Fujitsu AUXB04GBLH Installation guide

Category
Split-system air conditioners
Type
Installation guide
English
INDOOR UNIT (Cassette Type)
PART NO. 9371022482-02
Deutsch
INNENGERÄT (Kassettentyp)
TM
FrançaisEspañol
UNITÉ INTÉRIEURE (type cassette)
UNIDAD INTERIOR (Tipo casete)
Italiano
UNITÀ INTERNA (tipo a cassetta)
ΕλληνικάPortuguês
ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ (Τύπος Κασέτας)
UNIDADE INTERIOR (Tipo Cassete)
РусскийTürkçe
ВНУТРЕННИЙ МОДУЛЬ (кассетного типа)
İÇ ÜNİTE (Kaset Tipi)
AUXB04GBLH
AUXB07GALH
AUXB09GALH
AUXB12GALH
AUXB14GALH
AUXB18GALH
AUXB24GALH
INSTALLATION MANUAL
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Nur für autorisiertes Fachpersonal.
MANUEL D’INSTALLATION
MANUAL DE INSTALACIÓN
Pour le personnel agréé uniquement.
Únicamente para personal de servicio autorizado.
MANUALE DI INSTALLAZIONE
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
MANUAL DE INSTALAÇÃO
Apenas para técnicos autorizados.
РУКОВОДСТВО ПО УСТАНОВКЕ
Только для авторизованного обслуживающего персонала.
Yalnızca yetkili servis personeli için.
MONTAJ KILAVUZU
[Original instructions]
Refer to the rating label with the serial number.
MADE IN P.R.C.
En-1
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual to the customer.
Request the customer to keep them on hand for future use, such as for relocating or
repairing the unit.
WARNING
This mark indicates procedures which, if improperly performed,
might lead to the death or serious injury of the user.
Request your dealer or a professional installer to install the unit in accordance with this
Manual.
An improperly installed unit can cause serious accidents such as water leakage, electric
shock, or re.
If the unit is instruction in disregard of the instructions in the Installation Manual, it will
void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents such
as electric shock or re.
If refrigerant leaks while work is being carried out, ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units
during operation. It will cause compressor failure as well as water leakage. First, stop
the indoor unit by operating the control unit, converter or external input device and then
cut the breaker.
Make sure to operate through the control unit, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and stop
in the daily work.
CAUTION
This mark indicates procedures which, if improperly performed,
might possibly result in personal harm to the user, or damage
to property.
Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by quali ed personnel with a capacity certi cate for handling
refrigerant uids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3mm for this unit.
The unit must be correctly earthed (grounded) and the supply line must be equipped
with a differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Never touch electrical components immediately after the power supply has been turned
off. Electric shock may occur. After turning off the power, always wait 5 minutes before
touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.
When moving, consult authorized service personnel for disconnection and installation of
the unit.
2. ABOUT THIS PRODUCT
2.1. Precautions for using the R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the
refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become
abnormally high and cause the piping to rupture.
If there is a refrigerant leakage, make sure that it does not exceed the concentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leakage occurs during operation, immediately vacate the premises and
thoroughly ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses the R410A refrigerant, use dedicated tools and piping materials
that have been manufactured speci cally for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than
the R22, failure to use dedicated piping material or improper installation can cause
rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
re.
Tool name Contents of change
Gauge manifold
Pressure is huge and cannot be measured with a conventional
(R22) gauge. To prevent erroneous mixing of other refrigerants,
the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high
pressure display range –0.1 to 5.3 MPa and a low pressure
display range –0.1 to 3.8 MPa.
Charging hose
To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump
A conventional (R22) vacuum pump can be used by installing a
vacuum pump adapter.
Be sure that the pump oil does not backflow into the system.
Use one capable for vacuum suction of –100.7 kPa (5 Torr,
–755 mmHg).
Gas leakage
detector
Special gas leakage detector for HFC refrigerant R410A.
INSTALLATION MANUAL
PART NO. 9371022482-02
VRF system indoor unit (Cassette type)
Contents
1. SAFETY PRECAUTIONS .........................................................................................1
2. ABOUT THIS PRODUCT..........................................................................................1
2.1. Precautions for using the R410A refrigerant ...................................................... 1
2.2. Special tool for R410A ....................................................................................... 1
2.3. Accessories .......................................................................................................2
2.4. Optional parts .................................................................................................... 2
3. INSTALLATION WORK ............................................................................................ 2
3.1. Selecting an installation location .......................................................................2
3.2. Installation dimensions ...................................................................................... 3
3.3. Discharge direction setting ................................................................................ 3
3.4. Installing the unit ................................................................................................ 3
4. PIPE INSTALLATION ............................................................................................... 4
4.1. Selecting the pipe material ................................................................................ 4
4.2. Pipe requirement ............................................................................................... 4
4.3. Flare connection (pipe connection) ...................................................................4
4.4. Installing heat insulation .................................................................................... 5
5. INSTALLING DRAIN PIPES ..................................................................................... 5
6. ELECTRICAL WIRING .............................................................................................6
6.1. Electrical requirement ........................................................................................ 7
6.2. Wiring method ...................................................................................................7
6.3. Unit wiring .......................................................................................................... 7
6.4. Connection of wiring ..........................................................................................8
6.5. External input and external output (Optional parts) ...........................................9
7. FIELD SETTING ..................................................................................................... 11
7.1. Setting the address .......................................................................................... 11
7.2. Custom code setting ........................................................................................ 12
7.3. Function setting ............................................................................................... 12
8. CASSETTE GRILLE INSTALLATION ..................................................................... 13
8.1. Remove the intake grille ..................................................................................13
8.2. Install cassette grille to indoor unit ..................................................................14
8.3. Attach the intake grille ..................................................................................... 14
9. TEST RUN ..............................................................................................................14
9.1. Test run using Outdoor unit (PCB) ................................................................... 14
9.2. Test run using Remote Controller .................................................................... 14
10. CHECK LIST ...........................................................................................................14
11. ERROR CODES .....................................................................................................15
En-2
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
water leakage, electric shock, or re.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Do not discard any accessories needed for installation until the installation work has
been completed.
Name and Shape Q’ty Application
Operating manual
1
Installation manual
1
(This book)
Cable tie (Large)
4
For fixing the connection pipe (Large
and Small)
Cable tie (Medium)
2
For transmission and remote
controller cable binding.
Coupler heat insulation (Small)
1
For indoor side pipe joint (Small)
Coupler heat insulation (Large)
1
For indoor side pipe joint (Large)
Special nut A (Large flange)
4
For installing indoor unit
Special nut B (Small flange)
4
For installing indoor unit
Template (Carton top)
1
For ceiling openings cutting
Also used as packing
Drain hose
1
For installing drain pipe
VP25 (O.D.32, I.D.25)
Hose band
1
For installing drain hose
Drain hose insulation
1
For installing drain pipe
Cassette grille accessories
Name and Shape Q’ty Application
Connector cover
1
For covering connector
Tapping screw
(M5 × 12mm)
4
For mounting cassette grille
Tapping screw
(M4 × 12mm)
1
For mounting connector cover
2.4. Optional parts
Description Model Application
External connect kit
UTY-XWZXZC
For output function
(Output terminal / CNB01)
UTY-XWZXZB
For control input function
(Apply voltage terminal / CNA01)
UTY-XWZXZD
For control input function
(Dry contact terminal / CNA02)
UTY-XWZXZ7
For forced thermostat off function
(Apply voltage terminal / CNA03)
UTY-XWZXZE
For forced thermostat off function
(Dry contact terminal / CNA04)
Insulation kit for high
humidity
UTZ-KXGC
Install when the condition under the
roof is over 80% in humidity and
over 30°C in temperature.
3. INSTALLATION WORK
Correct initial installation location is important because it is dif cult to move unit after it is
installed.
3.1. Selecting an installation location
WARNING
Select installation locations that can properly support the weight of the indoor. Install the
units securely so that they do not topple or fall.
CAUTION
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
Area that can cause combustible gas to leak, contains suspended carbon bers or
ammable dust, or volatile in ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, power supply cable, transmission cable, and remote controller
cable at least 1 m away from a television or radio receivers. The purpose of this is to
prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under some
signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Use the “Insulation kit for high humidity” (option), when the condition under the roof
is over 80% in humidity and over 30°C in temperature. Otherwise, there is a risk of
condensation on the ceiling.
En-3
Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suf cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not ampli ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the lter can be removed.
3.2. Installation dimensions
• Leave the space speci ed in Fig. A so that the air from the blower will cover the entire
room.
• Install the indoor unit on a place having a suf cient strength so that it withstands
against the weight of the indoor unit.
• A place from where drainage can be extracted outdoors easily.
WARNING
Never install in a room where there is the potential of leaking ammable gas. A spark
could ignite the gas and cause an explosion or re.
Avoid installing in a location with high temperature.
Fig. A
Obstruction
1,800 mm to H
1,000 mm or
more
1,000 mm or
more
Floor
Strong and durable ceiling
262 mm
or more
H: Maximum height from oor to ceiling
Model name
H (mm)
AUXB04 AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24
Standard mode 2,700 2,700 2,700 2,700 2,700 2,700 2,700
High Ceiling
mode
- - - 3,000 3,000 3,000 3,000
* Be sure to make the function settings with the remote controller according to the
installed ceiling height.
3.3. Discharge direction setting
• The discharge direction can be selected as shown below.
Fig. B
(4 directions)
(3 directions)
100 mm or more
Piping position
* Select the most appropriate air ow direction from 3 or 4 directions according to the
shape of the room and the installation position.
* When changing the number of outlets, we recommend using the optional AIR OUTLET
SHUTTER PLATE KIT to close the outlet.
* For the speci c closing pattern, please refer to the attached AIR OUTLET SHUTTER
PLATE KIT’S MANUAL. (Do so before installing the cassette grille as it will be installed
on the body.)
3.4. Installing the unit
WARNING
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
When fastening the hangers, make the bolt positions uniform.
Perform nal tightening by tightening the double nut rmly. The product may fall if not
installed properly.
Using a level, or vinyl hose lled with water, ne adjust so that the body is level.
Install the air conditioner as follows.
Indoor unit installation
(1) Make the holes for installing in the ceiling (Fig. D).
(2)
Install the hanging bolts (M10), refer to the position in Fig. C.
(3) Install special nut A, then special nut B onto the hanging bolt (Fig. D).
(4) Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(5) Turn special nut B to adjust the height of the body.
(6) Be sure to leave service access for future service at the designated position.
Fig. C
530 mm (Hanging bolt position)
540 mm (Hanging bolt position)
570 mm (Indoor unit)
580 to 660 mm (Ceiling openings)
700 mm (Cassette grille)
135 mm
250 mm
150 to 200 mm
Min. 450 mm
Service access
75 mm
Min. 450 mm
Fig. D
Drain pipe (O.D. ø25.4)
40 mm
99 mm
102 mm
146 mm
245 mm
30 mm
262 mm
30 mm
58 mm
123 mm
Ceiling
Control box
Liquid pipe
Gas pipe
40 mm
En-4
Special nut A
Special nut B
Hook
Hanging bolt
30 mm or more
After installing the body,
tighten the nuts.
19 mm
Ceiling
Indoor unit
Leveling
• Using a level, or vinyl hose lled with water, ne adjust so that the body is level.
• Inclined installation so as the drain pipe side is higher may cause a malfunction of the
oat switch, and may cause water leakage.
Vinyl hoses
Drain pipe
4. PIPE INSTALLATION
CAUTION
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant R410A models. Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.
4.1. Selecting the pipe material
CAUTION
Do not use existing pipes from another refrigeration system or refrigerant.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion
(especially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary to
choose adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are
available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in)] Thickness [mm]
6.35 (1/4) 0.80
9.52 (3/8) 0.80
12.70 (1/2) 0.80
15.88 (5/8) 1.00
19.05 (3/4) 1.20
4.2. Pipe requirement
CAUTION
Refer to the installation manual for the outdoor unit for description of allowable pipe
length and height difference.
Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the
expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker and
if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. If
heat insulation is used that is not as thick as speci ed, condensation may form on the
surface of the insulation. In addition, use heat insulation with heat conductivity of 0.045
W/(m·K) or less (at 20 °C).
4.3. Flare connection (pipe connection)
WARNING
Tighten the flare nuts with a torque wrench using the specified tightening method.
Otherwise, the are nuts could break after a prolonged period, causing refrigerant to
leak and generate hazardous gas if the refrigerant comes into contact with a ame.
4.3.1. Flaring
Use special are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)
Insert the are nut (always use the are nut attached to the indoor and outdoor units (or
RB unit) respectively) onto the pipe and perform the are processing with a are tool. Use
the special R410A are tool. Leakage of refrigerant may result if other are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Pipe
A
Die
B
Check if [L] is ared uniformly and
is not cracked or scratched.
Pipe outside diameter
[mm (in)]
Dimension A [mm]
Dimension B
-
0
0.4
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional (R22) are tools to are R410A pipes, the dimension A should
be approximately 0.5 mm more than indicated in the table (for aring with R410A are
tools) to achieve the speci ed aring. Use a thickness gauge to measure the dimension A.
It is recommended that a R410A aring tool is used.
Width across
ats
Pipe outside diameter
[mm (in)]
Width across flats of
Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
4.3.2. Bending pipes
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it
dif cult to bend or stretch them any more.
• Do not bend or stretch the pipes more than 3 times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
En-5
4.3.3. Pipe connection
When the are nut is tightened properly by your hand, hold the body side coupling with
a separate spanner, then tighten with a torque wrench. (See the table below for the are
nut tightening torques.)
CAUTION
Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to
tighten the are nut correctly.
Connection pipe
Flare nut
Tighten with 2 wrenches.
Torque wrench
Indoor unit pipe
(Body side)
Holding wrench
Flare nut [mm (in)]
Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
4.4. Installing heat insulation
Install the heat insulation material after performing a refrigerant leak check (see the In-
stallation Manual for the outdoor unit for details).
Coupler heat insulation
• Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid
pipe of indoor side.
• After installing the coupler heat insulation, wrap both end with vinyl tape so that there
is no gap.
