Endres+Hauser Liquiphant FTL64 Operating instructions

Type
Operating instructions
Products Solutions Services
Operating Instructions
Liquiphant FTL64
Vibronic
HART
Point level switch for liquids in high-temperature
applications
BA02215F/00/EN/02.23-00
71630438
2023-11-30
Valid as of version
01.00.zz (Device firmware)
Liquiphant FTL64 HART
2 Endress+Hauser
Order code:
Ext. ord. cd.:
Ser. no.:
www.endress.com/deviceviewer Endress+Hauser
Operations App
XXXXXXXXXXXX
XXXXX-XXXXXX
XXX.XXXX.XX
Serial number
1.
3.
2.
A0023555
Liquiphant FTL64 HART Table of contents
Endress+Hauser 3
Table of contents
1 About this document ................ 6
1.1 Purpose of this document ................. 6
1.2 Symbols ............................. 6
1.2.1 Safety symbols .................. 6
1.2.2 Electrical symbols ................ 6
1.2.3 Tool symbols .................... 6
1.2.4 Communication-specific symbols ..... 6
1.2.5 Symbols for certain types of
information .................... 6
1.2.6 Symbols in graphics ............... 7
1.2.7 Registered trademarks ............. 7
2 Basic safety instructions ............ 7
2.1 Requirements for the personnel ............ 7
2.2 Intended use .......................... 7
2.2.1 Incorrect use .................... 8
2.3 Workplace safety ....................... 8
2.4 Operational safety ...................... 8
2.5 Product safety ......................... 8
2.6 Functional Safety SIL (optional) ............ 9
2.7 IT security ............................ 9
2.8 Device-specific IT security ................ 9
3 Product description ................. 9
3.1 Product design ....................... 10
4 Incoming acceptance and product
identification ..................... 10
4.1 Incoming acceptance ................... 10
4.2 Product identification ................... 11
4.2.1 Nameplate .................... 11
4.2.2 Manufacturer address ............ 11
4.3 Storage and transport .................. 11
4.3.1 Storage conditions ............... 11
4.3.2 Transporting the device ........... 11
5 Mounting ......................... 12
5.1 Mounting requirements ................. 12
5.1.1 Pay attention to the temperature for
devices with a PFA coating
(conductive) ................... 12
5.1.2 Take switch point into consideration .13
5.1.3 Take viscosity into consideration .... 13
5.1.4 Avoid buildup .................. 14
5.1.5 Take clearance into consideration ... 15
5.1.6 Support the device .............. 15
5.2 Mounting the device ................... 16
5.2.1 Required tool .................. 16
5.2.2 Installation .................... 16
5.3 Sliding sleeves ....................... 19
5.4 Post-mounting check ................... 19
6 Electrical connection .............. 20
6.1 Required tool ......................... 20
6.2 Connecting requirements ............... 20
6.2.1 Cover with securing screw ......... 20
6.2.2 Potential equalization ............ 20
6.3 Connecting the device .................. 21
6.3.1 Supply voltage ................. 21
6.3.2 Terminals ..................... 21
6.3.3 Cable specification ............... 21
6.3.4 4 to 20 mA HART ............... 22
6.3.5 Overvoltage protection ........... 22
6.3.6 Wiring ....................... 23
6.3.7 Terminal assignment ............ 23
6.3.8 Cable entries ................... 24
6.3.9 Available device plugs ............ 24
6.4 Ensuring the degree of protection ......... 25
6.4.1 Degree of protection ............. 25
6.5 Post-connection check .................. 25
7 Operation options ................. 26
7.1 Overview of operating options ............ 26
7.2 FEL60H electronic insert ................ 26
7.3 Function test using operating key on
electronic insert ....................... 27
7.4 Structure and function of the operating
menu .............................. 28
7.4.1 User roles and related access
authorization .................. 28
7.5 Access to the operating menu via the onsite
display ............................. 28
7.5.1 Device display (optional) .......... 28
7.5.2 Operation via Bluetooth® wireless
technology (optional) ............ 29
7.6 Access to the operating menu via the
operating tool ........................ 30
7.7 HistoROM data management ............. 30
8 System integration ................ 30
8.1 Overview of device description files ......... 30
8.2 Measured variables via HART protocol ...... 30
8.2.1 Device variables and measured
values ........................ 31
8.2.2 System units ................... 31
9 Commissioning ................... 31
9.1 Preparations ......................... 31
9.1.1 As-delivered state ............... 32
9.2 Function check ....................... 32
9.3 Connecting via FieldCare and DeviceCare .... 32
9.3.1 Via HART protocol ............... 32
9.3.2 FieldCare/DeviceCare via service
interface (CDI) ................. 33
9.4 Configuring the device address via software .. 33
Table of contents Liquiphant FTL64 HART
4 Endress+Hauser
9.5 Setting the operating language ........... 33
9.5.1 Local display ................... 33
9.5.2 FieldCare ..................... 33
9.5.3 DeviceCare .................... 33
9.6 Configuring the device .................. 34
9.6.1 Commissioning with DIP switch and
operating keys on the electronic
insert ........................ 34
9.6.2 Resetting the password or device via
operating keys ................. 35
9.6.3 Commissioning with "Commissioning"
wizard ....................... 35
9.6.4 Storing the oscillation frequencies ... 35
9.7 Simulation ........................... 35
9.8 Protecting settings from unauthorized
access .............................. 36
9.8.1 Locking or unlocking the hardware .. 36
9.8.2 Locking or unlocking the display
operation ..................... 36
9.8.3 Parameter configuration - locking or
enabling ...................... 36
10 Operation ......................... 37
10.1 Reading off the device locking status ....... 37
10.2 Reading off measured values ............. 37
10.3 Adapting the device to process conditions .... 37
10.3.1 Level limit detection ............. 37
10.3.2 Sensor frequency ................ 38
10.4 Heartbeat Technology (optional) .......... 38
10.4.1 Heartbeat Verification ............ 38
10.4.2 Heartbeat Verification/Monitoring .. 38
10.5 Proof testing for SIL/WHG devices (optional) .39
11 Diagnosis and troubleshooting ..... 39
11.1 General troubleshooting ................. 39
11.1.1 General errors .................. 39
11.1.2 Error - SmartBlue operation with
Bluetooth® .................... 40
11.1.3 Additional tests ................. 41
11.1.4 Behavior of current output in the
event of a fault ................. 41
11.2 Diagnostic information on local display ...... 41
11.2.1 Diagnostic message .............. 41
11.3 Diagnostic event in the operating tool ....... 43
11.4 Adapting the diagnostic information ....... 43
11.5 Queued diagnostic messages ............. 43
11.6 Diagnostic list ........................ 43
11.7 Event logbook ........................ 45
11.7.1 Event history ................... 45
11.7.2 Filtering the event logbook ........ 46
11.7.3 Overview of information events ..... 46
11.8 Resetting the device .................... 47
11.8.1 Resetting the device via the
operating software or display ....... 47
11.8.2 Resetting the device via operating
keys on the electronic insert ....... 47
11.9 Device information .................... 47
11.10 Firmware history ...................... 48
11.10.1 Version 01.00.zz ................ 48
12 Maintenance ...................... 48
12.1 Maintenance tasks .................... 48
12.1.1 Cleaning ...................... 48
13 Repair ............................ 48
13.1 General notes ........................ 48
13.1.1 Repair concept ................. 48
13.1.2 Repairs to Ex-approved devices ..... 48
13.2 Spare parts .......................... 49
13.3 Replacement ......................... 49
13.3.1 HistoROM ..................... 49
13.4 Return .............................. 49
13.5 Disposal ............................ 49
14 Accessories ....................... 50
14.1 Device Viewer ........................ 50
14.2 Protective cover for aluminum dual
compartment housing .................. 50
14.3 Protective cover for single compartment
housing, aluminum or 316L .............. 50
14.4 M12 socket .......................... 50
14.5 Sliding sleeves for unpressurized operation .. 51
14.6 High pressure sliding sleeves ............. 52
15 Technical data .................... 53
15.1 Input .............................. 53
15.1.1 Measured variable .............. 53
15.1.2 Measuring range ................ 53
15.2 Output ............................. 53
15.2.1 Output signal .................. 53
15.2.2 Signal on alarm ................. 54
15.2.3 Load ......................... 54
15.2.4 Damping ...................... 54
15.2.5 Switch output .................. 55
15.2.6 Ex connection data .............. 55
15.2.7 Protocol-specific data ............ 55
15.2.8 Wireless HART data ............. 56
15.2.9 Heartbeat Technology ............ 56
15.3 Environment ......................... 56
15.3.1 Ambient temperature range ....... 56
15.3.2 Storage temperature ............. 57
15.3.3 Humidity ..................... 57
15.3.4 Operating height ................ 57
15.3.5 Climate class .................. 57
15.3.6 Degree of protection ............. 57
15.3.7 Vibration resistance ............. 58
15.3.8 Shock resistance ................ 58
15.3.9 Mechanical load ................ 58
15.3.10 Pollution degree ................ 58
15.3.11 Electromagnetic compatibility
(EMC) ........................ 58
15.4 Process ............................. 59
15.4.1 Process temperature range ........ 59
Liquiphant FTL64 HART Table of contents
Endress+Hauser 5
15.4.2 Medium conditions .............. 59
15.4.3 Thermal shock ................. 59
15.4.4 Process pressure range ........... 59
15.4.5 Overpressure limit ............... 60
15.4.6 Medium density ................ 60
15.4.7 Viscosity ...................... 60
15.4.8 Pressure tightness .............. 60
15.4.9 Solids contents ................. 60
15.5 Additional technical data ................ 61
Index .................................. 62
About this document Liquiphant FTL64 HART
6 Endress+Hauser
1 About this document
1.1 Purpose of this document
These Operating Instructions contain all the information that is required in the various
phases of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols
1.2.1 Safety symbols
DANGER
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTICE
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
 Ground connection
Grounded clamp, which is grounded via a grounding system.
 Protective earth (PE)
Ground terminals, which must be grounded prior to establishing any other connections.
The ground terminals are located on the inside and outside of the device.
1.2.3 Tool symbols
 Flat-blade screwdriver
 Allen key
 Open-ended wrench
1.2.4 Communication-specific symbols
 Bluetooth
Wireless data transmission between devices over a short distance.
1.2.5 Symbols for certain types of information
  Permitted
Procedures, processes or actions that are permitted.
 Forbidden
Procedures, processes or actions that are forbidden.
Liquiphant FTL64 HART Basic safety instructions
Endress+Hauser 7
 Tip
Indicates additional information
 Reference to documentation
A
 Reference to another section
1.
,
2.
,
3.
 Series of steps
1.2.6 Symbols in graphics
A, B, C ...  View
1, 2, 3 ...  Item numbers
-
 Hazardous area
 Safe area (non-hazardous area)
1.2.7 Registered trademarks
HART®
Registered trademark of the FieldComm Group, Austin, Texas, USA
Bluetooth®
The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth
SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks
and trade names are those of their respective owners.
Apple®
Apple, the Apple logo, iPhone, and iPod touch are trademarks of Apple Inc., registered in
the U.S. and other countries. App Store is a service mark of Apple Inc.
Android®
Android, Google Play and the Google Play logo are trademarks of Google Inc.
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel must fulfill the following requirements to carry out the necessary tasks,
e. g., commissioning and maintenance:
Trained, qualified specialists must have a relevant qualification for the specific function
and task
Are authorized by the plant owner/operator
Are familiar with federal/national regulations
Must have read and understood the instructions in the manual and supplementary
documentation
Follow instructions and comply with conditions
2.2 Intended use
Only use the device for liquids
Improper use can pose hazards
Ensure that the measuring device is free of defects while it is in operation
Use the device only for media to which the wetted materials have an adequate level of
resistance
Do not exceed or drop below the relevant limit values for the device
A
 For more details, see the "Technical data" section
 See the Technical Documentation
Basic safety instructions Liquiphant FTL64 HART
8 Endress+Hauser
2.2.1 Incorrect use
The manufacturer is not liable for damage caused by improper or non-intended use.
Residual risks
Due to heat transfer from the process, the temperature of the electronics housing and the
assemblies contained therein may rise to 80 °C (176 °F) during operation.
Danger of burns from contact with surfaces!
If necessary, ensure protection against contact to prevent burns.
For requirements concerning functional safety in accordance with IEC 61508, the
associated SIL documentation must be observed.
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
regulations.
2.4 Operational safety
Risk of injury!
Operate the device only if it is in proper technical condition, free from errors and faults.
The operator is responsible for ensuring the interference-free operation of the device.
Modifications to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
Repair
To ensure continued operational safety and reliability:
Only perform repair work on the device if this is expressly permitted.
Observe federal/national regulations pertaining to the repair of an electrical device.
Use original spare parts and accessories from Endress+Hauser only.
Hazardous area
To eliminate danger to persons or the facility when the device is used in the hazardous
area (e.g. explosion protection):
Check the nameplate to verify whether the ordered device can be used for the intended
purpose in the hazardous area.
Observe the specifications in the separate supplementary documentation that is an
integral part of this manual.
2.5 Product safety
This device is designed in accordance with good engineering practice to meet state-of-the-
art safety requirements, has been tested, and left the factory in a condition in which it is
safe to operate.
It meets the general safety standards and legal requirements. It also complies with the EU
directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser
confirms this by affixing the CE mark to the device.
Liquiphant FTL64 HART Product description
Endress+Hauser 9
2.6 Functional Safety SIL (optional)
The Functional Safety Manual must be strictly observed for devices that are used in
functional safety applications.
2.7 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device has safety mechanisms integrated to prevent users
from inadvertently changing settings.
Provide additional protection for the device and data transfer to/from the device
IT security measures defined in the plant owner/operator's own security policy must be
implemented by plant owners/operators themselves.
2.8 Device-specific IT security
The device offers specific functions to support protective measures by the operator. These
functions can be configured by the user and guarantee greater in-operation safety if used
correctly. An overview of the most important functions is provided in the following section:
Write protection via hardware write protection switch
Access code (applies for operation via display, Bluetooth or FieldCare, DeviceCare, AMS,
PDM)
3 Product description
Point level switch for all liquids, for minimum or maximum detection in tanks, vessels
and pipes
Suitable for high-temperature applications up to 280 °C (536 °F)
Incoming acceptance and product identification Liquiphant FTL64 HART
10 Endress+Hauser
3.1 Product design
1
5
4
2
3 3
A0042420
 1 Product design
1 Housing with electronic insert and cover
2 Temperature spacer with gas-tight glass feedthrough → 2 lengths available, depending on the process
temperature
3 Process connection (flange or thread)
4 Probe design with compact version
5 Probe design, pipe extension
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
Check the following during incoming acceptance:
 Are the order codes on the delivery note and the product sticker identical?
 Are the goods undamaged?
 Do the data on the nameplate match the ordering information on the delivery note?
 If required (see nameplate): are the Safety Instructions e.g. XA provided?
If one of these conditions is not met, please contact the manufacturer's sales office.
Liquiphant FTL64 HART Incoming acceptance and product identification
Endress+Hauser 11
4.2 Product identification
The following options are available for identification of the device:
Nameplate data
Extended order code with breakdown of the device features on the delivery note
Enter serial number from nameplates in W@M Device Viewer
www.endress.com/deviceviewer. All of the information on the measuring device is
displayed along with an overview of the scope of technical documentation provided.
Enter the serial number on the nameplate into the Endress+Hauser Operations app or
scan the 2-D matrix code on the nameplate with the Endress+Hauser Operations app
4.2.1 Nameplate
The information that is required by law and is relevant to the device is shown on the
nameplate, e.g.:
Manufacturer identification
Order number, extended order code, serial number
Technical data, degree of protection
Firmware version, hardware version
Approval-related information, reference to Safety Instructions (XA)
DataMatrix code (information about the device)
4.2.2 Manufacturer address
Endress+Hauser SE+Co. KG
Hauptstraße 1
79689 Maulburg, Germany
Place of manufacture: See nameplate.
4.3 Storage and transport
4.3.1 Storage conditions
Use original packaging.
Storage temperature
–40 to +80 °C (–40 to +176 °F)
Optional –50 °C (–58 °F) or –60 °C (–76 °F)
4.3.2 Transporting the device
Transport the device to the measuring point in the original packaging
Hold the device by the housing, temperature spacer, flange or extension pipe
Take suitable measures to protect the coating!
Do not bend, shorten or extend the tuning fork
Mounting Liquiphant FTL64 HART
12 Endress+Hauser
A0042422
 2 Handling the device during transportation
5 Mounting
Mounting instructions
Any orientation for version with a pipe length of up to 500 mm (19.7 in) approx.
Vertical orientation from above for device with long pipe
Minimum distance between the tuning fork and the tank wall or pipe wall:
10 mm (0.39 in)
A0042329
 3 Installation examples for a vessel, tank or pipe
5.1 Mounting requirements
NOTICE
Scratches or impacts damage the coated surface of the device.
Ensure the device is handled properly and professionally during all mounting work.
5.1.1 Pay attention to the temperature for devices with a PFA
coating (conductive)
The difference in temperature between the outer and inner side of the flange may not
exceed 60 °C (140 °F).
Liquiphant FTL64 HART Mounting
Endress+Hauser 13
If necessary, use external insulation.
A
B
BA
-
C
1C
=
A0042298
 4 Difference in temperature between outer and inner side of flange
1 Insulation
A Temperature of flange, outer side
B Temperature of flange, inner side, for PFA (conductive) maximum 230 °C (446 °F)
C Difference in temperature for PFA (conductive) maximum 60 °C (140 °F)
5.1.2 Take switch point into consideration
The following are typical switch points, depending on the orientation of the point level
switch
Water +23 °C (+73 °F)
Minimum distance between the tuning fork and the tank wall or pipe wall:
10 mm (0.39 in)
~13 (0.5)
~5 (0.2)
~12.5 (0.49)
D
A B C
D
D
A0044069
 5 Typical switch points. Unit of measurement mm (in)
A Installation from above
B Installation from below
C Installation from the side
D Switch point
5.1.3 Take viscosity into consideration
Viscosity values
Low viscosity : < 2 000 mPa⋅s
High viscosity: > 2 000 to 10 000 mPa⋅s
Low viscosity
Low viscosity, e.g. water: < 2 000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.
Mounting Liquiphant FTL64 HART
14 Endress+Hauser
> 25 (0.98)
> !50 (1.97)
A0042333
 6 Installation example for low-viscosity liquids. Unit of measurement mm (in)
High viscosity
NOTICE
Highly viscous liquids may cause switching delays.
Make sure that the liquid can run off the tuning fork easily.
Deburr the socket surface.
High viscosity, e.g. viscous oils: ≤ 10 000 mPa⋅s
The tuning fork must be located outside the installation socket!
> 40 (1.57)
A0042335
 7 Installation example for a highly viscous liquid. Unit of measurement mm (in)
5.1.4 Avoid buildup
Use short installation sockets to ensure that the tuning fork projects freely into the
vessel
Leave sufficient distance between the buildup expected on the tank wall and the tuning
fork
Liquiphant FTL64 HART Mounting
Endress+Hauser 15
A0042345
 8 Installation examples for a highly viscous process medium
5.1.5 Take clearance into consideration
Allow sufficient space outside the tank for mounting, connection and settings involving
the electronic insert.
A0042340
 9 Take clearance into consideration
5.1.6 Support the device
NOTICE
If the device is supported incorrectly, shocks and vibrations can damage the coated
surface.
Use suitable supports only.
Support the device in the event of severe dynamic load. Maximum lateral loading capacity
of the pipe extensions and sensors: 75 Nm (55 lbf ft).
Mounting Liquiphant FTL64 HART
16 Endress+Hauser
A0042356
 10 Examples of support in the event of dynamic load
Marine approval: In the case of pipe extensions or sensors longer than
1 600 mm (63 in), a support is needed at least every 1 600 mm (63 in).
5.2 Mounting the device
5.2.1 Required tool
Open-ended wrench for sensor installation
Allen key for housing locking screw
5.2.2 Installation
Aligning the tuning fork using the marking
The tuning fork can be aligned using the marking in such a way that the medium drains
off easily and buildup is avoided.
Markings are identified on the process connection by:
Material specification, thread designation, circle, line or double line
316L/G1
A0042348
 11 Position of the tuning fork when installed horizontally in the vessel using the marking
Liquiphant FTL64 HART Mounting
Endress+Hauser 17
Installing the device in piping
Flow velocity up to 5 m/s with a viscosity of 1 mPa⋅s and density of 1 g/cm³ (62.4 lb/ft³)
(SGU).
Check for correct functioning in the event of other process medium conditions.
The flow will not be significantly impeded if the tuning fork is correctly aligned and the
marking is pointing in the direction of flow.
The marking is visible when installed
A0034851
 12 Installation in pipes (take fork position and marking into consideration)
Screwing in the device
Turn by the hex bolt only, 15 to 30 Nm (11 to 22 lbf ft)
Do not turn at the housing!
1.
2.
A0042423
 13 Screwing in the device
Mounting Liquiphant FTL64 HART
18 Endress+Hauser
Aligning the cable entry
2.
3.
43.5 Nm
1.
A0042355
 14 Housing with external locking screw and drip loop
Housings with locking screw:
The housing can be turned and the cable aligned by turning the locking screw.
The locking screw is not tightened when the device is delivered.
1. Loosen the external locking screw (maximum 1.5 turns).
2. Turn the housing, align the cable entry.
Avoid moisture in the housing, provide a loop to allow moisture to drain off.
3. Tighten the external locking screw.
Turning the housing
The housing can be rotated up to 380° by loosening the locking screw.
NOTICE
The housing cannot be unscrewed fully.
Loosen the external locking screw by a maximum of 1.5 turns. If the screw is
unscrewed too much or completely (beyond the screw anchor point), small parts
(counter disk) can become loose and fall out.
Tighten the securing screw (hexagon socket 4 mm (0.16 in)) with maximum
3.5 Nm (2.58 lbf ft)±0.3 Nm (±0.22 lbf ft).
Closing the housing covers
NOTICE
Thread and housing cover damaged from dirt and fouling!
Remove dirt (e.g. sand) on the thread of the covers and housing.
If you continue to encounter resistance when closing the cover, check the thread again
for fouling.
Housing thread
The threads of the electronics and connection compartment can be coated with an
anti-friction coating.
The following applies for all housing materials:
Do not lubricate the housing threads.
Liquiphant FTL64 HART Mounting
Endress+Hauser 19
Turning the display module
LWARNING
Supply voltage switched on!
Risk of electric shock and/or explosion!
Switch off the supply voltage before opening the device.
2.
1.
40.7 Nm
3.
4.
A0038224
1. If fitted: release the screw of the cover lock for the electronics compartment cover
using the Allen key.
2. Unscrew the cover from the housing and inspect the cover seal.
3. Press the release mechanism and remove the display module.
4. Turn the display module to the desired position: maximum 4 × 90 ° in each direction.
Insert the display module into the desired position until it clicks into place. Screw the
cover tightly back onto the housing. If fitted: tighten the screw of the cover lock using
the Allen key 0.7 Nm (0.52 lbf ft) ±0.2 Nm (±0.15 lbf ft).
In the case of a dual-compartment housing, the display can be mounted in the
electronics compartment as well as in the connection compartment.
5.3 Sliding sleeves
A
 For more details, see the "Accessories" section.
5.4 Post-mounting check
 Is the device undamaged (visual inspection)?
 Does the measuring device meet the measuring point specifications?
For example:
Process temperature
Process pressure
Ambient temperature
Measuring range
 Are the measuring point number and labeling correct (visual inspection)?
 Is the device adequately protected from wet conditions and direct sunlight?
 Is the device properly secured?
Electrical connection Liquiphant FTL64 HART
20 Endress+Hauser
6 Electrical connection
6.1 Required tool
Screwdriver for electrical connection
Allen key for screw of cover lock
6.2 Connecting requirements
6.2.1 Cover with securing screw
The cover is locked by a securing screw in devices for use in hazardous areas with certain
explosion protection.
NOTICE
If the securing screw is not positioned correctly, the cover cannot provide secure
sealing.
Open the cover: slacken the screw of the cover lock with a maximum of 2 turns so that
the screw does not fall out. Fit the cover and check the cover seal.
Close the cover: screw the cover securely onto the housing, making sure that the
securing screw is positioned correctly. There should not be any gap between the cover
and housing.
2 x 0.7 Nm
4
A0039520
 15 Cover with securing screw
6.2.2 Potential equalization
LWARNING
Explosion Hazard!
Please refer to the separate documentation on applications in hazardous areas for the
safety instructions.
1
A0045830
1 Ground terminal for connecting the potential matching line
If necessary, the potential matching line can be connected to the external ground
terminal of the transmitter before the device is connected.
For optimum electromagnetic compatibility:
Potential matching line as short as possible
Observe a cross-section of at least 2.5 mm2 (14 AWG)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64