P C O R E E L E C T R I C 1 3 5 G I L B E R T S T R E E T L E R O Y N Y 1 4 4 8 2
5 8 5 . 7 6 8 . 1 2 0 0 W W W . H U B B E L L P O W E R S Y S T E M S . C O M
B-330756-A Rev. 4-15-16
Instructions for Installation and Use of PCORE
®
Seismically Enhanced Test (SET) Terminals
PCORE® SET Terminals are manufactured with the highest quality materials and are designed for
many years of reliable service. In order to obtain the highest performance, it is necessary to follow
these steps for installation and usage.
WARNING: The moveable side bars should be kept in the closed position at all times, except for
when tests (electrical and/or mechanical) are being performed upon the bushings and/or related
equipment on which each SET Terminal is installed.
STORAGE
PCORE SET Terminals must be stored in a clean and dry environment. DO NOT STORE OUTDOORS.
If the contact surfaces become corroded, the corrosion must be completely removed from the contact
surfaces before they are used.
APPLICATION REQUIREMENTS
PCORE SET Terminals must be connected properly to the equipment or overheating and damage may
result. The following requirements must be met to ensure proper operation:
1. All contact surfaces on both the PCORE SET Terminal and the connected equipment must be
properly cleaned with an abrasive pad or sandpaper and, for aluminum contacts, antioxidant
grease applied before installation.
2. If the PCORE SET Terminal utilizes a NEMA pad, then the cross section of the current carrying
bus must be equal or greater than the cross section of the pad.
3. Maximum cantilever loading of the PCORE SET Terminal is 2500 ft.-lbs. with the moveable side
bars in the open or closed position.
a. It is possible that the allowable loading of the PCORE SET Terminal exceeds that of the
apparatus on which it is mounted. In such a scenario, always design around the lower
maximum cantilever value to avoid possible damage to equipment.
INSTALLATION
PCORE SET Terminals are packaged ready for use. However, a few precautions must be taken before
installation:
1. The PCORE SET Terminal should be oriented so that the movable bars open in a downward
motion. See Figure 1 on reverse side.
a. For units with NEMA pads, the recommended loading direction is parallel to the flats of
the blade.
b. For units with female threaded connectors, the recommended loading is perpendicular to
the terminal clamp bolts.
2. Verify all fasteners are tight, recommended Torque Values:
a. Captive Bolts & Terminal Clamp Bolts (1/2-13), 40 ft.-lbs.
b. Corona Ring Bolts (3/8-16), 20 ft.-lbs.
3. For aluminum, clean all contact surfaces using an abrasive pad to remove any oxidation. Wipe
off all dirt and immediately (within 2 minutes) apply a thin coat of no-ox grease made specifically
for aluminum electrical contacts.
4. All connections should be bolted tight. The use of cone washers to prevent loosening of the
connection is highly recommended.