• After af xing the coupler heat insulation, secure it with 2 cable ties (large), one on
each end of the insulation.
• Make sure that the cable ties overlap the heat insulation pipe.
Coupler heat insulation
(Accessories)
Cable tie (Large)
(Accessories)
Heat insulation
Heat insulation
Cover this portion with
heat insulation.
CAUTION
After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform
this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
5. INSTALLING DRAIN PIPES
WARNING
Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat
exchange erosion may occur)
Insulate the parts properly so that water will not drip from the connection parts.
Check for proper drainage after the construction by using the visible portion of
transparent drain port and the drain piping nal outlet on the body.
CAUTION
Do not apply adhesive agent on the drain port of the body. (Use the attached drain hose
and connect the drain piping)
• Install the drain pipe with downward gradient (1/100 to 1/50) and so there are no rises
or traps in the pipe. Unsmooth draining caused by accumulated water ow in the pipe
may cause clogged drain.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
• When the pipe is long, install supporters.
• Do not perform air bleeding. Drainage may be blown out.
• Always heat insulate the indoor side of the drain pipe.
• If it is impossible to have suf cient gradient of pipe, perform drain lift-up.
Pipe size
Drain pipe VP25 (O.D. 32 mm)
Hanging ttings
VP25 (O.D. 32 mm)
Downward gradient 1/100 to 1/50
1.5 to 2 m
Rise
PROHIBITED:
Trap Air bleeding
When lifting up drain:
• Height of inclined pipe should be less than 700 mm from the ceiling. A rise dimension
over this range will cause leakage.
• Lift up the pipe vertically at the position of 300 mm or less from the unit.
VP25 (O.D. 32 mm)
local arrangement
VP30 (O.D. 38 mm) or more
Downward gradient 1/100 to 1/50
Downward gradient
1/100 to 1/50
300 mm or less
700 mm or less
700 mm or less
Horizontal or
upward gradient
En-6
Working procedure
(1) Install the attached drain hose to the drain port of the body. Install the hose band
from the top of the hose within the graphic display area.
(2) Use vinyl adhesive agent to glue the drain piping (PVC pipe VP25) which is prepared
on site or elbow socket.
(Apply color adhesive agent evenly until the gauge line and seal)
(3) Check the drainage. (See separate diagram)
(4) Install the heat insulation.
(5) Use the attached heat insulation to insulate the drain port and band parts of the
body.
Install the knob
faces upward
Locally arranged
vinyl pipe
Attached drain hose
(Accessories)
Attached heat insulation
(Accessories)
Attached hose band
(Accessories)
Drain hose
Hose band
20 mm
Transparent
visible portion
5 to 10 mm
Applying area
of adhesive
Gauge line
Drain
hose
4 mm or less
35 mm
Wind the attached heat insulation
around the hose band
Make sure the
alignment is on top
Make sure there
are no gaps
(a) Top view
(b) Side view
(c) Hose opening view
(d) Top view
20 mm
NOTE: Check for drainage
Pour about 1 liter of water from the position shown in the diagram or from the air ow
outlet to the dew tray. Check for any abnormalities such as strange noises and whether
the drain pump functions normally.
Watering pot
Drain pipe
Wire cover
Screw
6. ELECTRICAL WIRING
WARNING
Electrical work must be performed in accordance with this Manual by a person certi ed
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insuf cient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or re.
Before starting work, check that power is not being supplied to the all units.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as
overheating the terminals, electric shock, or re.
Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as electric
shock or re through exposure to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insuf cient insulation, or exceeding the allowable
current can cause electric shock or re.
Do not modify the power cables, use extension cables, or use any branches in the
wiring. Improper connections, insuf cient insulation, or exceeding the allowable current
can cause electric shock or re.
Match the terminal block numbers and connection cable colors with those of the outdoor
unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or re.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric discharge may occur.)
Install an earth leakage breaker. In addition, install the earth leakage breaker so that the
entire AC main power supply is cut off at the same time. Otherwise, electric shock or re
could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable rmly to the terminal board. Imperfect installation may
cause a re.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly quali ed persons in order to avoid a hazard.
CAUTION
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote control cable
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of the
PCB. Follow the cautions below:
Establish an earth (ground) for the indoor and outdoor units and peripheral
devices.
• Cut power (breaker) off.
Touch metal part of the indoor units for more than 10 seconds to discharge static
electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
En-7
6.1. Electrical requirement
Voltage rating
230 V
Operating range 198 to 264 V (50 Hz)
198 to 253 V (60 Hz)
• Select the power cable type and size in accordance with relevant local and national
regulations.
Speci cations for local wiring power cord and branch wiring are in compliance with local code.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Breaker should be installed at every refrigerant system. Do not use a breaker in a different
refrigerant system.
Refer to the table for the breaker speci cations of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
Model MCA MFA
AUXB04GBLH 0.20 A
20 A
AUXB07GALH 0.20 A
AUXB09GALH 0.20 A
AUXB12GALH 0.24 A
AUXB14GALH 0.29 A
AUXB18GALH 0.30 A
AUXB24GALH 0.75 A
MCA: Minimum Circuit Ampacity
MFA: Maximum Fuse Ampacity
When the power crossover wiring is done, make it so that the total of the MCA of the
connected RB units and indoor units does not exceed the 15 A. For RB unit MCA, refer to
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Breaker capacity
* Maximum connectable “indoor units” or
“indoor units + RB units”
30 mA, 0.1 sec or less 44 or less **
100 mA, 0.1 sec or less 45 to 148
* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
** If the total number of units connected to the breaker exceeds 44, either add a 30mA
breaker, or use breakers with a greater capacity.
6.1.1. Cable speci cations
Recommended
cable size (mm
2
)
Cable type Remark
Power supply
cable
2.5
Type60245 IEC57
or equivalent
2 Cable + earth
(ground)
Transmission
cable
0.33
LONWORKS
compatible cable
22 AWG LEVEL 4
(NEMA) non-polar 2
core, twisted pair solid
core diameter 0.65 mm
Remote
controller cable
(2-wire type)
0.33 to 1.25
Sheathed PVC
cable*
Non-polar 2 core,
twisted pair
Remote
controller cable
(3-wire type)
0.33
Sheathed PVC
cable*
Polar 3 core
*: Use shielded cable in accordance with local rules for remote controller cable.
6.2. Wiring method
*2 *2
*3 *3
*2
*3
Outdoor unit or RB unit *1
Example
Transmission
Transmission
Indoor unit
Remote controller
(Master)
Power supply
Indoor unit Indoor unit
Power supply
Remote
control
Breaker
Breaker
Breaker
Remote controller
(Slave)
Remote controller
*1: When connecting to the Heat Recovery System, refer to the installation manual of the
RB unit.
*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
*3: When connecting the 2-wire type remote controller, Y3 is not used.
Power supply
Power supply
Power supply
Power supply
Indoor unit
Pull box
Indoor unit
Indoor unit
Breaker
Pull box
(Crossover wiring of power supply)
6.3. Unit wiring
Before attaching the cable to terminal block.
6.3.1. Power supply cable
Adjust the length of power supply cable to avoid excessive tension with referring gure
below.
Earth (Ground)
cable
20 mm
50 mm
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after
looping it around the end of the cable.
(2) Use the speci ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not x 2 power supply cables with 1 screw.
Strip 25 mm
Loop
Screw with
special washer
Screw with
special washer
Cable end (Loop)
Cable end (Loop)
Cable
Cable
Terminal block
En-8
WARNING
When using solid core cables, do not use the ring terminal. If you use the solid core
cables with the ring terminal, the ring terminal's pressure bonding may malfunction and
cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the speci ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not x 2 power supply cables with 1 screw.
Strip 10 mm
Sleeve
Screw with
special washer
Screw with
special washer
Ring terminal
Cable
Cable
Terminal block
Ring terminal
Ring terminal
WARNING
Use ring terminals and tighten the terminal screws to the speci ed torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
Tightening torque
M4 screw (Power supply /L, N, GND) 1.2 to 1.8 N•m (12 to 18 kgf•cm)
6.3.2. Transmission and Remote controller cable
Shielded cable (no lm)
For 3-wire type For 2-wire type
30 mm
40 mm
30 mm
30 mm
Transmission cable
Remote controller cable
• Connect remote controller and transmission cables as shown in Fig. C.
Fig. C
GOOD
Different diameter
Connect to 1 side
PROHIBITED
WARNING
Tighten the terminal screws to the speci ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
Tightening torque
M3 screw (Transmission /X1, X2)
(Remote controller /Y1, Y2, Y3)
0.5 to 0.6 N•m (5 to 6 kgf•cm)
CAUTION
To peel the lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the wire by overtightening the
screw. On the other hand, an undertightened screw can cause faulty contact, which will
lead to a communication failure.
6.4. Connection of wiring
(1) Remove the control box cover and install each connection cable.
Screw
Control box cover
(2) Connect the connection cable, with the cable tie.
CAUTION
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
En-9
SW1
2WIRE
3WIRE
Cable clamp
L, N:
Power supply cable
Y1,Y2,Y3: Remote
controller cable
Cable tie (Medium)
(Accessories)
X1, X2:
Transmission cable
DIP switch (SW1)
For 2-wire type For 3-wire type
Connect the remote
controller cable
Y1: Non-polar
Y2: Non-polar
Y3: Do not connect *1
Y1: Red
Y2: White
Y3: Black
Set the DIP switch (SW1) 2WIRE (Factory setting) 3WIRE
*1: If you connect the remote controller cable to the terminal Y3, 2-wire type
remote controller does not work.
(3) Install control box cover.
CAUTION
Do not bundle the remote controller cable, or wire the remote controller cable in
parallel, with the indoor unit connection cable (to the outdoor unit) and the power
supply cable. It may cause erroneous operation.
6.5. External input and external output (Optional parts)
Controller PCB
Dry contact terminal
Apply voltage terminal
(CNA04) (CNA02)
(CNA01)
(CNA03)
DIP switch
(SET 2)
Output terminal
(CNB01)
ON OFF
SW4
SW3
SW2
SW1
(1) External input
Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
“Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected
with function setting of indoor unit.
Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of termi-
nals cannot be used simultaneously.)
Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Input
device 1
Input
device 2
Input
device 3
Load resis-
tance
Load resis-
tance
Load resis-
tance
*1
DC power supply
12 to 24V
connected unit
*a
*a
*a
P.C.B
CNA01
CNA03
*b
*1
Make the power supply DC12 to 24V. Select a power supply capacity with an ample sur-
plus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power supply
12 to 24V
connected unit
Load resis-
tance
P.C .B
P.C .B
CNA01
P.C .B
Input
device 1
Input
device 2
Indoor unit
Indoor unit
Indoor unit
Load resis-
tance
CNA01
CNA01
Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
P.C .B
GND
Ch 1
Ch 3
*c
*c
*c
*d
Ch 2
CNA02
CNA04
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suf ciently careful when wiring.
En-10
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
Power supply for relay
Indoor unit
Indoor unit
Indoor unit
Input device 2
Input device 1
K1 - K6: Relay
(Device for DC Current)
P.C .B
K1
P.C .B
P.C .B
CNA02
K2
K3
K4
K5
K6
CNA02
CNA02
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
Operation behavior
Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
Pulse
The width of pulse
must be longer than
200msec.
Edge
DIP switch [Set 2 SW2] Input signal type
OFF (Factory setting) Edge
ON Pulse
When function setting is “Operation/Stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Operation
ON OFF Stop
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Operation
Ch2 OFF ON Stop
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Emergency stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Emergency stop
Ch2 OFF ON Normal
* All indoor units of same refrigerant system stops when Emergency stop operates.
When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Forced stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Forced stop
Ch2 OFF ON Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
Forced thermostat off function
[“Edge” input only]
Connector Input signal Command
Ch3 of CNA03 or CNA04
OFF ON Thermostat off
ON OFF Normal
(2) External output
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
Output voltage: Hi DC12V±2V, Lo 0V.
Permissible current: 50mA
Output select
When indicator etc. are connected directly
Operation indicator
Error indicator
Indoor unit Fan
status indicator
connected unit
P.C .B
CNB
01
When connecting with unit equipped with a power supply
CNB
01
P.C .B
Connected
device 1
Connected
device 2
Connected
device 3
connected unit Relay (locally purchased)
Operation behavior
Connector Output voltage Status
CNB01
External output1
Pins 1-2
0V Stop
DC 12 V Operation
External output2
Pins 1-3
0V Normal
DC 12 V Error
External output3
Pins 1-4
0V Indoor unit fan stop
DC 12 V Indoor unit fan operation
En-11
Setting
Setting
range
Type of switch
Indoor unit
address
0 to 63
Setting example
2
IU AD×10 IU AD×1
Refrigerant circuit
address
0 to 99
Setting example
63
REF AD×10 REF AD×1
(1) Indoor unit address
Rotary switch (IU AD ×1)...Factory setting “0”
Rotary switch (IU AD ×10)...Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A
.
(2) Refrigerant circuit address
Rotary switch (REF AD ×1)...Factory setting “0”
Rotary switch (REF AD ×10)...Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
• If working in an environment where the wireless remote controller can be used, the
addresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit
address and refrigerant circuit address to “00”.
(For information on setting using the wireless remote controller.)
Table A
Address Rotary
switch setting
Address Rotary
switch setting
Refrigerant
circuit
REF AD SW
Indoor unit
IU AD SW
× 10 × 1 × 10 × 1
000000
101101
202202
303303
404404
505505
606606
707707
808808
909909
10 1 0 10 1 0
11 1 1 11 1 1
12 1 2 12 1 2
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
99 9 9 63 6 3
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting “0”
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting
range
Type of switch
Remote controller
address
0 to 15
Setting
example 0
RC AD
(3) Connection methods
• Wire modi cation
Remove insulation from wire attached to wire kit connector.
Remove insulation from locally purchased cable. Use crimp type insulated butt connec-
tor to join eld cable and wire kit wire.
Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Option parts:
External input /output wire
Solder and insulate the connected parts.
Locally purchased
• Connection terminals and wiring arrangement
In following gure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
CNA02
CNA04
CNA03
Cable tie (locally purchased):
Bind to the transmission cable
CNA01 CNB01
Transmission cable
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD
, REF AD SW settings
............. This section (7.1. Setting the address)
(2) Remote controller settings ...............
Refer to the wired or wireless remote controller
manual for detailed setting information. (Set IU
AD, REF AD SW to 0)
(3) Automatic address settings .............
Refer to the outdoor unit manual for detailed
setting information. (Set IU AD, REF AD SW to 0)
CAUTION
Be sure to turn OFF the power before performing the eld setting.
7.1. Setting the address
CAUTION
Use an insulated screwdriver to set the dip switches.
Rotary switch
Example: “0”
Rotary switch
Example: “0”
En-12
Example
If 4 indoor units are connected.
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
Indoor unit
Remote
controller
Indoor unit Indoor unit Indoor unit
RC AD SW 01234567
Address
01234567
RC AD SW
89ABCDEF
Address
8 9 10 11 12 13 14 15
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting “0”
Since the remote controller address settings are automatically con gured, you do not
need to con gure them.
If con guring manually, it is necessary to con gure both the indoor unit and the remote
controller. For details, please refer to the remote controller manual.
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1 , SW2, referring to the Table B.
ON
OFF
SW
1
SW
2
SW
3
SW
4
DIP switch “SET3”
Table B
Custom code
A (Factory setting) B C D
DIP switch SET 3 SW1 OFF ON OFF ON
DIP switch SET 3 SW2 OFF OFF ON ON
CAUTION
Do not operate any switches other than prescribed, as it can cause the unit to operate
improperly or malfunction.
7.3. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address.” for indoor unit address and refrigerant circuit
address settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number Default Details
Filter indica-
tor interval
11
00 Standard
Adjust the lter cleaning interval
noti cation. If the noti cation is too early,
change to setting 01. If the noti cation is
too late, change to setting 02.
01 Longer
02 Shorter
Filter indica-
tor action
13
00 Enable
Enable or disable the lter indicator. Set-
ting 02 is for use with a central remote
controller.
01 Disable
02
Display only on
central remote
controller
Ceiling
air ow
20
00 Standard
Regulate the air ow according to the
needs of the installation location. When
set to 01, the air ow will be stronger.
(Cassette type only)
01 High Ceiling
Vertical air-
ow direction
23
00 Standard
Adjust the vertical air ow direction. All
air ow direction louvers are adjusted
together.
(Cassette type only)
01 Raise
Cool air
temperature
trigger
30
00 Standard
Adjust the cool air trigger temperature.
To lower the trigger temperature, use
setting 01. To raise the trigger tempera-
ture, use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 Standard
Adjust the heat air trigger temperature.
To lower the trigger temperature by 6
degrees C, use setting 01. To lower the
trigger temperature by 4 degrees C, use
setting 02. To raise the trigger tempera-
ture, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart 40
00 Enable
Enable or disable automatic system
restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold air ow with making
the air ow lower when starting
heating operation. To correspond to
the ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all refrig-
erant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
Change the target for reporting errors.
Errors can either be reported in all
locations, or only on the central remote
controller.
01
Display only on
central remote
controller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
When set to 01, the fan stops when
the thermostat is OFF in cooling op-
eration. Connection of the wired re-
mote controller (2-wire type or 3-wire
type) and switching its thermistor are
necessary.
01 Stop
(Forbidden) 60 00
(Forbidden) 61 00
(Forbidden) 62 00
En-13
7.3.1. Button name and function
OPERATION indicator lamp (Green)
FILTER indicator lamp (Red)
TIMER indicator lamp (Orange)
MANUAL AUTO button
7.3.2. Checking the function settings
Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to
normal operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indication pattern
Indoor unit
address
Refrigerant address
OPERATION indicator lamp
(Green)
ON Flash (1.0s ON/1.0s OFF)
TIMER indicator lamp (Orange) Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red) Address: ones place (0.5s ON/0.5s OFF)
Indoor unit address example
(Example) ADDRESS : 24
OPERATION
indicator lamp
(Green)
TIMER
indicator lamp
(Orange)
FILTER
indicator
lamp (Red)
10 sec
1 cycle 12 sec
8 sec
ON
OFF
0.5s
0.5s 0.5s 0.5s
0.5s
0.5s
0.5s 0.5s
0.5s
0.5s
0.5s 0.5s
ON
OFF
ON
OFF
ON
Refrigerant address example
(Example) ADDRESS : 30
OPERATION
indicator lamp
(Green)
TIMER
indicator lamp
(Orange)
FILTER
indicator
lamp (Red)
9 sec
1 cycle 12 sec
ON
OFF
1.0s 1.0s 1.0s
1.0s 1.0s 1.0s 1.0s
0.5s
0.5s
0.5s 0.5s 0.5s 0.5s
ON
OFF
ON
OFF
OFF
• Setting details
Function number Item Setting number
01 Indoor unit address 00 to 63
02 Refrigeration address 00 to 99
For use with a remote controller, set all rotary switches to 0, and refer to “7.1. Setting the
address” for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name Indication pattern
OPERATION indicator lamp (Green)
Function number; tens place (0.5s ON/0.5s
OFF)
TIMER indicator lamp (Orange)
Function number; ones place (0.5s ON/0.5s
OFF)
FILTER indicator lamp (Red) Setting number: (0 to 9) (0.5s ON/0.5s OFF)
(Example) Function : 31, Setting number : 2
OPERATION
indicator lamp
(Green)
TIMER
indicator lamp
(Orange)
FILTER
indicator
lamp (Red)
11 sec
10 sec
9 sec
1 cycle 12 sec
ON
OFF
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
ON
OFF
ON
OFF
8. CASSETTE GRILLE INSTALLATION
8.1. Remove the intake grille
(1) Slide the 2 grille hook
Grille hook
(2) Open the intake grille and remove.
En-14
8.2. Install cassette grille to indoor unit
(1) Install the cassette grille on the indoor unit.
“DRAIN” mark
“PIPE” mark
* Align the stamped marks on the cassette grille against the pipe and the drain of the
indoor unit.
CAUTION
Use only the supplied screws to install the cassette grille.
Indoor unit
Ceiling
No gap between ceiling and
cassette grille around entire
periphery
5 to 7 mm
Cassette grille
Sealant
(2) Connect the connector.
Cable (louver): WHITE
Cable (display): WHITE
Cable (louver): RED
Indoor unit side
• Arrange the cables as illustrated below.
(3) Attach the connector cover.
Screw
Connector cover
8.3. Attach the intake grille
The installation is the reverse of “8.1. Remove the intake grille”.
The intake grille can be rotated and installed 4 ways to suit the user’s preference.
CAUTION
The louver angle cannot be changed if the power is not on, (If moved by hand, it may
be damaged.)
The grille assembly is directional relative to the air conditioner body.
Install so that there is no gap between the grille assembly and the air conditioner body.
9. TEST RUN
9.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
9.2. Test run using Remote Controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator
lamps ash slowly at the same time.
10. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS If not performed correctly
CHECK
BOX
Has the indoor unit been installed
correctly?
Vibration, noise, indoor unit
may drop
Has there been a check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation work been
completed?
Water leakage
Does water drain easily from the indoor
units?
Water leakage
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
No operation, heat or burn
damage
Are the wires and pipes all connected
completely?
No operation, heat or burn
damage
Is the indoor unit earthed (grounded)? Short circuit
Is the connection cable the specified
thickness?
No operation, heat or burn
damage
Are the inlets and outlets free of any
obstacles?
No cooling, No heating
Does start and stop air conditioner
operation by remote control unit or
external device?
No operation
After installation is completed, has the
proper operation and handling been
explained to the user?
En-15
11. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote control-
ler display. If you use a wireless remote controller, the lamp on the photodetector unit
will output error codes by way of blinking patterns. See the lamp blinking patterns and
error codes in the table below.
Error indications
Wired Remote
Controller
Error code
Error contents
OPERATION
lamp (green)
TIMER
lamp
(orange)
FILTER
lamp (red)
(1) (2)
Remote controller
communication error
(1) (4)
Network communication error
(1) (6)
Peripheral unit communication
error
(2) (6)
Indoor unit address setting
error
(2) (9)
Connection unit number error
in wired remote controller
system
(3) (1)
Indoor unit power supply
abnormal
(3) (2)
Indoor unit main PCB error
(3) (10)
Indoor unit communication
circuit (wired remote controller)
error
(4) (1)
Indoor unit room temp.
thermistor error
(4) (2)
Indoor unit heat ex. temp.
thermistor error
(5) (1)
Indoor unit fan motor 1 error
(5) (2)
Indoor unit coil (expansion
valve) error
(5) (3)
Indoor unit water drain
abnormal
(9) (15)
Outdoor unit miscellaneous
error
(10) (8)
Poor refrigerant circulation
(13) (1)
RB unit error
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of ashing
Wired remote controller display
UTY-RNKY / UTY-RNKG / UTY-RNKYT (3-wire type)
UTY-RNRY / UTY-RNRG (2-wire type)
Error code
Error icon
Touch the [Status].
Touch the [Error Information].
2-digit numbers are corresponding to
the error code in the preceding table.
For more information, refer to the installation manual of the remote controller.
Touch the [Next Page] (or [previous page])
to switch to other indoor unit information.
UTY-RLRY / UTY-RLRG (2-wire type)
Error code
Error icon
For more information, refer to the installation manual of the remote controller.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Fujitsu AUXB04GBLH Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI