5.SERVICESCHEDULE
Table1
TaskPeriodicity
1.Inspectionforvisiblephysicaldamageweekly
2.Satisfactoryoperationtest monthly
3.Checkandcleandustcontaminationevery6months
4.CheckandcleanbaseandheadcontactsandconnectionsAnnually
6.WARRANTY
ThemanufacturerguaranteesproductcompliancewiththeEN54-7:2001.Thewarrantperiodis36
monthsfromthedateofpurchase,providingthatrequirementscoveredinsection5havebeen
observed.

UniPOSLtd
SHORTCIRCUITISOLATOR
WITHSURGEPROTECTOR

TYPE6202-4
1.INTRODUCTION
Shortcircuitisolator6202-4isdesignedtocutoff(toisolate)ashortcircuitedlineorloop.The
isolatorshouldbemountedinimmediatevicinityoffirecontrolpanelFS6000,atthebeginningofa
firealarmline(loop)andattheendofeachloop.6202-4isanintermediateunitandseparatesthe
loopintosegments.Inthiswaythevariableunitsñautomaticfiredetectors,manualcallpointsand
others,whicharenotintheshortcircuitedsegmentremainactiveandtheline(loop)protection
levelishigher.Whereisolatorsarenotincluded,incaseofashortcircuitthefirecontrolpanel
interruptsthepowersupplyoftheline(loop)andallunitsstopworking.
Asegmentisapartofaloopbetweentwoadjacentisolators.
Shortcircuitisolator6202-4issuppliedwithabuildinsurgeprotectorforeachofthefourfirealarm
lines.Thesurgeprotectorisprovidedforovervoltageprotection.

2.TECHNICALDATA
2.1.Operatingvoltage -24(+3.0,-5.0)VDC
Currentconsumptioninquiescentand
inalarmstateat26VDC-notmorethan100µA
2.3.Equivalentresistanceofisolatorinaline:
-inquiescentstate -<1;
-inalarmstate->6.5k.
2.4.Connectiontofirecontrolpanel-twowire,shielded
2.5.Surgeprotectortechnicaldata:
2.5.1.SurgecurrentIS8/20-20k¿
2.5.2.Responsetime-lessthan1ns
2.5.3.ProtectionlevelvoltageatIS8/20-45.7V
2.6.Protectionlevel-IP40
2.7.Operatingtemperaturerange-minus10°toplus60°
2.8.Temperaturelimits-minus40°toplus70°
2.9.Relativehumidityresistance -(92+3
-2)%at40°
Dimensions-(162ı120ı72)mm
2.11.Weight-0,3kg
3.STRUCTUREANDFUNCTION
3.1.Structure
Shortcircuitisolatortype6202-4containsfourone-wayisolators,whichcorrespondwiththefour
lineoutputsofLinearModule6002ofFireControlPanelFS6000.
Theshortcircuitisolatorlayoutisseenonthefrontpageofthisleaflet.Theunitconsistsoftwomain
parts:abaseandacover.Thebasecomprisesaprintedcircuitboard,providedwithscrew
terminals.Fixthecovertothebaseusingfourscrews.
3.2.Function
Theshortcircuitisolatormonitorstheline(loop)resistanceatisolatorísoutputpoint.When
resistancevaluereaches20threshold,theisolatorswitchesovertoalarmstate.Thesurface
yellowLEDilluminatesandtheline(loop)powersupply(negativewire)isinterruptedatisolatorís
outputpoint.Whentheresistanceoftheisolatedlineorloopisrestoredtothenormallimits,the
isolatorautomaticallyswitchesovertoitsquiescentstate.TheLEDextinguishesandthepower
supplyisresumed.Isolatordiagramisnotsymmetricalinrelationtotheinputandoutputofthe
isolator.ConnecttheincomingwiresandtheterminalsinaccordancewithFig.1.
IncaseofalightingstriketheSurgeProtectorrestrictsthemaximumlinevoltagedownto
150/180V,andthemaximumvoltageoffirecontrolpanelterminalsñdownto46V.
4.PREPARINGTHEUNITFOROPERATION
Electricalconnection(Fig.1)
1234
ToFireControlPanel
Tofirealarmlines
Fig.1
Recommendedwirecross-section-0.5mm2to1mm2
onnectiontofirecontrolpanel:
ìLn-îisconnectedtothecorrespondingnegativelineoftheLinearModule;
ìLn+îisconnectedtothecorrespondingpositivelineoftheLinearModule;
ìLnsîisconnectedtotheGNDterminalortothefirecontrolpanelcase(donot
connecttoOUTnsterminalsoftheLinearModule).
Connectiontoaline:
ìLn-îisconnectedtonegativefirealarmline;
ìLn+îisconnectedtopositivefirealarmline;
ìLnsîisconnectedtothefirealarmlineshield
(ìnîisforthelinenumber)
4.1.3.Isolatepartoftheshieldofeachwireusinganisolationband.
Importantnote:TogetthemostreliableperformanceoftheSurgeProtectormakea
secureelectricalconnectionofallshieldsintheterminalsandofallshieldstothefire
controlpanelcase.Thefirecontrolpanelcaseistobegroundedbyaseparatewire,cross
section1,5mm2.
Mounting.
Removethecoverandthecircuitboardfromthebase.
Makesuitableholesinthebaseforthewiresandforappropriatefixings.
Fixthebaseonthewallusingappropriatefixings.
Maketheelectricalconnectioninaccordancewith4.1.
Replacethecircuitboardonthebaseandfixwiththefourscrews.
4.3.Test
4.3.1Applypowertoeachisolator,consequiently,atterminalsìLn+îËìLn-î
(wheren=(1;2;3;4),tothefirecontrolpanelside)inthelimitsof19VDCto26VDCandoutput
resistancenotlessthan20(asin4.1.).
4.3.2.TerminateeachisolatorbyaresistorR20,inparalleltotheoutputterminalsìLn+îË
ìLn-î(n=1;2;3;4).
4.3.3.InactivestatetheyellowLEDilluminatesuntiltheshortcircuitstateiseliminated.
Note:Inrealconditionsitispermissibletotesteachisolatorbyterminatingthepositiveandthe
negativewireoftheline(loop).
  • Page 1 1