Dunkirk 3ES1.25 Owner's manual

Category
Water heaters & boilers
Type
Owner's manual

This manual is also suitable for

O|L-F|REDCAST |RONSTF.AM
BO|
Installation
Operation
RepairParts
Theseinstructionsmustbeaffixedonoradjacenttotheboiler.DUNKIRKBOILERS
DUNKIRK,NEWYORK14048- 716366-5500
MEMBER: The llydronies Institute
I/2" NPT
TANKLESS
HEATER
, o i
F , t , t i
, t , * ,
LEFT SIDE
3/4 _ NPT
_LOW UMIT
CONTROL ON
COIL PLATE
I/2" NPT
PRESSURETROL
PRESSURE GAUGE
COMBINATION
\
1-1/2" NPT
RETURN
i
FRONT
T
27"
WATER
IJNE
_l
2-I/2" NPT
SUPPLY
iq°p
i-i/2" NPT
i SKIM TAPPING
i
'L
,-V2 ° NPTi
RETURN
REAR
5/4" ASNE
POP SAFETY
VALVE
35
EMPIRE OIL-FIRED STEAM BOILER RATINGS
BOILER MODEL NO.
With Without
Tankless Tankless
Coil Cotl
3ESt O0C 3ES100 3
3ES1.25C 3ES1,25 3
3ES1.35C 3ES1.35 3
4ES1,50C 4ES1,50 4
4ES1.75C 4ES1 75 4
4ES1.85C 4ES1.85 4
* MBH = 1,000 BTUpet hour
No.
9ec.
Input
*MBH
140
175
189
2!0
245
259
Nesting
Capacity
*MBH
118
145
156
177
204
215
Net
I=B-R
Rating
"MBH
89
109
117
133
153
161
Not I-S-R
Rating
Sq. Ft,
Radiation
371
454
488
554
638
671
*Tonldelm
Cell
Ratings
GPM*
2.75
3,10
3.25
3.50
3.85
4,00
Typl©al
Chimney
Size and
Height
8" x 8'x 15'
8" x 8' x 15'
8" x 8' x 15'
8' x 8' x 15'
8" x 8" x 15'
8" x 8' x 20'
CIMF31SIONS- INCHES
A B C
16% 7 9
16½ 7 9
16% 7 9
20% 8 11
20% 8 11
20% 8 11
BTUH = British Thermal Unit Per Hour
GPH _ Gallons per Hour Oil at 140,000 BTU per Gallon
** Heating Capacity is based on a 13% CO2 with a -,02' w.c, draft over fire, and a #1 smoke or less. The testing on the boilers
was done in accordance with lhe DOE. (Department of Energy) test procedure
NewYorkCityMEANumber134-98-E
Selectionofboilersizeshouldbe basedupon"Net1=8=RRatingbeing
equaltoorgreaterthanthesq.ft.ofradiationalreadyinstalledinthe
building.
TheNetI=B=RRatingsshownarebasedonanallowanceof1.333in
accordancewiththefactorsshownonthe1=B=RStandardaspublishedby
TheHydronicsInstitute.
Theseboilersmusthavea non-combustiblebaseifinstalledon acombustible
floor.Two-inchcladlitepadmaybeused.Theseboilersarelowpressure
sectionalcastironboilersconstructedandhydrostaticallytestedfora maximum
workingpressureof 15psiin accordancewithA.SME. (AmericanSocietyof
MechanicalEngineers)SectionIVStandardsforcastironheatingboilers.They
arecapacityratedinaccordancewiththecodeofthe1=B=R(Hydronics
Institute).
RulesforSafeInstallationandOperation
1. Readthe Owner'sManualforSafeOperationcarefully.Failuretofollow
therulesforsafeoperationandtheinstructionscancausea malfunctionof
the boilerand result in death, _rious bodilyinjury, and/or property
damage.
2. Checkyourlocalcodesandutilityrequirementsbeforeinstallation.The
installationmustbe inaccordancewiththeirdirectives,orfollowNFPA31
- InstallationofOilBurningEquipment,latestrevision.
3. Beforeservicing,allowboilertocool.Nwaysshutoffanyelectricityand
oiltoboilerwhenworkingonit.Thiswillpreventanyelectricalshocksor
burns.
4. Inspectoillineandconnectionsforleaks.
5. Be certainoil burnernozzleis size required.Overfiringwillresultin
earlyfailureoftheboilersections.Thiswillcausedangerousoperation.
6. Nevervent this boiler intoan enclosedspace.Alwaysvent to the
outside.Neverventtoanotherroomor insidea building.
7. Besurethereisadequateairsupplyforcompletecombustion.
8. Followa regutarserviceandmaintenancescheduleforefficientand
safeoperation.
9. Keepboilerareacleanandfreeofcombustiblematerial,gasolineand
otherflammablevaporsandliquids.
This boiler has been designedfor residentialinstallations. If used for commercial
applications,alljurisdictionalrequirementsmustbemet.Thismayrequirewiringandlor
pipingmodifications.Themanufacturerisnotresponsibleforanychangestothe original
design.
BeforeYouStart
Check to be sure you have the dght size boiler beforestartingthe
installation.See ratingand capacitytableon precedingpage.Checkthe
ratingplateontheboiler.
You mustseethat theboileris suppliedwiththe properoil,freshair for
combustion,and a suitableelectricalsupply.Also, the boiler must be
connectedto a suitableventingsystemand an adequatepipingsystem.
Finally,a thermostat,properlylocated,is neededforcontrolofthe heating
system.If youhaveanydoubtsasto thevariousrequirements,checkwith
local authorities and obtain professionalhelp where needed. THE
OPERATING INSTRUCTIONSand THE FINAL CHECKS AND
ADJUSTMENTSare vitalto the properandsafe operationof theheating
system.Takethetimetobesuretheyarealldone.
Thefollowingstepsareallnecessaryforproperinstallationandsafe
operationofyourboiler.
1. LOCATINGTHEBOILER
2. OILSUPPLYANDPIPING
3. FRESHAIR FORCOMBUSTION
4. PIPINGCONNECTIONS
5. CHIMNEY& VENTPIPECONNECTIONS
6. ELECTRICALWIRING
7. THERMOSTATLOCATION
8. CHECKING&ADJUSTING
9. MAINTENANCE
Locatingthe Boiler
If yourboileris partof a plannedheatingsystem,locateit as nearlyas
possiblewhereshownon yourplan.If boileris to be partof an existing
system,it is usuallybestto put it wheretheold onewas.If youplanto
changelocation,youwillneedadditionalmaterialsaswellasan adequate
base.Thefollowingrulesapply:
1. Theboilermustbe levelandlocatednearpiping.
2. Usea raisedbaseiff]oorcanbecomewetordamp.
3. Theventpipeconnectionshouldbeasshortaspossible.
4. Maintainclearancesforfiresafetyaswellasservicing.SeeFigure2for
minimumclearances.18"clearancemustbemaintainedatasidewhere
passageisrequiredforaccessto anothersidefor cleaning,servicing,
inspection,or replacementofanypartsthatnormallymayrequiresuch
attention.Boilersmustbe installedat least6"fromcombustiblematerial
onallsidesandabove.Allowatleast24"frontclearanceforservicing.
Allowatleast18"leftsideclearanceforservicingboilersequippedwith
atanklesscoil.
5. FRESHAIRforcombustionmustbeavailableatthefrontoftheboiler.
FRESHAIRforventilationmustbeavailabletothefrontANDrearof
theboiler.Airpassagesmustbefreeofobstructionsatalltimes.
Ventilatingandcombustionairmustenterboilerroomwithout
restrictions.
6. The floor suppo_ng the boiler must be non-combustible.If it is
combustible,placetheboileron 2"cladlitepad.Thepadmustbeunder
theentireboilertoprotectthefloor.
7. Besureinstallationisinaccordancewiththerequirementsofthelocal
authoritieshavingjurisdiction.Compliancewiththeseregulationsis
required.Intheabsenceoflocalcodes,followNFPA31- Insbtlationof
OilBurningEquipment.
Q 6" MIN. 18" WITH COIL
_
_" 6" MIN. "
I_// . I BOILER
I-----2, .,..------IFRO.T
6" MIN.
SeRVraceL_NeLL,.------e_.ec_rRic
F_LPtFE ] I I[ s_,rrc_
GENERAL PRINCIPAL REQUiREMEnTS FOR A TYPICAL INSTALLATION
m_
Fresh Air for Combustion
WARNING
NOTE
Be sure to provide enough fresh airfor combustion. Enough air ensures
proper combustion and assures that no hazard will develop due to
the lackof oxygen.
If you use a fireplaceor a kitchenor bathroomexhaustfan, you
shouldinstallan outsideair intake.Thesedeviceswillrobthe boiler
andwaterheaterofcombustionair.
You must provide for enough fresh air to assure proper combustion. The fire
in the boiler uses oxygen. It must have a continuous supply. The air in a
house contains only enough oxygen to supply the burner for a short time.
Outside air mustenter the house to replace that used by the burner. Study
foIIowingexampIes 1and 2 to determineyour fresh air requirements.
EXAMPLE 1:Boiler Located in Unconfined Space
If your boiler isin an open area (unpartitioned basement) ina conventional
house, the air that leaks through the cracks around doors and windows will
usually be adequate to provide air for combustion. The doors should not fit
tightly. Do not caulkthecracks aroundthe windows.
An unconfinedspace isdefinedas a space whose volume isnot lessthan 50
cubic feet per 1,000 Btu per hour of the total inputrating of all appliances
installedin thatspace.
EXAMPLE 2: Boiler Located in Confined Space
A, All Air from Inside the Building: The confined space shallbe provided
with two permanent openings communicating directly with an additional
room(s) of sufficientvolume so that the combined volume of all spaces
meets the criteria for an unconfined space. The total input of all
combustion equipment installed in the combined space shall be
considered in making this determination. Each opening shall have a
minimumfree area of one square inch per 1,000Btu per hourof thetotal
inputratingofall combustionequipment inthe confinedspace, but not less
than 100squareinches. One openingshall be within 12 inches ofthe top
andone within 12 inchesof the bottomof theenclosure.See Figure4.
Example: Your boiler is rated at 100,000 Btu per hour. The water heater
is rated at 30,000 Btu per hour. The total is 130,000 Btu per hour. You
need two grilles, each with 130square inchesof FREE opening. Metal
grilles have about 60% FREE area. To find the Iouveredarea needed,
multiply the FREE area required by 1.7 (130 x 1.7 = 221.0 sq. in.
Iouvered area). In thisexample twogrilles, each having an 8"x 30" (240
sq.in,) Iouvered area would be used. Fig. 4 shows the grille locations.
B. All Air from Outdoors: The confined space shall be provided with two
permanent openings, one commencing within 12 inches of the top and
one commencing within 12 inches of the bottom of the enclosure. The
openings shall communicate directly, or by ducts, with the outdoors or
spaces (crawl or attic)thatfreelycommunicatewith the outdoors.
1.When directly communicatingwith the outdoors,each opening shall have
a minimumfree area of one squareinchper 4,000 Btu per hour of total
inputratingof all equipmentin theenclosure.
2. When communicatingwith the outdoors through ve_cal ducts, each
opening shall have a minimumfree area of one square inch per 4,000
Btu perhour of total input ratingof all equipmentin theenclosure.
3.Whencommunicatingwiththeoutdoorsthroughhorizontalducts,each
openingshall havea minimumfreearea of one squareinchper
2,000 Btu per hour of totalinput ratingof all equipmentin the
enclosure.
4. Whenductsareused,theyshallbeof thesamecross-sectionalarea
asthefreeareaoftheopeningstowhichtheyconnect.Theminimum
dimensionofrectangularairductsshal{benotlessthanthreeinches.
VENTILATING -'_--i
GRII.LE I
i I ' 1
i ,11 II ',
AIR GRILLE _
Fresh Air Duct Capacities for Ducts Supplying Fresh Air to
boiler in tightly constructed houses. British Thermal Units per
hour Input (Btuh)*.
Fresh Air
Duct Size
31/2"x 12"
8* x 8"
8" x 12"
8" x 16"
1/4"Mesh
Screen Btuh
144,000
256,000
384,000
512,0O0
Wood
Louvers Stuh
36,000
64,000
96,000
128,000
Metal
Louvers Btuh
108,000
!92,000
288,000
384,000
*Based on opening covered by IA" mesh screen, wood louvers, or mela{ louvers
FRESH
Boilers With Tankless Heater Coil
Boilersmaybefactorypackagedwithatanklessheatercoil.Theuseofthis
coileliminatestheneedforahotwaterstoragetank.Instantaneousheatingof
waterinthecoilwillprovidea flowof hotwaterfordomesticuse- ifproper
watersupplylinecontrolsareused.
IMPORTANT
Donotusea tanklesscoilif yourwaterisexcessivelyhardwithlimeor
otherdepositswhichwillaccumulateinsidethecoil.
Forsummerrunningwithcoilyouneedtofillboilerwithwaterandaddthe
L6006limitcontrolto the coil.Thiswill maintainwatertemperaturein the
boilerand bringtheburneronwhennecessary.
TANKLESSCOlLPIPING
Pipingisshownin Figure7B.A temperingvalve(mixingvalve)is
recommended.
LowLimit(whenused)- 140° F
Thesesettingscanbechangedafteryouhavesomeideahowthesystem
responds.If moredomestichotwateris required,the lowlimitsettingcan
alsoberaised.
_NT_pERE_ _OT WATER
¢OL_ WATE_ _N_ET
WLV_
Installation-SystemPiping
Thenearboilerpiping,thatisthepipingaroundtheboiler,mustbeconsidered
aspartoftheboilerforproperwaterlevelcontrol,andtoproducedrysteam.
Correctnearboilerpipingiscrucialtotheproperoperationoftheboilerand
theheatingsystem.Followtheserecommendationscarefully.
1.Placeboilerintheselectedlocation,asnearchimneyaspossible.
2. Installthepopsafetyvalve,usingthefurnished3/a" 90" ell,intothe3/4"
pipenippleonthebackoftheboiler.Makea dischargepipe,using3/4"pipe
(notfurnished)to carrythe wateror steamto a nearbydrain.Do not
connectthe dischargepipe directlyto a drain butleavean air gap.No
shutoffofanydescriptionshallbeplacedbetweenthepopsafetyvalveand
theboiler,orondischargepipes
betweensuchsafetyvalvesandtheatmosphere.Installationofthepop
safetyvalveshallconformtotherequirementsoftheANSI/ASMEBoiler
and Pressure Vessel Code, Section IV The manufactureris not
responsibleforanywaterdamage.
3.Thisboileris equippedwithtwo 21/2"supplyconnectionson topand
two 1V2"returnconnections,oneeachon frontand backsidesof the
boiler.Unusedconnectionsmust
4.Recommendednearboilerpipingfor gravityreturnsys-temsisshown
in Figure8.Thisconfigurationusesonesupplyandonereturntapping.
Pipingoff bothboilertap-pingsisrecommendedon units5 sectionand
larger.
Note:Usebothsupplytappingsonboilers5 sectionandlarger.
PtPES_E
5.Forinstailerschoosingto usebothsupplytappings,Figure8Ashowsthe
correctwayto pipethissystem.Figure8Bshowsthewrongwaytopipe
a headerwithtworisers.
, Headersmustbe fittedwith headeroffsetsor swingjoints,or be
equippedwith expansionjoints, so that thermalexpansionand
contractionofthe headerwillnatdamagetheboiler.Headersshall
netbewelded.
, Systemtakeoffsfromtheheadermustbebetweentheequalizerand
therisertotheheadernearesttheequalizer.Systemtakeoffsmust
neverbe betweentworisers.
6.Systemtakeoffsfromtheheadermustneverbe bull-headed.Ifthesteam
maingoesintwodirections,theremustbetwotakeoffsfromtheheader,
oneforeachmain.
7. All boilersingravityreturnsystemsmustbeequippedwitha Hartford
LoopasshowninFigures8 and8A.
8. Whenpipingtheverticalrisersfromtheboilertotheheader,thebottom
oftheheadermustbea minimumof 24inchesabovethewaterlevel
lineantherightsideoftheboiler(i.e.51inchesabovethefloor).
9. Steamriser(s)andheadershallbe272"pipesize.
10. Equalizerlineshailbeminimum1 1/2"pipesize.
11. Theboilerhasa 1V2"tappinginrearsecflanfarskimming.
_EA_{ MAINS
HART_ORO
CLOSE
N|PPLE
MAIN VENT
D_Y RETURN
M_[N
THIS, PIPING
COMMON
tS INCORRECT
MISTAKES
TO SHOW
©
L
12. The near boilerpipingshall includea 1 1/2"ballvalvein thereturn
pipingasshowninFigure8Afarbottomblowdawnanddraining.
13. Forgravityreturnsystems,thebottomoftheloweststeamcarrying
pipe,beita dryreturn,ortheendofthesteammain,mustbeatleast
28"abovethenormalwaterlevellineanthedghtsideoftheboiler.
Thisisknownas"DimensionA."
14. Forpumpedreturnsystems,followthecondensatepumporbailerfeed
pumpmanufacturer'sinstructionsforproperinstallationandhookup.
15. Inconnectingthecoldwarer supplytothewaterinletvalve,makesure
thata deanwatersupplyisavailable.Whenthewatersupplyisfroma
wellor pump,asandstrainershouldbeinstalledatthepump.
FORUSEWITHCOOLINGUNITS
A.
This boiler, when used in connection with chilledwater systems,must
be installedso that the chilledwater is piped in parallel with the heating
boiler. Appropriate valves must be used to prevent the chilled water
from enteringthe heating boiler(Fig. g).
B.Whenthis boileris connectedto heatingcoilslocatedin air handlingunit.,
wherethey may be exposedto refrigeratedair circulation,the piping
systemshall be equippedwith flow controlvalvesor other automatic
meansto preventgravitycirculationoftheboilerwaterduringthecoolinc
cycle.
'_rd,.vE8 A & m
VALVESC & Q
_R _OUNG
ChimneyandChimneyConnection
CHECKYOURCHIMNEY
Followlocalcodes.Intheabsenceof localcodes,followANSI/NFPA31
InstallationofOilBurningEquipment,latestedition.
Thisisaveryimportantpartofyourheatingsystem.Noboiler,however
efficientitsdesign,canperformsatisfactorilyifthechimneythatservesitis
inadequate.Checkyourchimneytomakecertainthatitistherightsize,
properlyconstructedandinsoundcondition.
Itischeapertorebuilda poorchimneythantopayexcessivefuelbills.If
yoursisanoldmasonrychimney,a newsteellineror a new
prefabricatedchimneymaybethebestsolution.Thefollowingchartshows
recommendedminimumchimneysizesbasedonTable3andFigure6 of
theI:B:R TestingandRatingStandardfor HeatingBoilers,Sixth
Edition,June1989.
MUST BE REQUIRED MIN*
IMUM HEIGHT, MUST BE
AT LEAST 3 FT. HIGHER
THAN HIGHEST PART OF
PASSAGE THROUGH
ROOF. MUST BE AT
LEAST 2 FT. HIGHER
THAN ANY NEIGHBORING
OBJECT. MUST HAVE AN
UNOBSTRUCTED TOP
OPENING,
MUST BE AT LEAST
4 INCHES THICK -
AND BE LINED.
_l_ CHFM_ I
.60- i 30 15
13Iol 80 15
i,81o2,00 20
FIECOMMENDED MtNiMUM _IMNEY SIZES
=!:
_ER_ LNER;
_!NNqY' i_DE I_
8"×8 ' 6' 6:5_x 6_'
8' x 8" 7' , 6_f;_"× 6_!4"
[:<]re#_@:(Y)88_ee 2,#_ if,,8J3_es_ _i, ad_3 feetIocblm_qeYhe_gP4_
[_!et la Fiqure 1@t
Foradditionalchimneydesignandsizinginformation,consulttheASHRAE
1996HVACSystemsandApplicationsHand-book,Chapter30,Chimney,
GasVentandFireplaceSystems;ortheNationalStandardforChimneys,
Fireplaces,VentsandSolidFuelBurningAppliances,ANSI/NFPA211.
CHIMNEYCONNECTORANDDRAFTREGULATOR
Yourboilerrequires7"diameterchimneyconnectorpipeon 3 section,8"
diameterchimneyconnectorpipeon 4 section.Youmustalsouse a dralt
regulatorpackedwithboiler.Properlyinstalled,theregulatorwillcontrolthe
draftautomatically.Itisbettertoinstallitina horizontalsectionofthepipe;but
itmaybeinanangledorverticalsection.Justmakecertainthatthe"top"isat
top- andthattheshortpipesectionwhichholdstheVaneishorizontal.Install
itascloseaspracticabletotheboiler.
Toinstallthechimneyconnector,startattheboilerandpreferablytakeoff
fromthefluecollectorcollarwithanelbow- theninstallthedraftregulator
next,makingithorizontal.Whentheregulatorisinplace,startatthechimney
andworkbacktotheregulator.JointhetwosectionswithaDrawband.The
horizontalpipemustslopeuptowardthechimneyatleast1/4inchperfoot.It
mustnotleakandmustbefirmlysupported.Joinsectionswithatleasttwo
sheet-metalscrews.Supporteverysecondsectionwitha stovepipewire.
MINIMUMVENTPIPECLEARANCE
ALTERNATE POSITIONS
TOP
1
MUSTSLOPEUP
AT LEAST 1/
PER FOOT OF
HORIZONTALRUN
DRAWBAND
LAST PIECE
INSTALLED
I
I L
_,TIGHT. SMOOTH,
CORRECTLY SIZED.
I
I
t
I
&LEDIN
THIMBLE
TIGHT
DOOR
DRAFT REGULATOR
VANE
Woodandothercombustiblematerialsmustnotbecloserthan18"fromany BALANCEDWEIGHT
surfaceoftheventpipe.
EquipmentandOptionalAccessories-WhatTheyDo
POPSAFETYVALVE
Youmusthavea popsafetyvalveonyourboiler.Steamexpandsasitisheated.
Ifthereisno placeforthesteamtoexpandinto,pressurewillbuildupinsidethe
boilerandsystem.Shouldthishappen,thepopsafetyvalvewillautomatically
openata pre-determinedpressure.Thiswillrelievethestrainontheboilerand
system.Runa pipefromthesafetyvalveoutlet(pipemustbesamesizeasoutlet
andtheopenendmustnotbethreaded)toan opendrain,tuborsink,or other
suitabledrainagepointnotsubjecttofreezing.Failuretodosomaycausewater
damageorinjuryshouldreliefvalverelease.Donotcapoffthedrainlinefrom
thisvalve!Eachpopsafetyvalveisprovidedwitha liftingdevicefortestingand
shouldbetestedmonthlyduringtheheatingseason.Refertosafetyvalve
manufacturer'sinstructionspackagedwithsafetyvalve.
STEAMPRESSUREGAUGE
Everysystemshouldhavea pressuregaugeinstalledintheboiler.Thisgauge
enablesyoutomonitorthepressureinthesystem.Ifthesafetydevicesfailtoshut
offyourboileratthepropersettings,notifyyourservicetechnicianimmediately
WATERLEVELGAUGE
Thewaterlevelin theboilercanbeseenthroughtheglasstubeinthewater
levelgaugeatsideofboiler.Correctcoldboilerwaterlevelisstampedonside
jacketpanel.Whenmakingsteam,thewaterlevelwilldroponetothreeinches.
Thewaterlevelshouldbecheckedregularly.
STEAMPRESSURECONTROL
Thesteampressurelimitcontrol(pressuretrol)shutsofftheoiltotheburnerifthe
steampressureintheboilerreachesthecut-offsetpoint(i.e.thesumofthecut-in
andthedifferentialsetpoints).Burnerretireswhenthesteampressuredropsto
thecut-insetpoint.Systempressurerequirementsarebasedonthesizeand
conditionofthepipes,andtheload.
Forgoodsystemoperation,thecut-insettingofthepressuretrolshouldnever
be less than twicethe systempressuredrop. In a typicalsinglefamily
residencewith a cleanonepipeheatingsystemand castiron radiation,this
meansthatthecut-inwillusuallybesetattheminimumsetting,i.e._/2psi.
Steamradiationis usuallysizedbasedon squarefeet of equivalentdirect
radiation(EDR).Thisis basedon a steampressurein theradiatorofjust less
than1 psi.Therefore,in our examplesystemfromabove,wewouldsetthe
differentialadjustmentat1psi,i.e.thesteampressurerequiredintheradiators.
Thiswillgiveusa cut-offsetpointd 1_12psi.
Theaboveisanexampleofa typicalonepipesystem.Forlargersystemsor
othertypesofsystemssuchastwo pipesystems,or systemswithconvectors
or fan coil units,the pressuretrolsettingswill needto be determinedon a
system-by-systembasis.
The cut-insetpointisdeterminedbythesystempressuredroptothefurthest
radiatoror terminalunit.Doublethesystempressuredropasa safetyfactor,
resultinginthe rulethatthecut-insettingshouldneverbe lessthantwicethe
systempressuredrop.
Thedifferentialset#ointisthesteampressurerequiredattheterminalheating
units.
Nowyourboilerwill operatein the correctpressurerange.It will maintain
enoughsteampressuretosendthesteamouttothefurthestradiator,andnot
go overtheoptimumsteampressurethatisrequiredattheradiators.
67D-t LOWWATERCUT-OFF
Thefloat-typelowwatercut-offshutsofftheburnerwhenthewaterlevelis
belowasafepoint.Theburnerwillstartwhenthewaterisrefilledtoa
minimumsafelevel.
WATERFEEDER(Optional)
Awaterfeederworkswiththelowwatercut-off(LWCO)tomaintaina
minimumsafelevelofwaterforboileroperation.It'susedtokeeptheboiler
runningbycompensatingforminorevaporativesteamleaks,andtoprevent
freeze-upsifthehomeownersareawayanda returnlineshouldspringa
leak,Theautomaticwaterfeederisa safetydevice,nota
convenienceitem.Itisnotdesignedtomaintaina "normal"waterline.The
waterfeederdoesnottaketheplaceofa responsiblepersonmonitoringand
maintainingthe"normal"waterline.Steamboilersrequirepersonal
attention.
Four electricwater feedersare offeredby McDonnell-Millerwhichare
compatiblewiththe 67D-1LWCO.The model#101Aand #WF2-U-120
waterfeedersareusedwith120voltwiringcircuits,asfoundanthissteam
boiler.The McDonnell-Millermodel#101A-24and#WF2-U-24are used
with 24 volt circuits,which may be usefulin a retrofitinstallationwhich
alreadyhasa 120voltto 24volttransformer.
TheWF2-U-120and WF2-U-24(Uni-Match)waterfeedersareequipped
witha solidstateelectroniccontrolwhichfeedswaterwhensignaledbythe
LWCO.Thewaterfeedrateisfieldadaptablefar 1,2, or 4 gpm.These
waterfeedershavean adjustableslideswitchtomatchthetimingcyclean
theLWCO.Whenusinga McDonnell-MillerLWCOtheslideswitchneeds
toselectposition#1.Thetimingcyclecreatesaninitialdwellperiodofone
minuteto allowcondensateto be returnedto the boiler.If afterthedwell
periodthewaterhasnatreachedtheminimumsafelevelandcompletedthe
LWCOcircuit,thenwaterisfedattheselectedflowratefaroneminute.The
dwellpedodistheninitiatedagainfaroneminute.Ifthewaterlevelhasstill
not reachedthe minimumsafe level,then wateris addedagain at the
selectedflowrateforoneminute.Thiscyclecontinuesuntilwaterreaches
the minimumsafe leveland the circuitis completed.DunkirkRadiator
recommendsusinga Uni-Matchwaterfeederataflawrateof1or2gpm.If
the steamboilerrequireshigherflow rateson a regularbasisa service
technicianshouldbenotified.
The1OlAwaterfeedermaybe used,howeverthewaterfeedrateistoo
high and needsto be regulatedor throttled.The IO1Awillfeedupto 6
gpm,muchgreaterthanthedesiredflowrateof1-2gpm.Also,thereisno
dwellperiodto providea marginfor condensateto returnto the boiler.
Thesetwofactorsincreasethechancesofoverfeedingwatertothesteam
boiler.Excessivewaterinthesteamboilerwillproducenoise
Consultthe water feedermanufacturer'sinstallationguidelinesfor more
detailson waterfeederselection,recommendedpipingarrangement,and
start up procedures.Dunkirk Radiator supports McDonnell-Miller's
recommendationtoarrangetheinstalledpipingsoa brokenuniontestcan
beimplemented.
DRAINVALVE
Thismanualvalveprovidesa meansofdrainingallwaterfromtheboilerand
system.Itshouldbeinstalledinthe3/a"teewherethewatersupplyline
enterstheboiler(Fig.8).Youcanalsousethisvalvetolowerthewaterlevel
ifitistoohigh.
STEAMVENTS
Beforea steamsystemwilloperateproperly,suitablesteamventsmustbe
installedin eachradiatoras wellasthe returnmain.Somesystemsrequire
steamtrapsinthereturnlineattheradiationunit.
The"Hartfordloop"isa pipingarrangementwhichmustbeincluded(Fig.8)
forproperoperationofthesteamsystem.
BOILERSWITHTANKLESSCOILSONLYFlowRegulatorandWater
TemperingValve
Ifyouhavea TanklessCoilfordomestichotwater,thesetwopartscanbe
used.Thiswillprovideyouinstantaneoushotwaterthatisneither
scaldinghotnormerelytepid.TheFlowRegulatorisplacedinthecoldwater
linetothecoil.It assuresa steadyflowofwatersothatthecoilcanproperly
heatit. It prevents"spurts"of "half-heated"water.Thisisimportantwherethe
waterpressureisexcessivelyhighorvariable.TheWaterTemperingValve
is ateewhichis connectedata junctionbetweenthehotwaterlinefromthe
coilandacoldwaterbranchfromthesupplyline.Itmixeshotandcoldwater
as requiredto furnisha temperedsupplyof watertothe house.Thewater
willbejusttherighttemperatureforyouruse.Thisisimportanton a steam
systemto preventscaldingtemperaturesatthefaucets.Bothpartsare self-
containedandautomatic.
Starting Your Boiler
HOWASTEAMSYSTEMOPERATES
Thewaterintheboilerisheateduntilit reachestheboilingpoint.Asthe
waterboilsit turnsintosteam.Thesteamrisesfromthetopofthewater
throughthesupplymainto theradiationunits.Asit passesthroughthe
radiatorsitreleasesitsheatandcondensesintowater.Thewaterreturns
totheboilerthroughthereturnmain.
FILLINGSYSTEMWITHWATER
Onsteamheatingsystemstheboileris partiallyfilledwithwater.Itisvery
importantto theproperoperationoftheentiresystemthatyourboilerbe
filledtotheproperlevel.Thecorrectwaterlevelon coldstartconditionis
abouthalfwayupthe glasswaterlevelgaugeasmarkedon theboiler
jacket.Tofill:
1.Closetheboilerdrainvalve.
2. Openthevalvesatthetopandbottomoftheglasswaterlevelgauge.
Alsoopenthedrainvalveatthebottomofthegauge.
3. OpenthefilIvalveandatlowwatertorunintotheboiler.
WARNING- Neverrunwaterintoa hotemptyboiler,
4.Allowboilertofilluntilwaterrunsoutthegaugedrainvalve.Then
closethegaugedrainvalve.
5.Continuetofillboileruntilwaterreachestheindicatedwaterline.This
Checking and Adjusting
isabouthalfwayuptheglasstube.Alwayskeepthewateratthislevel
whensystemisoff.
IMPORTANT
Skimminga newsteamboileronan existingsystemmustbedoneseveral
timestoremoveall oil,greaseandsediment.Thereshouldbe a teewitha
plugpipedtothesupplylineoftheboilerinordertoproperlyskimtheboiler.
Wheneverthewaterin the glassgaugebecomesdiscolored,yourboiler
shouldbeskimmed.
Whenskimming,makesuretopipetheopenendoftheteetothefloorora
drainto preventanyonefrom beingburnedbythe steamand hotwater
whichwillbereleased.
TheFloatLowWaterCut-offshouldbe blowndownafterskimming.Following
blowdown,allowtheboilertocoolandthenaddfreshwaterslowly.
Thefloatchamberofthelowwatercut-offmustbeflushedcleanandmaintained
clearof sedimentto allowfree movementof the float.This mustbe done
frequentlyduring initialoperationof the boilerand at least onceper week
thereafter.Followinstructionsontagattachedto control.Neverthrottlea steam
radiatorvalve on a one-pipesystem.It mustbe fully openor fully closed.
Otherwisewaterisheldintheradiatorunits.Thiswillcauseknockingsounds.
Skimmingmayberequiredagainafterafewdaysoperation.
CHECKINGCONTROLS
To checkthe LowWaterCut-Off,turnoff powerto theboileror turnthe
thermostatdownto the lowestsetting.Drainwaterto belowthevisible
bottomofthewatergaugeglass.Turnpoweronandturnthethermostatto
callforheat.WhentheboilerisequippedwiththefloattypeLWCO,theoil
burnershouldnotrunonacallforheatwhenthewaterislow.
To checkthe pressurelimit, run the boileruntil the pressurereaches
systemdemand.Thenturn the pressurescrewand dropthe pressure
settinguntiltheboilershutsdown.Thiswillshowthatthepressurelimitis
operatingproperly.
If youhaveinstalledyourownboiler,we recommendthat youcallforan
inspectionby a servicetechnician.The peace of mind and assured
performanceare wellworththe costinvolved.Hecanquicklymakethe
necessarychecksandadjustments.
OIL BURNERADJUSTMENT
Suggestednozzlesand preliminaryburnersettingsarefoundon page20.
Referto youroil burnerownersmanualfor checkingand adjustingthe
burner.
ADJUSTOPERATINGCONTROLSInstructionsforeachcontroland
burnerareincluded.
Betthermostatheatanticipatorat.20.Instrucfionsforthefinaladjustmentof
thethermostatarepackagedwiththethermostat.
CHECKTHERMOSTATOPERATION
Whensetabovetemperatureindicatedon the thermometer,boilerburner
shouldstart. Makecertainthe thermostatturnsoff the boilerwhenroom
temperaturereachesthe selectedsettingand startsthe boileroperating
whenroomtemperaturefallsafewdegrees.
Finally,setthethermostatforthedesiredtemperature.Specialconditionsin
yourhomeandthelocationofthethermostatwillgovernthissetting.
MaintainingYourBoiler
Checkthe waterlevelevery dayor two.Verifythe watertineshownby
operatingthedrainvalvean thegauge.Be suretop and bottom valves
on gaugearealwaysopen sothatactualwaterlevelwill beshown
atalltimes,
POPSAFETYVALVE
Thisvalveshouldopenautomaticallywhenthesteampressureexceedsthe
safelimit(perinstructionspackagedwithvalve).Shoulditeverfailto open
undertheseconditions,shut downyoursystem.Havethevalvereplaced
immediately,The pop safetyvalve shouldbe testedmonthlyduringthe
heatingseason.Refertothevalvemanufactureflsinstructionspackagedwith
thepopsafetyvalve.
LOWWATERCUT-OFF
TheLowWaterCut-offwillin_rrupttheelectricalcurrenttotheburnerwhen
thewaterlinein theboilerdropsto a lowlevel.It isveryimportanttokeep
thefloatchamberfreefromsediment,a conditionessentialto dependability.
To keepany accumulationfrom interferingwith floatactionis to "BLOW
DOWN"orflushoutthecontrolregularly.Thismustbedonetwo-threetimes
thefirstweekafterinstallationandoncea weekthereafterduringtheheating
season.Doitwhiletheboileris inoperation.Firstnotewaterlevelin gauge
glass.Openblow-offvalveatbottomof control,waterwillpourout,flushing
awaysediment.Drainuntilwaterisclear,abouta pail,thenclosevalve.If
waterlevelingaugeglasshasdropped,addwatertoboilertorestorelevel.
Consultlowwater cut-offmanufacturersinstructionsincludedwith boiler.
NOTE:Openingblow-offvalvecheckscut-offoperationtoo.Asfloatdrops
withfallingwaterlevel,burnerswillshutoff.Aftervalveisclosedandnormal
operatingconditionsarerestored,burnerswillresumefiring.
Boilersshouldnot be drainedbetweenheatingseasons.Onlywhenthe
waterin thesystembecomesdirtyshouldtheboilerbe drained,flushedor
boiledout,andrefilled.Steamboilersmaybeentirelyfilledwithwaterduring
thesummermonthstoexcludeair.
CLEANINGYOURBOILER
Undernormaloperatingconditions,withthe burnersproperlyadjusted,we
recommendthat you have the flue passages,burneradjustment,and
operationof the controlscheckedonce each year by a Service
Technician.
Before the start of each season (orwheneversystemhasbeen
shutdownforsometime)recheckthewholesystemforleaks...andrecheck
theboilerandventpipeforleaks.Replaceor patchanyboilersealsthatare
faulty.
BOILERFLUEPASSAGES
FluePassagesbetweensectionsshouldbeexaminedyearlyandcleaned.
Removevent pipe.Raisetoppanelof boilerandswingoutto exposeflue
collector.Removefluecollectortop. Cleanpassagewaysbetweensections
witha flexiblehandlewirebrush.Removedirtfomthebottomoftheboiler
and reassembleall parts.Be surevent pipeconnectionsto chimneyare
secureandnoobstructionsarepresent.
FOAMING,PRIMINGORSURGING
Thesetermsareusedtodescribeafluctuatingwaterline- whenwater
leavestheboiler.
Itiscausedbyanycombinationofthefollowing:
1.Threadingoilandorganicmatterintheboilerwater.(Mineraloil,orcore
sanddoesnotcausesurging.)
2. Faultyquickventsthatdonotreleaseair untila sizeablepressureisbuilt
up- replace.Ifdirty,cleansothatyoucaneasilyblowthroughvalve.
3. Improperheader design - whensteamflowsin oppositedirectionof
equalizerlineon"Hartfordloop."Generallya 15"horizontalrunbetween
riserandmaintakeoffwill allowentrainedwaterto falloutofthesteam
vaporsoitcanreturnto boiler.(Seepage7,Fig.8)
4.Adjustmentof steamlimitcontroltoa widedifferentialincreasesdifficultyif
quickventsare oldstyle,slow-releasingtypeor dirty.Alwayssetsteam
limitcontroldifferentialaslowaspossible.
5.Soapanddetergentscauseextremesurging- cleanthoroughlyby
skimmingtheboiler.
CAUTION
Neverrefilla hotboilerwithcoldwater- thedangerofthermalshockmay
crackasection.
CAUTION
Neverallowelectricianor oil burnermechanicsto tryouttheirwork by
turningon oil burnerfor evenone secondunlessboileris filledto the
properoperatinglevel.
SYSTEMCHECKSAFTERFIRSTSTARTING- STEAMSYSTEMS
Readthe instructionspackagedwithyourcontrolsand makechecksand
adjustmentsaccordingly.Start the burnerand set the Thermostatfor the
desiredroomtemperature.WhenadjustingtheSteamPressurecontrol,watch
thesteamPressureGaugeanduseits pressurereading- asitwillbemore
accuratethanthecontrol.(Anydifferencebetweenthetwowillbeduetotheir
differentlocation.)
BOILERWATERTREATMENT
Inclosedhotwaterheatingsystems,negligibleamountsofmakeupwaterare
used,and watertreatmentis not required.In steamsystemswherethe
systemistight,freefromleaks,andall thesteamis returnedtotheboileras
condensate,theamountofmakeupwaterissmall.Again,watertreatmentis
notrequired.
On steamsystemswith less than 90% of the steambeingreturnedas
condensate,orwithveryhardor corrosivemakeupwater,treatmentmaybe
desirable.Followthe recommen-dationsoftheASME(AmericanSocietyof
MechanicalEngineers)Boilerand PressureVesselCode,SectionVl, latest
version.
BETWEENHEATINGSEASONS
Boilersshouldnotbedrainedbetweenheatingseasons.Boilersinclosedhot
waterheatingsystemsmaybeleftasis.Steamboilersshouldbeentirelyfilled
withwaterduringthesummermonthstoexcludeair.
Oil Boiler/BurnerCleaningInstructions
1. ShutoffalIelectricaIpowertotheboiler/burnerandshutofffuelsupply.
2. Removethesheetmetalsmokepipefromthetopd theboiler.Inspect
pipeandchimneyforsignsofcorrosionanddeterioration.Cleanbase
ofchimney.
3. Removetopjacketpanel.
4. Removethetwobrasswingnutsholdingtheflueccllectorfop.
5. Checkthegasketontheundersideofthefluecollectorandreplaceas
necessary.
6. Removetheoil burner(threecapscrews).-OR-
Removetheoil burner/firedoorassembly(fourhexnuts).This is the
recommendedmethod,as it allows full accessto the combustion
chamberandlesspotentialdamagetothetargetwallduringthecleaning
process.
7. Removetheburnerdrawerassembly.Cleananysootaccumulations.
8. Replacetheburnernozzlewiththeexactsizeandtyperecommended
forusonthisboiler.
Note:Changingto adifferentfiringrate,otherthanisrecommended,ortype
of nozzlemaychangethe performanceof this boilerand/orcausea
hazardouscondition.
9. Cleanelectrodeassemblyandsetelectrodesasperburner
manufacturersrecommendations.
10.Reinstalldrawerassemblyandcheckforproperheadlocationasper
themanufacturer'srecommendations.
11.Inspectthetargetwail,blanket,andfiredoorinsulationforcrackingand
deterioration.If thereisanysignsofcrackingor deterioration,replace
beforereassemblingtheboiler.
12.Removesootfromfiresidesurfacesbybrushingdiagonallythroughthe
flue passages(see drawing).Care shouldbe taken so as not to
damagethetargetwallwiththefluebrush.
13.Carefullyvacuumsootaccumulationsfromthecombustionchamber
area,beingparticularlycarefulnottodamagethetargetwailandblanket
withthevacuum.Targetwallandblanketmustbeingoodconditionand
correctlyinstalledtoinsurepropercombustion.
\
oooooooooooo
ooooooo
%%%°°%%°2°
°j°o°2o%%%°2o°Co°2o
°°°°%02°%°o%%°°°0%%°Oo°
14. Reinstalltheburner/firedoorassembly.
15. Reinstallthefluecollectortopandsecurewiththetwobrasswingnuts.
16. ReinstalIthetopjacketpanel.Reconnectthefluepipe.
17. Inspectandcleantheoil burnerblowerwheel.
18. Oiltheburnermotor(DONOTOVEROIL}.
19.Removetheoilpumpcoverandclean/replacethepumpscreen.Carefully
reassemble.
20.Replacethefuelfilter(ifapplicable).
21.Reconnecttheelectricalandfuelsupplies.
22. Firethe burner,checkingfor propercombustionusingcombustiontest
equipment,makingadjustmentsasnecessary.
23.Insurethatallsafetycontrolsandoperatingcontrolsarefunctioning
properly.
IMPORTANTOPERATINGANDMAINTENANCEREQUIREMENTSKEEPYOURBOILERANDTHEAREAAROUNDIT
CLEANNEVERBURNREFUSEORANYMATERIALOTHERTHANTHESPECIFIEDFUELINYOURBOILERHAVEYOUR
BOILERCHECKEDEACHYEARBYAQUALIFIEDTECHNICIAN
_u me_javowalir_o_nven_ and servi_ calls _ ch_ these potn(s _m _ c_l for _r_ce.
Bu _ler may not _ iitng at proper
re[@
Burner may be shortocyct ag,
po_r _ boile_
OonttoIs o_t of adjustment
What: to
Reset themsostat above room tem_raIu 8.
Cean all flue passages and _'he'_nt pipe,
Nave burner c_ea_d and read ueted,
C_eek _e_f_e size if there is _y doubt,
Have burner adjusted
S_ort-r_cting {too frequent off and on) of bu[ner will cause s,aoti_ _f_r ar_df
or burner bec_e dirty at frequent in_ervaJs,dter eorreotino Itre drt conditior_....
also correct _he@n_ro_setting (or other _se e#_:heehorbcV_c4i_'_gl
Check thefm_sM he_[ _ntio pa,tor_d _rre_ _tt_, if neces_ry, per ine_r_t_or_
Check o,.,_ercurreetprotection Check to _ sure power supply circuit is "ON,
Reset accordi_ to in_r_l_ie_s packed with coatro/&
Check a_icontrol term_inatsan_ w#e ioinls,
HAV_ YOUR 8_RVIC_ TECHNICIAN CHECK ANY PROBLE_ YOU ARE UNAI_LE _ CORRECT.
COLORCODE
BK = BI_CK
BL = BLUE
W = WHITE
G = GREEN
i_ =WIRE NUT
pARTNO, - 146-34-O47
2 X 4 JUNCTION
PART NO, _45-31-O82
HANDY BOX COVER (NOT SHOWN)
PART N0. _46-61-121
LOCK-NUT (2
PART NO.
I/2" CLOSE
PART NO. 146-07-030
HONEYWELL
PRESSURETROL _
PART NO. 146-62-015
- GROUND SCREW
PART NO. 1€6-54-B02
-UNE VOLTAGE (GROUND)
LINE VOLTAGE (NEUT. LEAD)
\
_PRESSURETROL TO LWC.O HARNESS
PART NO, 433-00-873
OIL BURNER
PRIMARY RELAY
OPTIONAL LOW LIMIT
CONTROL FOR BOILERS
WITH TANKLESS COIL
\ z z
TO 24v
THERMOSTAT
LOW VOLTAGE WiRiNG HARNESS NOT FURNISHED
L BURNER TO L.WC.O. HARNESS
PART NO - 433-00-872
LINE VOLTAGE (NOT LEAD)
#2 TERMINAL LWCO
PART NO, 433--00--874
67D-1 LW*C,O,
W_RINGTERMINAL DETAIL
'tJ
WH_E
FROM OIL BURNER
BLACK LEAD
FROM OiL BURNER
McDONNELL M_LLER
L W.C.O
PART NO. 146-26-042
4 X 4 OIL BURNER
JUNCTION BOX
"_p_r_ Tsr_kle_ _i_ K_t4340_14 (ir_l:_s coJ_,_8{, and b_l_)
4
L_!
(1 _69BI0! )
BOILER
MODEL
3ES1.00(C)
3ES1,25(0)
3ES! .35(C)
4ES1,50(C)
4ES1,75(C)
4ES1,85(0)
SUGGESTED NOZZLES AND SETTINGS
FOR BECKETT AFG-M OIL BURNER SERIES
NOZZLE ACTUAL
0,85-60°W 1.00
1,10-70°B 1.25
1,20-70°B 1.35
1,25-60°B 1.50
1,50-60°B 1.75
1.75-60°B 1.85
PUMP
PRESSURE
(psig)
!40
140
!40
140
140
140
HEAD
ADJUSTMENT
1
1
1
3
3
AIR
SHUTTER
10
10
10
I0
10
10
AIR
BAND
1
1
2
2
3
4
OIL
BURNER
MODEL
AFG-50MB
AFG-50MD
AFG-50MD
AFG-50MD
AFG-50MD
AFG-50MD
FOR RIELLO R40 OIL BURNER SERIES
ACTUAL PU MP AI R OIL
BOILER NOZZLE TURBULATOR
MODEL (DELEVAN) INPUT PRESSURE SETTING GATE BURNER
RATE (gph) (psig) SETTING MODEL
3ES1,00(C) 0.85-60°W 1.00 150 2,0 3.00 F5
3ES1,25(C) 1.00-60°W 1.25 165 2.5 3.60 F5
3ESl.35(C) 1.10-60°W 1.35 165 3.5 4.25 F5
4ES1.50(C) 1.25-60°W 1.50 160 1.5 2.60 FIO
4ES1.75(C) 1.50-60°W 1.75 145 1,5 3.25 FIO
4ES1.85(C) 1.50-60°W 1.85 160 2.0 3.40 FIO
FOR CARLIN EZ OIL BURNER SERIES
BOILER NOZZLE I HEAD
[
MODEL (DELEVAN) ! SETTING
3ES1.00(C)
3ES1,25(C)
3ES1.35(C)
4ES1.50(C)
4ES1,50(C)
4ES1,65(C)
4ES1,85(0)
0.85x70ow
1.00x70°W
1, !Ox70°W
1.25x60°W
1,25x60°W
1.35x60°W
1,50x60°W
ACTUAL
INPUT
RATE (gph)
1.00
1.25
1.35
1.50
1.50
1.65
1.85
PUMP
PRESSURE
(psig)
150
150
150
150
150
150
150
0.85-1.00
0.85-1.00
1,10-1.25
1.10-1.25
0.85-!.00
1.50
! ,50
AIR BAND
SET
POINT
0.65
0.90
1.!0
1,10
1,65
1.65
2.00
OIL
BURNER
MODEL
EZ-1 HP
EZ-1 HP
EZ-I HP
EZ-1 HP
EZ-2 HP
EZ-2 HP
EZ-2 HP
All burners fired at an over fire pressure of -0,02"wc.
Burner insertion depth of 2-1/8" allows burner tip to
be 1/4" behind insulation, I NOTE: These settings are intended for ini-
I
tial start up only, Final adjustment must be
!
made using combustion test instruments, i
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Dunkirk 3ES1.25 Owner's manual

Category
Water heaters & boilers
Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI