to) and COM. The monitor will be measuring the voltage across this resistor as 1-5 Vdc cor-
responding to 4-20 mA.
If you will be monitoring the status of a door position, then wire the contacts labeled DOOR to the normally
open contacts on a door jamb switch. The monitor will show the door "Warning" (when enabled) when the
door is open. The door jamb switch should be closed when the door is closed and open when the door is open.
1.5.4 Optional Remote Transducer Wiring
The figure below references the Setra remote sensors equipped with 4-20 mA output. The instruction booklets
supplied with the sensors cover both the
3-wire voltage output configuration and 2-wire current configuration. The figure below clarifies the 2-wire 4-
20 mA connection between the Setra 264 or 267 and APM2 inputs. The same connection applies to IN2 (AI2).
If the APM2 output is configured for 4-20 mA on the AO, the users can use either 249 or 500 Ohm resistors
depending on whether they desire 1-5 or 2-10 Vdc.
Figure 1-7. Optional Remote Transducer Wiring
+
-
+ 15 Vdc
IN1
COM
APM2
Setra Model 264
Current Output
249
Ohm
10
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Wiring
1.5.5 Relay and Annunciator Output, Labeled RELAY
There is an SPDT dry contact available. When an alarm occurs the Normally Open (NO) and the Common
(COM) internal contacts will be closed. During no alarm conditions the Normally Closed (NC) and COM are
shorted.
This relay can also drive a Remote Annunciator.
1.5.6 Optional Remote Annunciator Wiring
In the figure below, the Remote Annunciator connector is at left, and the APM2 connector is at right.
Figure 1-8. Remote Annunciator Wiring Diagram
To connect +15 Vdc power, connect the +15 Vdc from the relay connector to +15 Vdc, A1 at the Remote
Annunciator. This supplies 15 V exc. to the Remote Annunciator for powering the circuit during normal
conditions.
To connect power return, connect the COM of relay connector to Ground, A2 at the Remote Annuncia-
tor.
On of the relay connector, connect a short jumper between the +15 and relay connector. This will connect
the internal 15V supply to the common of the internal alarm relay.
Connect the NO on the relay output to the +15 Vdc Trigger, A3 terminal on the Remote Annunciator.
When an alarm occurs and after the programmed alarm delay times out, the internal relay will supply 15 V to
the Remote Annunciator circuit to actuate the audible buzzer and the red LED.
Advanced Pressure Monitor II Rough-In Installation
Wiring
11
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
1.5.7 Third Party Remote Annunciator
The APM2 can drive other annunciators that are powered by a 15V supply, 50 mA max current draw, and
accept a 15V trigger. If purchased separately, the Remote Annunciator can also be driven as shown below.
Figure 1-9. 3rd Party Remote Annunciator Wiring Diagram
1.5.8 Completing the Finish Wiring
1. Connect all the electrical connectors matching the wiring connector with the mates on the back of the
unit. Connectors are color coded and keyed.
2. Connect the pressure signals to the HIGH and LOW ports on the back of the unit. The springs on the
outside of the tubing are there to prevent buckling of the tube. As you push the unit into the electrical box
push the black instrument tubing into the conduit tube or into the wall, Ideally the supplied silicone tube
is the only tubing in the electrical box after the unit is slid in as far as it will go.
Figure 1-10. Connecting Electrical Connectors to Back of APM2
3. Mount the unit cover to the electrical box using four of the supplied mounting screws. Leaving screws
slightly loose adjust the cover so that it is square. Securely tighten so that the back of the cover is tight to
the finish wall surface.
12
MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Wiring
Figure 1-11. Mounting APM2 in Triple Gang Electrical Box
4. Mount the front cover assembly.
Figure 1-12. Installed APM2
Fitting an APM2 in an APM100 Enclosure
Overview
13
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
Section 2. Fitting an APM2 in an APM100 Enclosure
2.1 Overview
APM100 pressure monitors from Phoenix Controls can be replaced in the field using the newer APM2 units.
However, it is important to order the Retrofit Kit version of the APM2 product for compatibility with the
existing enclosure. The APM2 Retrofit Kit includes additional parts and modifications to the standard APM2
product that permits easy installation in the field.
These instructions outline how to replace an APM100 series pressure monitor with APM200 series units.
APM100 models installed in the field are housed in a 5-gang single-deep electrical box. The APM2 models
require a 3-gang double-deep electrical box for new installations, so it will not fit directly into the APM1
enclosure without this adapter kit.
2.1.1 What Is Included In Your Kit
APM2 model with the pressure range you ordered with 90 degree pressure taps on the rear of the unit for
proper seating in the APM100 enclosure
Stainless steel adapter plate to cover the larger APM100 wall opening
Four (4) phillips head screws to secure APM2 to the adapter plate
Four (4) Allen head screws to secure adapter plate to the existing APM100 enclosure
APM2 white faceplate
APM2 installation instructions
APM2 connector kit
APM2 calibration certificate
2.1.1.1 Not Included - Tools You Will Need
Small blade terminal screwdriver
Phillips head screwdriver
1/8" Allen wrench
14
MKT-0262 MPC-1748 Rev 02/13
Fitting an APM2 in an APM100 Enclosure
Instructions
2.2 Instructions
IMPORTANT: As part of the site preparation, any wiring or tubing coming into the APM100 unit may
need to be moved to accomodate the depth of the APM2.
Figure 2-1. APM100 Display
2.2.1 Turn Off Power To the APM100 Unit And Remove It From The
Wall
1. Remove the four allen head screws from the APM100.
CAUTION: Carefully, pull the APM100 out of the APM100 box.
2. Disconnect power and all connectors. Label connectors so it will be clear how to reconnect them to the
APM2 unit.
3. Disconnect pressure tubing from the APM100 and label room side and reference side tubing.
Fitting an APM2 in an APM100 Enclosure
Instructions
15
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
2.2.2 Ensure Existing APM1 Enclosure Is Prepared For APM2 Unit
1. Make sure the wall surface around the existing enclosure is flat and clean with no wall damage or holes
beyond the electrical box.
2. A full 5.18" of the center of the existing enclosure will be occupied by the APM2 unit when it is installed.
Any wires or tubing in this region of the electrical box should be moved to the outer perimeter of the
enclosure so the APM2 can slide in without obstructions. You may need to use the knockouts on either
sides, tops or bottom as shown below.
Figure 2-2. APM100 Knockout Locations
2.2.3 Attach the Base APM2 Unit
Mount the base APM2 unit to the adapter plate using the four supplied phillips head screws. Leaving screws
slightly loose adjust the cover so that it is square. Securely tighten so that the back of the cover is tight to the
finish wall surface.
Figure 2-3. Installing APM2 to the Adapter Plate
Four phillips head
screws provided
16
MKT-0262 MPC-1748 Rev 02/13
Fitting an APM2 in an APM100 Enclosure
Instructions
2.2.4 Wiring
Figure 2-4. Rear View of the APM2 Showing Wiring and Plumbing Connections
The back of the APM2 has electrical connectors labeled with their function. The mating electrical connectors
(supplied) are color coded and labeled with the matching function.
Refer to the Advanced Pressure Monitor II User’s Guide (MKT-0263) for detailed wiring instructions.
2.2.5 Remotely Switching Alarm Setpoints
The APM100 model uses dry contacts to switch pressure setpoints between positive and negative, whereas the
APM2 uses an input voltage: 0, 5 or 10 Volts to switch pressure setpoints between negative-neutral-positive
respectively. If this function was used on the APM100 product, adaptations will need to be made to restore their
function with other equipment or devices that will generate the 0, 5 or 10 Volt signal.
ANALOG (ANL) OUTPUT
COM COM
mA Current Output (4-20 mA)
Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door
DI Digital Input
COM COM Analog Input2
IN2 Analog Input2 (0-5, 0-10Vdc)
+15 15 Vdc
COM COM Analog Input1
IN1 Analog Input1 (0-5, 0-10Vdc)
+15 15 Vdc
Earth Ground
L1 24 Vac
L2 24 Vac
HIGH or room pressure tubing
contacts here
LOW or reference pressure tubing
connects here
POWER
RELAY
COM COM
+15 +15 Vdc
NO Normally Open
RC Relay COM
NC Normally Closed
COM BACnet APM2-xx-ENG-BAC Products
B (+)
A (-)
GND
REAR VIEW
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46

Phoenix Advanced pressure monitor II Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI