Micropilot M FMR240, 244, 245, 250 HART, PROFIBUS PA, FOUNDATION Fieldbus

Endres+Hauser Micropilot M FMR240, 244, 245, 250 HART, PROFIBUS PA, FOUNDATION Fieldbus Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Endres+Hauser Micropilot M FMR240, 244, 245, 250 HART, PROFIBUS PA, FOUNDATION Fieldbus Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
BA291F/00/en/11.05
Valid as of software version:
V 01.04.00 (amplifier)
V 01.04.00 (communication)
Description of Instrument Functions
Micropilot M FMR250
Level-Radar
6
8
Basic Setup Micropilot M
2Endress+Hauser
Basic Setup
SD
SD
F
F
L
L
D
D
E
E
flange:
reference point of
measurement
flange:
reference point of
measurement
tank shape
dome ceiling
vessel / silo
metal silo
media type media type
liquid solid
measuring cond.
Unknown
measuring cond.
Unknown
measuring cond.
Standard
measuring cond.
Standard
pipe diameter
mapping
mapping
safety settings
linearisation
extended calibr.
...
empty calibr. empty calibr.
full calibr. full calibr.
(for bypass/stilling well)
(description see BA 291F)
E = empty calibr. (= zero), setting in 005
F = full calibr. (= span), setting in 006
D = distance (distance flange / product), display in 0A5
L = level, display in 0A6
SD = safety distance, setting in 015
basic setup (standard - liquids)
basic setup (standard - solids)
option
level measurement in liquids
level measurement in solids
Micropilot M Table of contents
Endress+Hauser 3
Table of contents
1 Notes on use . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Using the table of contents to locate a function
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Using the graphic of the function menu to locate
a function description . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Using the index of the function menu to locate
a function description . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 General structure of the operating menu . . . . . . . . . 6
1.5 Display and operating elements . . . . . . . . . . . . . . . . 7
1.6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Function menu Micropilot M . . . . . . . . 11
3 Function group
"basic setup" (00) . . . . . . . . . . . . . . . . . . 14
3.1 Function "measured value" (000) . . . . . . . . . . . . . . 14
3.2 Function "media type" (001) . . . . . . . . . . . . . . . . . 14
3.3 Function "tank shape" (002),
liquids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4 Function "medium property" (003),
liquids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.5 Function "process cond." (004),
liquids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6 Function "vessel / silo" (00A),
solids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.7 Function "medium property" (00B),
solids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.8 Function "process cond." (00C),
solids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.9 Function "empty calibr." (005) . . . . . . . . . . . . . . . . 20
3.10 Function "full calibr." (006) . . . . . . . . . . . . . . . . . . 21
3.11 Function "pipe diameter" (007),
liquids only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.12 Display (008) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.13 Function "check distance" (051) . . . . . . . . . . . . . . 23
3.14 Function "range of mapping" (052) . . . . . . . . . . . . 24
3.15 Function "start mapping" (053) . . . . . . . . . . . . . . . 24
3.16 Display (008) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4 Function group
"safety settings" (01) . . . . . . . . . . . . . . . . 26
4.1 Function "output on alarm" (010) . . . . . . . . . . . . . 26
4.2 Function "output on alarm" (011), HART only . . . . 28
4.3 Function "outp. echo loss" (012) . . . . . . . . . . . . . . 28
4.4 Function "ramp %span/min" (013) . . . . . . . . . . . . 29
4.5 Function "delay time" (014) . . . . . . . . . . . . . . . . . . 30
4.6 Function "safety distance" (015) . . . . . . . . . . . . . . . 30
4.7 Function "in safety dist." (016) . . . . . . . . . . . . . . . . 30
4.8 Function "ackn. alarm" (017) . . . . . . . . . . . . . . . . . 32
4.9 Function "overspill prot." (018) . . . . . . . . . . . . . . . 32
5 Function group
"linearisation" (04) . . . . . . . . . . . . . . . . . 33
5.1 Function "level/ullage" (040) . . . . . . . . . . . . . . . . . 33
5.2 Function "linearisation" (041) . . . . . . . . . . . . . . . . . 34
5.3 Function "customer unit" (042) . . . . . . . . . . . . . . . 38
5.4 Function "table no." (043) . . . . . . . . . . . . . . . . . . . 39
5.5 Function "input level" (044) . . . . . . . . . . . . . . . . . . 39
5.6 Function "input volume" (045) . . . . . . . . . . . . . . . . 40
5.7 Function "max. scale" (046) . . . . . . . . . . . . . . . . . . 40
5.8 Function "diameter vessel" (047) . . . . . . . . . . . . . . 40
6 Function group
"extended calibr." (05) . . . . . . . . . . . . . 41
6.1 Function "selection" (050) . . . . . . . . . . . . . . . . . . . 41
6.2 Function "check distance" (051) . . . . . . . . . . . . . . . 41
6.3 Function "range of mapping" (052) . . . . . . . . . . . . . 42
6.4 Function "start mapping" (053) . . . . . . . . . . . . . . . 43
6.5 Function "pres. map dist." (054) . . . . . . . . . . . . . . . 43
6.6 Function "cust. tank map" (055) . . . . . . . . . . . . . . . 44
6.7 Function "echo quality" (056) . . . . . . . . . . . . . . . . . 44
6.8 Function "offset" (057) . . . . . . . . . . . . . . . . . . . . . . 45
6.9 Function "antenna extens." (0C9) . . . . . . . . . . . . . 45
6.10 Function "output damping" (058) . . . . . . . . . . . . . . 45
6.11 Function "blocking dist." (059) . . . . . . . . . . . . . . . . 46
7 Function group "output" (06),
- "profibus param." (06),
PROFIBUS PA only . . . . . . . . . . . . . . . . . 47
7.1 Function "commun. address" (060),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.2 Function "instrument addr." (060),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 47
7.3 Function "no. of preambels" (061),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.4 Function "ident number" (061),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 48
7.5 Function "low output limit" (062),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.6 Function "set unit to bus" (062),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 49
7.7 Funktion "curr.output mode" (063),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.8 Function "out value" (063),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 50
7.9 Function "fixed cur. value" (064),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.10 Function "out status" (064),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 51
7.11 Function "simulation" (065) . . . . . . . . . . . . . . . . . . 52
7.12 Function "simulation value" (066) . . . . . . . . . . . . . 53
7.13 Function "output current" (067),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table of contents Micropilot M
4Endress+Hauser
7.14 Function "2nd cyclic value" (067),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 54
7.15 Function "4mA value" (068),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.16 Function "select v0h0" (068),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 55
7.17 Function "20mA value" (069),
HART only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.18 Function "display value" (069),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 56
8 Function group
"envelope curve" (0E) . . . . . . . . . . . . . . . 57
8.1 Function "plot settings" (0E1) . . . . . . . . . . . . . . . . 57
8.2 Function "recording curve" (0E2) . . . . . . . . . . . . . 57
8.3 Function "envelope curve display" (0E3) . . . . . . . . 58
9 Function group
"display" (09) . . . . . . . . . . . . . . . . . . . . . . 60
9.1 Function "language" (092) . . . . . . . . . . . . . . . . . . 60
9.2 Function "back to home" (093) . . . . . . . . . . . . . . . 60
9.3 Function "format display" (094) . . . . . . . . . . . . . . 61
9.4 Function "no.of decimals" (095) . . . . . . . . . . . . . . 61
9.5 Function "sep. character" (096) . . . . . . . . . . . . . . . 61
9.6 Function "display test" (097) . . . . . . . . . . . . . . . . . 62
10 Function group
"diagnostics" (0A) . . . . . . . . . . . . . . . . . . 63
10.1 Function "present error" (0A0) . . . . . . . . . . . . . . . 64
10.2 Function "previous error" (0A1) . . . . . . . . . . . . . . 64
10.3 Function "clear last error" (0A2) . . . . . . . . . . . . . . 64
10.4 Function "reset" (0A3) . . . . . . . . . . . . . . . . . . . . . 65
10.5 Function "unlock parameter" (0A4) . . . . . . . . . . . . 66
10.6 Function "measured dist." (0A5) . . . . . . . . . . . . . . 67
10.7 Function "measured level" (0A6) . . . . . . . . . . . . . . 68
10.8 Function "detection window" (0A7) . . . . . . . . . . . 68
10.9 Function "application par." (0A8) . . . . . . . . . . . . . 69
11 Function group
"system parameters" (0C) . . . . . . . . . . . 70
11.1 Function "tag no." (0C0) . . . . . . . . . . . . . . . . . . . . 70
11.2 Function "Profile Version" (0C1),
PROFIBUS PA only . . . . . . . . . . . . . . . . . . . . . . . . 70
11.3 Function "protocol+sw-no." (0C2) . . . . . . . . . . . . 70
11.4 Function "serial no." (0C4) . . . . . . . . . . . . . . . . . . 71
11.5 Function "distance unit" (0C5) . . . . . . . . . . . . . . . 71
11.6 Function "download mode" (0C8) . . . . . . . . . . . . . 72
11.7 Function "antenna extens." (0C9) . . . . . . . . . . . . . 72
12 Function group "service" (0D) . . . . . . . 73
12.1 Software history . . . . . . . . . . . . . . . . . . . . . . . . . . 73
13 Envelope curve . . . . . . . . . . . . . . . . . . . . . 74
14 Trouble-shooting . . . . . . . . . . . . . . . . . . . 78
14.1 Trouble-shooting instructions . . . . . . . . . . . . . . . . 79
14.2 System error messages . . . . . . . . . . . . . . . . . . . . . 80
14.3 Application errors in liquids . . . . . . . . . . . . . . . . . 82
14.4 Application errors in solids . . . . . . . . . . . . . . . . . . 84
14.5 Orientation of the Micropilot . . . . . . . . . . . . . . . . . 86
Index function menu . . . . . . . . . . . . . . . . . . 89
Micropilot M 1 Notes on use
Endress+Hauser 5
1Notes on use
You have various options for accessing the descriptions of instrument functions or how to enter
parameters.
1.1 Using the table of contents to locate a function
description
All the functions are listed in the table of contents sorted by function group (e.g. basic setup,
safety settings, etc.). You can access a more detailed description of a function by using a page
reference / link.
The table of contents is on page 3.
1.2 Using the graphic of the function menu to locate a
function description
This guides you step by step from the highest level, the function groups, to the exact function
description you require.
All the available function groups and instrument functions are listed in the table (see page 11).
Select your required function group or function. You can access an exact description of the function
group or function by using a page reference / link.
1.3 Using the index of the function menu to locate a
function description
To simply navigation within the function menu, each function has a position which is shown in the
display. You can access each function via a page reference/link in the function menu index (see
page 89) which lists all the function names alphabetically and numerically.
!Note!
The default values of the parameters are typed in boldface.
1 Notes on use Micropilot M
6Endress+Hauser
1.4 General structure of the operating menu
The operating menu is made up of two levels:
Function groups (00, 01, 03, …, 0C, 0D):
The individual operating Selection of the instrument are split up roughly into different function
groups. The function groups that are available include, e.g.: "basic setup", "safety settings",
"output", "display", etc.
Functions (001, 002, 003, …, 0D8, 0D9):
Each function group consists of one or more functions. The functions perform the actual operation
or parameterisation of the instrument. Numerical values can be entered here and parameters can
be selected and saved. The available functions of the “basic setup (00)” function group include,
e.g.: "tank shape (002)",
"medium property (003)", "process cond. (004)", "empty calibr. (005)", etc.
If, for example, the application of the instrument is to be changed, carry out the following
procedure:
1. Select the “basic setup (00)” function group.
2. Select the "tank shape (002)" function (where the existing tank shape is selected).
1.4.1 Identifying the functions
For simple orientation within the function menus (see Page 11 ff.), for each function a position is
shown on the display.
The first two digits identify the function group:
The third digit numbers the individual functions within the function group:
Hereafter the position is always given in brackets (e.g. "tank shape" (002)) after the described
function.
•basic setup 00
• safety settings 01
• linearisation 04
•basic setup 00 • tank shape 002
• medium property 003
• process cond. 004
Micropilot M 1 Notes on use
Endress+Hauser 7
1.5 Display and operating elements
Fig. 1: Layout of the display and operating elements
1.5.1 Display
Liquid crystal display (LCD):
Four lines with 20 characters each. Display contrast adjustable through key combination.
Fig. 2: Display
ENDRESS + HAUSER
E
+
ENDRESS+HAUSER
MICROPILOTII
ENDRESS+HAUSER
MICROPILOTII
IP65
IP65
OrderCode:
Ser.-No.:
OrderCode:
Ser.-No.:
Messbereich
Measuringrange
Messbereich
Measuringrange
U16...36VDC
4...20mA
U16...36VDC
4...20mA
max.20m
max.20m
MadeinGermany Maulburg
MadeinGermany Maulburg
T>
70°C:
At>85°C
T>
70°C:
At>85°C
LCD
(liquid crystal display)
Symbols
3 keys
snap-fit
X
X
X
X
S
S
O
OFF
F
F
HOME
FG00 F000 F001 F002 F003 F004 ...
FG01
FG02
FG03
FG04
FG05
FG06
FG07
...
+21dB 09C
10.002.305m
0.00
ENDRESS + HAUSER
E
+
Headline Position indicator
Main value
Unit
Symbol
Selection list
Function groups -> Functions
Help text
Envelope
curve
Bargraph
1 Notes on use Micropilot M
8Endress+Hauser
1.5.2 Display symbols
The following table describes the symbols that appear on the liquid crystal display:
Tab. 1-1Meaning of Symbols
1.5.3 Key assignment
The operating elements are located inside the housing and are accessible for operation by opening
the lid of the housing.
Function of the keys
Tab. 1-2Function of the keys
Symbols Meaning
ALARM_SYMBOL
This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates
a warning.
LOCK_SYMBOL
This lock symbol appears when the instrument is locked,i.e. if no input is possible.
COM_SYMBOL
This communication symbol appears when a data transmission via e.g. HART, PFOFIBUS-PA or
Foundation Fieldbus is in progress.
Key(s) Meaning
O or VNavigate upwards in the selection list
Edit numeric value within a function
S or WNavigate downwards in the selection list
Edit numeric value within a function
X or ZNavigate to the left within a function group
F or MNavigate to the right within a function group, confirmation.
O and F
or
S and FContrast settings of the LCD
O and S and F
Hardware lock / unlock
After a hardware lock, an operation of the instrument via display or
communication is not possible!
The hardware can only be unlocked via the display. An unlock parameter must
be entered to do so.
Micropilot M 1 Notes on use
Endress+Hauser 9
1.5.4 Operation with the VU 331
Fig. 3: Selection and configuration in operation menu
ENDRESS + HAUSER
E
+
XX
X
X
X
SS
S
S
S
S
O
O
O
O
O
O
F
F
F
F
F
>3 s
F
...
...
3x
...
...
unknown
DC: < 1.9
DC: 1.9 ... 4
DC: 4 ... 10
DC: > 10
unknown
DC: 1.6...1.9
DC: 1.9...2.5
DC: 2.5...4
DC: 4...7
DC: > 7
Example - Selection and configuration in Operation menu:
Group Selection
Function Group
unction
Note!
Selection menus:
function
Typing in numerals and text:
numeral / text
function
function
Group selection
Measured value display
1.) Change from Measured Value Display to by pressing
2.) Press or to select the required (e.g.. "basic setup (00)") and confirm by pressing
(e.g. "tank shape (002)") is selected.
The active selection is marked by a in front of the menu text.
3.) Activate Edit mode with or .
a) Select the required in selected (e.g. "tank shape (002)") with or .
b) confirms selection appears in front of the selected parameter
c) confirms the edited value system quits Edit mode
d) + (= ) interrupts selection system quits Edit mode
a) Press or to edit the first character of the (e.g. "empty calibr. (005)")
b) positions the cursor at the next character (a) until you have completed your input
c) if a symbol appears at the cursor, press to accept the value entered
system quits Edit mode
d) + (= ) interrupts the input,
4) Press to select the next (e.g. "medium property (003)")
5) Press + (= ) once return to previous (e.g. "tank shape (002)")
Press + (= ) twice return to
6) Press + (= ) to return to
F
SO
O
SO
F
S
X
S
F
S
F
F
OS X
OS
F
OX
F
OS X
OS
OX
Ü
Ü
Ü
Ü
Ü
Ü
Ü
First f
continue with
system quits Edit mode
Ü
Parameter
Return to
Group Selection
basic setup
safety settings
linearisation
tank shape
vessel / silo
dome ceiling
horizontal cyl
bypass
stilling well
flat ceiling
sphere
medium property
medium property
media type
liquids
solids
unknown
metal silo
concrete silo
bin / bunker
dome
stockpile
conveyor belt
extended calibr.
1 Notes on use Micropilot M
10 Endress+Hauser
1.6 Commissioning
1.6.1 Switching on the measuring device
When the instrument is switched on for the first time, the following messages appear on the display:
After 5 s, the following message appears
After 5 s, the following message appears
After 5 s or after you have pressed F the following
message appears
Select the language
(this message appears the first time the instrument is
switched on)
Select the basic unit
(this message appears the first time the instrument is
switched on)
The current measured value is displayed
After F is pressed, you reach the group selection.
This selection enables you to perform the basic setup
ENDRESS + HAUSER
E
+
Micropilot M 2 Function menu Micropilot M
Endress+Hauser 11
2 Function menu Micropilot M
Basic Setup in liquids
Function group Function Description
basic setup 00 measured value 000 Page 14
(see page 14) media type liquid 001 Page 14
tank shape 002 Page 15
medium property 003 Page 18
process cond. 004 Page 19
empty calibr. 005 Page 20
full calibr. 006 Page 21
pipe diameter 007 Page 22
check distance 051 Page 23
range of mapping 052 Page 24
start mapping 053 Page 24
Basic Setup in solids
Function group Function Description
basic setup 00 measured value 000 Page 14
(see page 14) media type solid 001 Page 14
vessel / silo 00A Page 18
medium property 00B Page 18
process cond. 00C Page 19
empty calibr. 005 Page 20
full calibr. 006 Page 21
check distance 051 Page 23
range of mapping 052 Page 24
start mapping 053 Page 24
Further Functions
Function group Function Description
safety settings 01 output on alarm 010 Page 26
(see page 26) output on alarm (HART only) 011 Page 28
outp. echo loss 012 Page 28
ramp %span/min 013 Page 29
delay time 014 Page 30
safety distance 015 Page 30
in safety dist. 016 Page 30
ackn. alarm 017 Page 32
overspill prot. 018 Page 32
linearisation 04 level/ullage 040 Page 33
(see page 33) linearisation 041 Page 34
customer unit 042 Page 38
table no. 043 Page 39
input level 044 Page 39
input volume 045 Page 40
max. scale 046 Page 40
diameter vessel 047 Page 40
2 Function menu Micropilot M Micropilot M
12 Endress+Hauser
Further Functions
Function group Function Description
extended calibr. 05 selection 050 Page 41
(see page 41) check distance 051 Page 41
range of mapping 052 Page 42
start mapping 053 Page 43
pres. map dist. 054 Page 43
cust. tank map 055 Page 43
echo quality 056 Page 44
offset 057 Page 45
antenna extens. 0C9 Page 45
output damping 058 Page 45
blocking dist. 059 Page 46
output 06 commun. address (HART only) 060 Page 47
Profibus Param. 06 instrument addr. (PROFIBUS PA only) 060 Page 47
nur PROFIBUS PA no. of preambels (HART only) 061 Page 48
(see page 47) ident number (PROFIBUS PA only) 061 Page 48
low output limit (HART only) 062 Page 49
set unit to bus (PROFIBUS PA only) 062 Page 49
curr.output mode (HART only) 063 Page 50
out value (PROFIBUS PA only) 063 Page 50
fixed cur. value (HART only) 064 Page 51
out status (PROFIBUS PA only) 064 Page 51
simulation 065 Page 52
simulation value 066 Page 52
output current (HART only) 067 Page 52
2nd cyclic value (PROFIBUS PA only) 067 Page 54
4mA value (HART only) 068 Page 55
select v0h0 (PROFIBUS PA only) 068 Page 55
20mA value (HART only) 069 Page 56
display value (PROFIBUS PA only) 069 Page 56
envelope curve 0E plot settings 0E1 Page 57
(see page 57) recording curve 0E2 Page 57
envelope curve display 0E3 Page 58
display 09 language 092 Page 60
(see page 60) back to home 093 Page 60
format display 094 Page 61
no.of decimals 095 Page 61
sep. character 096 Page 61
display test 097 Page 62
Micropilot M 2 Function menu Micropilot M
Endress+Hauser 13
Further Functions
Function group Function Description
diagnostics 0A present error 0A0 Page 64
(see page 63) previous error 0A1 Page 64
clear last error 0A2 Page 64
reset 0A3 Page 65
unlock parameter 0A4 Page 66
measured dist. 0A5 Page 67
measured level 0A6 Page 68
detection window 0A7 Page 68
application par. 0A8 Page 69
system parameters 0C tag no. 0C0 Page 70
(see page 70) Profile Version (PROFIBUS PA only) 0C1 Page 70
protocol+sw-no. 0C2 Page 70
serial no. 0C4 Page 71
distance unit 0C5 Page 71
download mode 0C8 Page 72
antenna extens. 0C9 Page 45
service D00 service level D00 Page 73
3 Function group "basic setup" (00) Micropilot M
14 Endress+Hauser
3 Function group "basic setup" (00)
3.1 Function "measured value" (000)
This function displays the current measured value in the selected unit
(see "customer unit"(042) function). The number of digits after decimal point can be selected in
the "no.of decimals"(095) function.
3.2 Function "media type" (001)
This function is used to select the media type.
Selection:
• liquid
•solid
ENDRESS + HAUSER
E
+
ENDRESS + HAUSER
E
+
ENDRESS + HAUSER
E
+
With the selection "liquid" only
the following functions can be
adjusted:
With the selection "solid" only
the following functions can be
adjusted:
• tank shape 002 vessel / silo 00A
• medium property 003 • medium property 00B
• process cond. 004 process cond. 00C
• empty calibr. 005 • empty calibr. 005
• full calibr. 006 full calibr. 006
• pipe diameter 007 • check distance 051
• check distance 051 range of mapping 052
• range of mapping 052 • start mapping 053
• start mapping 053 • …
•…
Micropilot M 3 Function group "basic setup" (00)
Endress+Hauser 15
3.3 Function "tank shape" (002), liquids only
This function is used to select the tank shape.
Selection:
• dome ceiling
• horizontal cyl
•bypass
• stilling well
• flat ceiling
•sphere
ENDRESS + HAUSER
E
+
3 Function group "basic setup" (00) Micropilot M
16 Endress+Hauser
3.4 Function "medium property" (003), liquids only
This function is used to select the dielectric constant.
Selection:
• unknown
•DC: < 1.9
• DC: 1.9 ... 4
• DC: 4 ... 10
•DC: > 10
1) Treat Ammonia NH3 as a medium of group A, i.e. use FMR 230 in a stilling well.
ENDRESS + HAUSER
E
+
Product class DC (εr) Examples
A1,4 … 1,9 non-conducting liquids, e.g. liquefied gas 1)
B1,9 … 4 non-conducting liquids, e.g. benzene, oil, toluene, …
C4 … 10 e.g. concentrated acids, organic solvents, esters, aniline, alcohol, acetone,
D> 10 conducting liquids, e.g. aqueous solutions, dilute acids and alkalis
Micropilot M 3 Function group "basic setup" (00)
Endress+Hauser 17
3.5 Function "process cond." (004), liquids only
This function is used to select the process conditions.
Selection:
•standard
• calm surface
• turb. surface
• add. agitator
• fast change
• test:no filter
ENDRESS + HAUSER
E
+
standard calm surface turb. surface
For all applications that do not fit into
any of the following groups.
Storage tanks with immersion tube or
bottom filling
Storage / buffer tanks with rough
surface due to free filling or mixer
nozzles
The filter and output damping are set
to average values.
The averaging filters and output
damping are set to high values.
-> steady meas. value
-> precise measurement
-> slower reaction time
Special filters to smooth the input
signals are emphasised.
-> smoothed meas. value
-> medium fast reaction time
add. agitator fast change test:no filter
Agitated surfaces (with possible
vortex) due to agitators
Fast change of level, particularly in
small tanks
All filters can be switched off for
service / diagnostic purposes.
Special filters to smooth the input
signals are set to high values.
->smoothed meas. value
->medium fast reaction time
->minimization of effects by
agitator blades
The averaging filters are set to low
values. The output damping is set to
0.
-> rapid reaction time
-> possibly unsteady meas. value
All filters off.
3 Function group "basic setup" (00) Micropilot M
18 Endress+Hauser
3.6 Function "vessel / silo" (00A), solids only
This function is used to select the vessel / silo.
Selection:
• unknown
•metal silo
• concrete silo
•bin / bunker
•dome
• stockpile
• conveyor belt
3.7 Function "medium property" (00B), solids only
This function is used to select the dielectric constant.
Selection:
• unknown
• DC: 1.6 ... 1.9
• DC: 1.9 ... 2.5
• DC: 2.5 ... 4
• DC: 4 ... 7
•DC: > 7
The respective lower group applies for very loose or loosened bulk solids.
ENDRESS + HAUSER
E
+
ENDRESS + HAUSER
E
+
Product class DC (εr) Examples
A1.6 … 1.9 Plastic granulate
White lime, special cement
–Sugar
B1.9 … 2.5 Portland cement, plaster
C2.5 … 4 Grain, seeds
–Ground stones
–Sand
D4 ... 7 Naturally moist (ground) stones, ores
–Salt
E> 7 Metallic powder
Carbon black
–Coal
Micropilot M 3 Function group "basic setup" (00)
Endress+Hauser 19
3.8 Function "process cond." (00C), solids only
This function is used to select the process conditions.
Selection:
•standard
• fast change
• slow change
• test: no filter
ENDRESS + HAUSER
E
+
3 Function group "basic setup" (00) Micropilot M
20 Endress+Hauser
3.9 Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the measurement) to
the minimum level (=zero).
"Caution!
For dish bottoms or conical outlets, the zero point should be no lower than the point at which the
radar beam hits the bottom of the vessel.
ENDRESS + HAUSER
E
+
/