15
2.5 Connecting the pipe network
There are various guidelines to be observed when installing the pipe network:
The piping must NEVER be glued to the detector input collector;
The pipe network MUST be fully glued (with the exception of the abovementioned point);
Use socket unions where necessary.
Caution: Do not insert ANY object other than piping into the collector. The insertion of objects may
accidentally damage the flow sensor located at the collector input.
.
Table 2-1: Specifications for collector input piping
Piping
IFT-P
25 mm (1 in)
25 mm
2 x 100 m
External diameter
2.6 Startup
After installation, the unit will need to be powered up in order to carry out the commissioning and
procedures and ensure correct operation in accordance with the piping layout connected.
After being connected to the power supply, the system requires 30 seconds to complete the startup
process.
If the detector is not switched on, check the connections and make sure the polarities have
been observed.
The detector may display faults immediately after power-up; this is normal. Reset it to restore the standby
mode of the fault relay.
2.7 Configuration
The device may be configured using:
the VSC software installed on a PC.
2.8 Flow standardisation
Flow standardisation is necessary in order for the detector to acquire the correct System flow value. This
function can be carried out using VSC and takes 6 minutes; we recommend NOT making any changes to
the detector configuration during this time.
The airflow depends on the fan speed (adjustable between 3 and 10). We recommend setting it to 5 unless
there are particularly long stretches of piping which require a different setting.
Once the pipe network has been completed, the detector will learn the current airflow value from both
collectors and will set this value to 100% of the flow.
Standardising the detector airflow using the VSC software
1. Remove the front cover.
2. Connect the detector to a PC with VSC installed on it.
3. Log in to the VSC program.
4. From the DEVICE menu, select STANDARDISE AIRFLOW.
5. Wait for approximately 10 minutes.