Deif TDG-210DG Quick start guide

Type
Quick start guide
TDG-210DG/2
Insulation amplifiers, DC/DC amplifiers
Quick guide
1159040018D
1. Installation
Item Description Notes
1 DEIF order number This number identifies the transducer and should be stated when you contact DEIF.
2 LOAD Impedance of input circuit (Ri).
3 LOAD Output loads
4 INPUT Measuring range
5 OUTPUT Output
6 SUPPLY Auxiliary voltage
Voltage output loads
The load must not drop below the stated resistance.
Current output loads
The load must not exceed the stated resistance.
Installation requirements
To ensure a long lifetime and optimal function:
The distance between the mounted transducers or other equipment must not be less than 10 mm. The recommended
minimal distance is 30 mm.
The DIN rail must always be in the horizontal position when several transducers are mounted on the same DIN rail.
The transducer must be installed in a well-aerated location.
QUICK START GUIDE 1159040018D EN Page 2 of 3
2. Wiring
NOTICE
Take normal ESD precautions when handling the transducer.
Dimensions
Terminal connection
OutputI Supply
+ -
Input
0
A1 A2 B1 B2 X1 X2
+ - + -
Recommended fuse: 2 A.
QUICK START GUIDE 1159040018D EN Page 3 of 3
  • Page 1 1
  • Page 2 2
  • Page 3 3

Deif TDG-210DG Quick start guide

Type
Quick start guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI