Fujitsu RDG12LLTA Installation guide

Category
Split-system air conditioners
Type
Installation guide
INSTALLATION MANUAL
For authorized service personnel only.
INSTALLATIONSANLEITUNG
Nur für autorisiertes Personal.
MANUEL D'INSTALLATION
Pour le personnel agréé uniquement.
MANUAL DE INSTALACIÓN
Solo para personal autorizado.
MANUALE D'INSTALLAZIONE
Ad uso esclusivo del personale autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
Για εξουσιοδοτημένο προσωπικό σέρβις.
MANUAL DE INSTALAÇÃO
Apenas para técnicos autorizados.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для уполномоченного персонала.
KURULUM KILAVUZU
Yetkili servis personeli içindir.
INSTALLATION MANUAL
AIR CONDITIONER
INDOOR UNIT
Duct Type
hcstueDsiaçnarFloñapsEonailatIάkIvηλλEsêugutroP
hsilgnE
eçkrüT
йикссуР
PART NO. 9374815173-04
9374815173-04_IM.indb 1 9/21/2011 1:45:04 PM
En-1
CAUTION!
This mark indicates procedures which, if improperly performed,
might possibly result in personal harm to the user, or damage to
property.
Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
Th
e installation must be carried out in compliance with regulations in force
in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3mm for this unit.
The unit must be correctly grounded and the supply line must be equipped with a
differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Never touch electrical components immediately after the power supply has been turned
off. Electric shock may occur. After turning off the power, always wait 5 minutes before
touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service
personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation of
the unit.
2. ABOUT THE UNIT
2.1. Precautions for using the R410A refrigerant
WARNING
• Do notintroduceanysubstance other than the prescribed refrigerant into the
refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become
abnormally high and cause the piping to rupture.
• Ifthereisarefrigerantleakage,makesurethatitdoesnotexceedtheconcentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such
as oxygen starvation.
• Do nottouch refrigerant thathas leaked fromthe refrigerant pipe connections or
other area. Touching the refrigerant directly can cause frostbite.
• If a refrigerant leakage occurs during operation, immediately vacate the premises
and thoroughly ventilate the area.
 Iftherefrigerantcomesincontactwithaame,itproducesatoxicgas.
2.2. Special tool for R410A
WARNING
• To install a unit that uses the R410Arefrigerant, use dedicated toolsand piping
materialsthathavebeenmanufacturedspecicallyforR410Ause.
 BecausethepressureoftheR410Arefrigerantisapproximately1.6timeshigherthan
the R22, failure to use dedicated piping material or improper installation can cause
rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
re.
Tool name Contents of change
Gauge manifold
•Pressureishugeandcannotbemeasuredwithaconventional
gauge. To prevent erroneous mixing of other refrigerants, the
diameter of each port has been changed.
It is recommended to use a gauge manifold with a high
pressuredisplayrange–0.1to5.3MPaandalowpressure
displayrange–0.1to3.8MPa.
Charging hose
•Toincreasepressureresistance,thehosematerialandbase
size were changed.
Vacuum pump
• Aconventionalvacuumpumpcanbeusedbyinstallinga
vacuum pump adapter.
Gas leakage
detector
•SpecialgasleakagedetectorforHFCrefrigerantR410A.
1. SAFETY PRECAUTIONS
• BesuretoreadthisManualthoroughlybeforeinstallation.
• ThewarningsandprecautionsindicatedinthisManualcontainimportantinformation
pertaining to your safety. Be sure to observe them.
• HandthisManual,togetherwiththeOperatingManualtothecustomer.
Request the customer to keep them on hand for future use, such as for relocating or
repairing the unit.
WARNING!
This mark indicates procedures which, if improperly performed,
might lead to the death or serious injury of the user.
• Requestyourdealeroraprofessionalinstallertoinstalltheunitinaccordancewith
thisManual.
An improperly installed unit can cause serious accidents such as water leakage,
electricshock,orre.
 IftheunitisinstalledindisregardoftheinstructionsintheInstallationManual,itwill
void the manufacturer’s warranty.
• DonotturnONthepoweruntilallworkhasbeencompleted.
 Turning ON the power before thework is completed can cause serious accidents
suchaselectricshockorre.
• Ifrefrigerantleakswhileworkisbeingcarriedout,ventilatethearea.
Iftherefrigerantcomesincontactwithaame,itproducesatoxicgas.
• Installationworkmustbeperformedinaccordancewithnationalwiringstandardsby
authorized personnel only.
• ExceptforEMERGENCY, neverturn offmainas wellassub breakerof theindoor
units during operation. It will cause compressor failure as well as water leakage.
First, stop the indoor unit by operating the control unit, converter or external input
device and then cut the breaker.
 Makesuretooperatethroughthecontrolunit,converterorexternalinputdevice.
When the breaker is designed, locate it at a place where the users cannot start and
stop in the daily work.
INSTALLATION MANUAL
PARTNO.9374815173-04
INDOORUNIT(DuctType)
Contents
1. SAFETYPRECAUTIONS ..........................................................................................1
2. ABOUTTHEUNIT
2.1.PrecautionsforusingtheR410Arefrigerant .......................................................1
2.2.SpecialtoolforR410A ........................................................................................1
2.3. Accessories ........................................................................................................2
2.4.Optionalparts .....................................................................................................2
3. INSTALLATIONWORK
3.1.Selectinganinstallationlocation ........................................................................2
3.2A.Installationdimensions(Ceilingconcealedtype) .............................................3
3.2B.
Installationdimensions(Wallmountedtype/Floorstandingconcealedtype) ...3
3.3A.Installationtheunit(Ceilingconcealedtype) ....................................................3
3.3B.Installtheunit(Wallmountedtype/Floorstandingconcealedtype) ................5
4.
PIPEINSTALLATION
4.1.Selectingthepipematerial .................................................................................6
4.2.Piperequirement ................................................................................................7
4.3.Flareconnection(Pipeconnection) ....................................................................7
4.4.Installingheatinsulation .....................................................................................7
5. INSTALLINGDRAINPIPES
5.1A.Installingdrainpipes(Ceilingconcealedtype) .................................................8
5.1B.Installingdrainpipes(Wallmountedtype/Floorstandingconcealedtype) .............8
5.2. Install the drain pipe ...........................................................................................8
6. ELECTRICALWIRING
6.1.Wiringsystemdiagram .....................................................................................11
6.2.Connectioncablepreparation ........................................................................... 11
6.3.Connectionofwiring .........................................................................................11
7. REMOTECONTROLLERSETTING
7.1.Installingtheremotecontroller .........................................................................12
7.2.Settingthedipswitches ....................................................................................12
7.3.Functionsetting ................................................................................................13
7.4.Jumperwiresetting ..........................................................................................14
7.5.Specialinstallationmethods .............................................................................15
8. TESTRUN ...............................................................................................................15
9. OPTIONALPARTS
9.1.Wiredremotecontroller(Simpleremotecontroller) ..........................................16
9.2.Externalinputandexternaloutput ....................................................................16
9.3.Remotesensor(Optionalparts) .......................................................................16
9.4.IRReceiverUnit(Optionalparts) ......................................................................16
9.5.Autolouvergrille(Optionalparts) .....................................................................17
9.6.Optionalpartscablebinding .............................................................................17
10. CUSTOMERGUIDANCE ........................................................................................17
11. ERRORCODES ......................................................................................................18
9374815173-04_IM.indb 1 9/21/2011 1:45:04 PM
En-2
2.3. Accessories
WARNING
• Forinstallationpurposes,besure tousethepartssupplied bythemanufactureror
other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
waterleakage,electricshock,orre.
• Thefollowinginstallationpartsarefurnished.Usethemasrequired.
• KeeptheInstallationManualinasafeplaceanddonotdiscardanyotheraccessories
until the installation work has been completed.
Do not discard any accessories needed for installation until the installation work has
been completed.
Name and Shape Q’ty Application
OperatingManual
1
InstallationManual
1
(Thisbook)
Installation
template
1
For positioning the indoor
unit
Washer
8
For installing indoor unit
Coupler
heat insulation
(Large)
1
For indoor side pipe joint
(Largepipe)
Coupler
heat insulation
(Small)
1
For indoor side pipe joint
(Smallpipe)
Binder
Medium
3
For power supply and
transmission and remote
controller cable binding.
Large
4
For fixing the coupler heat
insulation.
Filter(Small)
2
(7000,9000,12000,14000BTU/h)
Filter(Big)
2
(18000BTU/h)
Drain hose
1
For installing drain pipe
VP25(O.D.32,I.D.25)
Name and Shape Q’ty Application
Hoseband
1
For installing drain hose
Drain hose insulation B
1
Insulates the drain hose
Wired Remote
Controller
1
RemoteController
Cable
1
For connecting the
remote controller
Tapping screw
(M4×16mm)
2
For installing the remote
controller
2.4. Optional parts
Parts name Model No. Application
Wired remote controller UTY-RNN*M For air conditioner operation
SimpleRemoteController UTY-RSN*M For air conditioner operation
IRReceiverUnit UTY-LRH*M For the wireless remote controller
Remote sensor unit UTY-XSZX Room temperature sensor
External control set UTD-ECS5A Forcontrolinput/outputport
Auto louver grille UTD-G*S*-W Air outlet grille with auto louver
3. INSTALLATION WORK
3.1. Selecting an installation location
Especially, the installation place is very important for the split type air conditioner
becauseitisverydifculttomovefromplacetoplaceaftertherstinstallation.
WARNING
• Selectinstallationlocationsthatcanproperlysupporttheweightoftheindoor.Install
the units securely so that they do not topple or fall.
CAUTION
• Donotinstalltheunitinthefollowingareas:
• Areawithhighsaltcontent,suchasattheseaside.
It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Arealledwithmineraloilorcontainingalargeamountofsplashedoilorsteam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
• Areathatcancausecombustiblegastoleak,containssuspendedcarbonbersor
ammabledust,orvolatileinammablessuchaspaintthinnerorgasoline.
 Ifgasleaksandsettlesaroundtheunit,itcancauseare.
• Areawhereanimalsmayurinateontheunitorammoniamaybegenerated.
• Do not use the unit for special purposes, such as storing food, raising animals,
growing plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
• Donotinstallwherethereisthedangerofcombustiblegasleakage.
• Donotinstalltheunitnearasourceofheat,steam,orammablegas.
• Installtheunitwheredrainagedoesnotcauseanytrouble.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and
remotecontroller cableat least 1m awayfrom atelevisionor radioreceivers.The
purpose of this is to prevent TV reception interference or radio noise.
(Evenifthey areinstalledmore than1mapart,you couldstillreceive noiseunder
somesignalconditions.)
9374815173-04_IM.indb 2 9/21/2011 1:45:06 PM
En-3
CAUTION
• Ifchildrenunder10yearsoldmayapproachtheunit,takepreventivemeasuresso
that they cannot reach the unit.
Decide the mounting position with the customer as follows:
(1) Installtheindoorunitinalocationhavingsufcientstrengthtosupporttheweightof
the indoor unit.
(2) Theinletandoutletportsshouldnotbeobstructed;theairshouldbeabletoblowall
over the room.
(3) Leavethespacerequiredtoservicetheairconditioner.
(4) Locatewheretheaircanbedistributedevenlythroughouttheroombytheunit.
(5) Installtheunitwhereconnectiontotheoutdoorunitiseasy.
(6) Installtheunitwheretheconnectionpipecanbeeasilyinstalled.
(7) Installtheunitwherethedrainpipecanbeeasilyinstalled.
(8) Installtheunitwherenoiseandvibrationisnotamplied.
(9) Takeservicing,etc.,intoconsiderationandleavethespaces.Alsoinstalltheunit
wheretheltercanberemoved.
3.2A. Installation dimensions (Ceiling concealed type)
ProvideaServiceaccessforinspectionpurposes.
Do not place any wiring or illumination in the service space, as they will impede service.
Installation Dimensions
Left
side
Stronganddurableceiling
Indoor unit
Right
side
150mm
or more
400mm
or more
Serviceaccess Ceiling
2500mmormore
(Whennoceiling)
Floor
240mmormore
20mmormore
20mmormore
300mmormore
Adjust the wind direction in the room depending on the shape of blow out opening.
Serviceaccess
Unit
Control
box
400mm
or more
100mm
or more
300mm
or more
Servicespace
3.2B.
Installation dimensions (Wall mounted type/Floor
standing concealed type)
Thewallmountedtype/oorstandingconcealedtyperequiresatemperature
correctionsetting.Performthisin“7.3.Functionsetting”.
Strongand
durableoor
10mm
or less
Leftside
Leftside
150mm
or more
150mm
or more
150mm
or more
150mm
or more
150mm
or more
150mm
or more
20mm
or more
20mm
or more
20mm
or more
20mm
or more
400mm
or more
400mm
or more
Inlet air
Inlet air
Strongand
durableoor
Strongand
durableoor
10mm
or less
Right side
(PIPEside)
Right side
(PIPEside)
Grille
Duct
Grille
Strongand
durableoor
3.3A. Installation the unit (Ceiling concealed type)
WARNING
• Install the air conditioner in a location which can withstanda load do at least 5
times the weight of the main unit and which will not amplify sound or vibration. If the
installation location is not strong enough, the indoor unit may fall and cause injuries.
• If the job is done with thepanel frame only,there is a risk that theunit will come
loose.Pleasetakecare.
3.3A.1. UNIT INSTALLATION EXAMPLE (CEILING CONCEALED
TYPE)
Connectthelocallypurchasedduct.
(1)Inletside
• Connecttheducttothelocallypurchasedinletange.
• Connecttheangetothebodywiththelocallypurchasedtappingscrews.
• Windtheinletangeconnectingtotheductwiththealuminumtapeetc.toavoidthe
air discharge.
CAUTION
• Whentheductisconnectedtoinletside,removecontainedlterandsurelyattach
locallypurchasedlteratinletopening.
(2)Outletside
• Connecttheductwithadjustinginsideofoutletange.
• Windtheoutletangeconnectingtotheductwiththealuminumtapeetc.toavoidthe
air discharge.
• Insulatetheducttoavoidthedewcondensation.
CAUTION
• Check that duct work doesnot exceed the rangeof externalstaticpressure of
equipment.
• Makesuretoinsulateductstoavoidthedewcondensation.
• Makesuretoinsulatebetweenductsandwallsifmetalductsareused.
• Pleaseexplainhandlingandwashingmethodsoflocallypurchasedmaterialstothe
customer.
• Topreventpeoplefromtouchingthepartsinsidetheunit,besuretoinstallgrilleson
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
• Whenconnectingtheducttotheoutletportoftheindoorunit,besuretoinsulatethe
outlet port and the installation screws to prevent water from leaking around the port.
AR07/09/12/14/18Model
• Setthestatic pressure outside the unit to 90 Pa or less (the allowable range is
between0and90Pa).
9374815173-04_IM.indb 3 9/21/2011 1:45:07 PM
En-4
Replace the cover as follows.
• Removethescrews,andthenremovecoverandfanguard.
• Installthecoverwiththescrewsasshownintheillustrationbelow.
Model
Screw
M5
7000,9000,12000,14000BTU/h 9
18000BTU/h 11
screw(M5)
Cover
Fan guard
SideInlet-SideOutlet
Insulationmaterial(Fieldsupply)
Aluminum tape
Flange(Fieldsupply)
Air
Duct
(Fieldsupply)
Air
Intake grille
(Fieldsupply)
SideInlet-SideOutlet(Duct)
Insulationmaterial(Fieldsupply)
Aluminum tape
Aluminum tape
Tapping screw for
angeconnection
(M5x10mm/
Fieldsupply)
Flange(Fieldsupply)
Flange(Fieldsupply)
Air
Duct
(Fieldsupply)
Air
Intake grille
(Fieldsupply)
BottomInlet-SideOutlet
Duct(Fieldsupply)
Intakegrille(Fieldsupply)
Air
Air
Outletside
Inlet side
7000,9000,12000,14000BTU/h 18000BTU/h
A 650mm 850mm
B P200×2=400mm P200×3=600mm
CAUTION
• Be sure to install the air inlet grille and the air outlet grille for aircirculation. The
correct temperature cannot be detected.
• Grills mustbexed so that man cannot touch indoor unit fan and exchanger, and
cannot be removed by only hand operation without tool.
• Besuretoinstalltheairlterintheairinlet.
If the air fi lter is not installed, the heat exchanger may be clogged and its
performance may decrease.
3.3A.2. INSTALL THE FILTERS
• Installthelterstotheunit.
Filter(Accessories)
Unit
Filter
3.3A.3.
DRILLING HOLES FOR BOLTS AND INSTALLING THE BOLTS
• Usingtheinstallationtemplate,drillholesforbolts(4holes).
Drilling position
for bolts
Installation template
A
Air
377mm
7000,9000,12000,14000BTU/h 18000BTU/h
A 734mm 934mm
9374815173-04_IM.indb 4 9/21/2011 1:45:12 PM
En-5
3.3B. Install the unit (Wall mounted type/ Floor standing
concealed type)
WARNING
• Install the air conditioner in a location which can withstand a load doat least 5
times the weight of the main unit and which will not amplify sound or vibration. If the
installation location is not strong enough, the indoor unit may fall and cause injuries.
• If the job is done with the panel frame only, there is a risk that the unitwill come
loose.Pleasetakecare.
3.3B.1. UNIT INSTALLATION EXAMPLE
(Wall mounted type/Floor standing concealed type)
Connectthelocallypurchasedduct.
(1)Inletside
• Connecttheducttothelocallypurchasedinletange.
• Connecttheangetothebodywiththelocallypurchasedtappingscrews.
• Windtheinletangeconnectingtotheductwiththealuminumtapeetc.toavoidthe
air leakage.
CAUTION
• Whentheductisconnectedtoinletside,removecontainedlterandsurelyattach
locallypurchasedlteratinletopening.
(2)Outletside
• Connecttheductwithadjustinginsideofoutletange.
• Windtheoutletangeconnectingtotheductwiththealuminumtapeetc.toavoidthe
air discharge.
• Insulatetheducttoavoidthedewcondensation.
CAUTION
• Check that duct work doesnot exceed the rangeof externalstaticpressure of
equipment.
• Makesuretoinsulateductstoavoidthedewcondensation.
• Makesuretoinsulatebetweenductsandwallsifmetalductsareused.
• Pleaseexplainhandlingandwashingmethodsoflocallypurchasedmaterialstothe
customer.
• Topreventpeoplefromtouchingthepartsinsidetheunit,besuretoinstallgrilleson
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
• Whenconnectingtheducttotheoutletportoftheindoorunit,besuretoinsulatethe
outlet port and the installation screws to prevent water from leaking around the port.
• Set the static pressure outside the unit to 90Pa or less (the allowable range is
between0and90Pa).
• Removethescrews,andthenremovecoverandfanguard.
• Installthecoverwiththescrewsasshownintheillustrationbelow.
Model
Screw
M5
7000,9000,12000,14000BTU/h 9
18000BTU/h 11
Cover
Fan guard
screw(M5)
3.3A.4. FIX THE UNIT
(1)Hangtheunit
Hangerbolt
Nut A
(Fieldsupply)
Nut B
(Fieldsupply)
Washer
(Accessories)
Hanger
Hangerbolt
Nut A
(Fieldsupply)
Washer
(Accessories)
Nut B
(Fieldsupply)
Unit
Hanger
20mm
length
Cover
*:It might become difficult to open and shut the Cover /control box cover when the
lengthexceeds20mm.
(2)Leveling
Base horizontal direction leveling on top of the unit.
Ceiling
Level
OK
NOGOOD
10mmorless
Level
Air
OK NOGOOD
10mmorless
CAUTION
• Leaveaspaceof100mmormorebetweentheinletportandtheceiling.
• FastentheunitsecurelywithSpecialnutsAandB.
9374815173-04_IM.indb 5 9/21/2011 1:45:17 PM
En-6
3.3B.2. INSTALL THE FILTER
Installthelters(Accessories)totheunit.
Filter
Unit
Filter
Replace drain cap
CAUTION
• Set“7.4.JumperwiresettingofDrainagefunctionsetting(JM1)”.
• Drain pump cannot be used if it is installed in wallmounted type/floor standing
concealed type.
3.3B.3. INSTALLING THE UNIT
(1)Fixingmethodoftheunit
• Topreventoverturning,xtheunittotheoororthewall.
• Toavoidthevibrationoftheunit,insertthespacerbetweentheunitandtheoororthe
wall,andxit.
(2)Leveling
Base horizontal direction leveling on top of the unit.
Level
10mmorless
NOGOOD
OK
Level
NOGOODOK
10mmorless
CAUTION
FastentheunitsecurelywithSpecialnutsAandB.
4.
PIPE INSTALLATION
CAUTION
• Be careful that foreign matter (oil, water, etc.) does not enter the piping with
refrigerantR410Amodels.Also,whenstoringthepiping,securelysealtheopenings
by pinching, taping, etc.
• While brazing the pipes, be sure to purge with dry nitrogen gas.
4.1. Selecting the pipe material
CAUTION
• Do not use existing pipes.
• Use pipes that have clean external and internal sides without any contamination
which may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or
water.
• It is necessary to use seamless copper pipes.
Material:Phosphordeoxidizedseamlesscopperpipes
Itisdesirablethattheamountofresidualoilislessthan40mg/10m.
• Do not use copper pipes that have a collapsed, deformed, or discolored portion
(especiallyontheinteriorsurface).Otherwise,theexpansionvalveorcapillarytube
may become blocked with contaminants.
• Improperpipeselectionwilldegradeperformance.AsanairconditionerusingR410A
incurs pressure higher than when using conventional refrigerant, it is necessary to
choose adequate materials.
•
ThicknessesofcopperpipesusedwithR410Aareasshowninthetable.
•
Never use copper pipes thinner than those indicated in the table even if they are
available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in.)] Thickness [mm]
6.35(1/4) 0.80
9.52(3/8) 0.80
12.70(1/2) 0.80
15.88(5/8) 1.00
19.05(3/4) 1.20
9374815173-04_IM.indb 6 9/21/2011 1:45:20 PM
En-7
4.2. Pipe requirement
CAUTION
• Referto the Installation Manualof the outdoor unitfor description of thelength of
connecting pipe or for difference of its elevation.
• Usepipewithwater-resistantheatinsulation.
CAUTION
• Install heat insulation around both the gas and liquid pipes. Failure to do so may
cause water leaks.
Useheatinsulationwithheatresistanceabove120°C.(Reversecyclemodelonly)
In addition, if the humidity level at the installation location of the refrigerant piping is
expectedtoexceed70%,installheatinsulationaroundtherefrigerantpiping.Ifthe
expectedhumiditylevelis70-80%,useheatinsulationthatis15mmorthickerand
iftheexpectedhumidityexceeds80%,useheatinsulationthatis20mmorthicker.
Ifheatinsulationisusedthatisnotasthickasspecied,condensationmayformon
the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045W/(m·K)orless(at20°C).
4.3. Flare connection (Pipe connection)
WARNING
• Tightenthe are nuts with a torque wrench using the specied tighteningmethod.
Otherwise,thearenutscouldbreakafteraprolongedperiod,causingrefrigerantto
leakandgenerateahazardousgasiftherefrigerantcomesintocontactwithaame.
4.3.1. Flaring
• UsespecialpipecutterandaretoolexclusiveforR410A.
(1)
Cuttheconnectionpipetothenecessarylengthwithapipecutter.
(2)
Hold the pipe downward so that cuttings will not enter thepipe and remove any
burrs.
(3)
Insertthearenut(alwaysusethearenutattachedtotheindoorandoutdoorunits
respectively)ontothepipeandperformtheareprocessingwithaaretool.Use
thespecialR410Aaretool,orthe conventionalaretool. Leakageofrefrigerant
mayresultifotherarenutsareused.
(4)
Protectthepipesbypinchingthemorwithtapetopreventdust,dirt,orwaterfrom
entering the pipes.
/
Die
Pipe
A
B
Checkif[L]isareduniformly
and is not cracked or scratched.
Pipe outside diameter
[mm (in.)]
Dimension A [mm]
Dimension B
-
0
0.4
[mm]
Flare tool for R410A,
clutch type
6.35(1/4)
0to0.5
9.1
9.52(3/8) 13.2
12.70(1/2) 16.6
15.88(5/8) 19.7
19.05(3/4) 24.0
Whenusing conventional are tools to are R410Apipes, the dimensionAshould be
approximately0.5mmmorethanindicatedinthetable(foraringwithR410Aaretools)
toachievethespeciedaring.UseathicknessgaugetomeasurethedimensionA.
Width across
ats
Pipe outside
diameter [mm (in.)]
Width across flats
of Flare nut [mm]
6.35(1/4) 17
9.52(3/8) 22
12.70(1/2) 26
15.88(5/8) 29
19.05(3/4) 36
4.3.2. Bending pipes
•
If pipes are shaped by hand, be careful not to collapse them.
•
Donotbendthepipesinananglemorethan90°.
•
When pipes are repeatedly bend or stretched, the material will harden, making it
difculttobendorstretchthemanymore.
•
Do not bend or stretch the pipes more than 3 times.
CAUTION
• To prevent breaking of the pipe, avoid sharp bends.
• If the pipe is bent repeatedly at the same place, it will break.
4.3.3. Pipe connection
CAUTION
• Be sure to install the pipe against the port on the indoor unit correctly. If the centering
isimproper,thearenutcannottightensmoothly.Ifthearenutisforcedtoturn,the
threads will be damaged.
• Do not removethe flare nut fromthe indoor unit pipe until immediatelybefore
connecting the connection pipe.
• Holdthetorquewrenchatitsgrip,keepingitatarightanglewiththepipe,inorderto
tightenthearenutcorrectly.
• Tightentheare nutswith a torquewrench using thespecied tightening method.
Otherwise,thearenutscouldbreakafteraprolongedperiod,causingrefrigerantto
leakandgenerateahazardousgasiftherefrigerantcomesintocontactwithaame.
• Connectthepipingsothatthecontrolboxcovercaneasilyberemovedforservicing
when necessary.
• Inordertopreventwaterfromleakingintothecontrolbox,makesurethatthepiping
is well insulated.
Whenthearenutistightenedproperlybyyourhand,holdthebodysidecouplingwith
aseparatespanner,thentightenwithatorquewrench.(Seethetablebelowfortheare
nuttighteningtorques.)
Tighten with 2 wrenches.
Holdingwrench
Flare nut
Connectionpipe
Torque wrench
Indoor unit pipe
(Bodyside)
Flare nut [mm (in.)] Tightening torque [N·m (kgf·cm)]
6.35(1/4)dia. 16to18(160to180)
9.52(3/8)dia. 32to42(320to420)
12.70(1/2)dia. 49to61(490to610)
15.88(5/8)dia. 63to75(630to750)
19.05(3/4)dia. 90to110(900to1,100)
4.4. Installing heat insulation
Install the heat insulation material after performing a refrigerant leak check (see the
InstallationManualfortheoutdoorunitfordetails).
4.4.1. COUPLER HEAT INSULATION
• Insulatewiththecouplerheatinsulation(Accessories)aroundthegaspipeandliquid
pipe at indoor unit.
• Afterinstallingthecouplerheatinsulation,wrapbothendswithvinyltapesothat
there is no gap.
• Afterafxingthecouplerheatinsulation,secureitwith2binders(large),oneoneach
end of the insulation.
• Makesurethatthebindersoverlaptheheatinsulationpipe.
Couplerheat
insulation
(Accessories)
Coverthisportionwith
heat insulation.
Binder(Large)
(Accessories)
Heatinsulation
CAUTION
• Afterchecking for gas leaks (refer to the Installation Manual of the outdoor unit),
perform this section.
• Installheatinsulationaroundboththelarge(gas)andsmall(liquid)pipes.Failureto
do so may cause water leaks.
9374815173-04_IM.indb 7 9/21/2011 1:45:21 PM
En-8
5. INSTALLING DRAIN PIPES
5.1A. Installing drain pipes (Ceiling concealed type)
Usegeneralhardpolyvinylchloridepipeandconnectitwithadhesive(polyvinylchloride)
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Useadrainpipethatmatchesthesizeofthedrainhose(TableA).
• Donotperformarise,trapandairbleeding.
• Provideadownwardgradient(1/100ormore).
• Providesupportswhenlongpipesareinstalled.
• Useaninsulationmaterialasneeded,topreventthepipesfromfreezing.
• Installthepipesinawaythatallowsfortheremovalofthecontrolbox.
Table A
O.D.
Drain pipe 32mm(VP25)
CEILINGCONCEALEDTYPE(UseDrainPump)
Outletair
ow
Arrange the drain hose
lower than this port.
Drain hose
Trap
OK
NOGOODDrain cap NOGOOD
Rise
Air bleeding
Supporter
NOGOOD
1.5to2m
OK
• Installthedrainpipewithdownwardgradient(1/50to1/100)andsotherearenorises
or traps in the pipe.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm] and
connectitwithadhesive(polyvinylchloride)sothatthereisnoleakage.
• Whenthepipeislong.Installsupports.
• Donotperformairbleeding.
• Alwaysheatinsulatetheindoorsideofthedrainpipe.
VP25
[O.D32mm
ormore]
Horizontalor
upward gradient
Supporter
Gapof1.5-2m
Locallyarrangedpipe
Max.
300mm
700mmorless
RiseAir bleeding
BAD
Trap
Observe the following procedures to construct centralized drain pipe ttings
.
VP30ormore[O.D38mmormore]
Downwardgradient1/100ormore
700mmorless
WARNING
• Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat
exchangeerosionmayoccur)
• Insulatethepartsproperlysothatwaterwillnotdripfromtheconnectionparts.
• Check for proper drainage afterthe construction by using the visible portion of
transparentdrainportandthedrainpipingnaloutletonthebody.
CAUTION
• Donotapplyadhesiveagentonthedrainportofthebody.
 (Usetheattacheddrainhoseandconnectthedrainpiping)
5.1B. Installing drain pipes (Wall mounted type/Floor
standing concealed type)
NOGOOD
OK
NOGOOD
RiseTrap
Drain
cap
CAUTION
• Drain pump cannot be usedif it is installed in wall mounted type/floor standing
concealed type.
• Set“7.4.JumperwiresettingofDrainagefunctionsetting(JM1)”.
• Besuretoconnectthepipesfordrainagewithoutleakage.
• Toavoidcondensationanddripping,alwaysinsulatetheindoordrainpipe.
5.2. Install the drain pipe
(1)BesuretousesuppliedDrainhose
1
andHoseband
2
2
Hoseband
Drain
hole
1
Drain hose
HardPVCside
• When drain pump is used.(Ceilingconcealedtypeonly)
Hoseband
4mmorless
20mm
• When drain pump is not used.(Naturaldrainage)
Jointpipe
(Fieldsupply)
Drainpipe(VP25)
(Fieldsupply)
Applying
area of
adhesive
4mmorless
CAUTION
• Whendrainpumpisnotused,donotconnecttheaccessorydrainhoseandsoftPVC
hose directly
.
9374815173-04_IM.indb 8 9/21/2011 1:45:22 PM
En-9
(2)
Be sure to insert Drain hose
1
to the very end of the Drain pan of the unit with no space
.
Applying
area of
adhesive
Jointpipe
(Fieldsupply)
Drainpipe(VP25)
(Fieldsupply)
4mmorless
2
Hoseband
1
Drain hose
FastentheHoseband
2
at the position where
vertical against ground.
TheHoseband
2
must be positioned at the right
side of the Drain hose
1
asinthegure.
CAUTION
• DonotconnecttotheDrainholewithadhesive.Usingadhesivemaycausedamage
and water leaks.
(3) AfterinstallingtheDrainhose
1
, check if the drainage is smooth.
• When drain pump is not used.(Naturaldrainage)
Downward
gradient
2.5-5.0mm
CAUTION
• TopreventexcessiveforceonDrainhose
1
,avoidbendsortwists.(Tobendortwist
maycausewaterleaks.)
(4) Aftercheckingfordrainage,attachtheDrainhoseinsulationB
3
to insulate, following
theinstructionsasinthegures.
To avoid space with Drain hose
1
andHoseband
2
,pressrmlytheDrainhose
insulation B
3
.
• When drain pump is used.(Ceilingconcealedtypeonly)
3
Drain hose
insulation B
Ensure there is
no space.
• When drain pump is not used.(Naturaldrainage)
3
Drain hose
insulation B
Ensure there is
no space.
• STEP1~STEP3
Butt the insulation against the unit.
STEP1
Unit
Slit
Pressrmly
Pressrmly
STEP2
Slit
Pressrmly
Roll the
insulation
over the joint.
STEP3
Pressrmly
Pressrmly
Slit
• FINISH
Checkthatthereisnogapbetweentheunitandthedrainhoseinsulation.
• When drain pump is used.(Ceilingconcealedtypeonly)
Do not cover the
panel window.
• When drain pump is not used.(Naturaldrainage)
Do not cover the
control box cover.
Note: Check for drainage
Pourabout1literofwaterfromthepositionshowninthediagramorfromtheairow
outlettothecondensatetray.Checkforanyabnormalitiessuchasstrangenoisesand
whether the drain pump functions normally.
CAUTION
•Makesurethedrainwaterisproperlydrained.
9374815173-04_IM.indb 9 9/21/2011 1:45:23 PM
En-10
6. ELECTRICAL WIRING
Cable Cable size (mm
2
) Type Remarks
Connectioncable 1.5 Type60245IEC57 3Cable+Ground,1φ230V
Max.CableLength:Limitvoltagedroptolessthan2%.Increasecablegaugeifvoltagedropis
2%ormore.
WARNING
• Electrical work mustbe performed in accordance with this Manual by a person
certiedunderthenationalorregionalregulations.Besuretouseadedicatedcircuit
for the unit.
 Aninsufcientpowersupplycircuitorimproperlyperformedelectricalworkcancause
seriousaccidentssuchaselectricshockorre.
• Beforestartingwork, checkthat powerisnot beingsupplied totheindoor unitand
outdoor unit.
• Forwiring, use the prescribed typeof cables, connect them securely,making sure
that there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as
overheatingtheterminals,electricshock,orre.
• Securelyinstalltheelectricalboxcoverontheunit.
An improperly installed electrical box cover can cause serious accidents such as
electricshockorrethroughexposuretodustorwater.
• Installsleevesintoanyholesmadeinthewallsforwiring.Otherwise,ashortcircuit
could result.
• Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the
allowablecurrentcancauseelectricshockorre.
• Donotmodifythepowercables,useextensioncables,oruseanybranchesinthe
wiring. Improper connections, insufficient insulation, or exceeding the allowable
currentcancauseelectricshockorre.
Match the terminal blocknumbers and connection cable colors with those of the
outdoor unit or branch box. Erroneous wiring may cause burning of the electric parts.
• Securelyconnecttheconnectioncablestotheterminalboard.Inaddition,securethe
cables with wiring holders. Improper connections, either in the wiring or at the ends
ofthewiring,cancauseamalfunction,electricshock,orre.
Alwaysfastentheoutsidecoveringoftheconnectioncablewiththecableclamp.(If
theinsulatorischafed,electricleakagemayoccur.)
• Installaearthleakagebreaker.Inaddition,installtheearthleakagebreakersothat
theentireACmainpowersupplyiscutoffatthesametime.Otherwise,electricshock
orrecouldresult.
Always connect the earth cable.
Improper grounding work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
• Performwiringworkinaccordancewithstandardssothattheairconditionercanbe
operated safely and positively.
• Connecttheconnectioncablermlytotheterminalboard.Imperfectinstallationmay
causeare.
CAUTION
• Groundtheunit.
Do not connect the earth cable to a gas pipe, water pipe, lightning rod, or a telephone
earth cable.
Improper grounding may cause electric shock.
• Do not connect powersupply cables to the transmissionor remotecontroller
terminals, as this will damage the product.
• Neverbundlethepowersupplycableandtransmissioncable,remotecontrollercable
together.
 Separatethesecableby50mmormore.
Bundling these cables together will cause miss operation or breakdown.
• WhenhandlingPCB,staticelectricitychargedinthebodymaycausemalfunctionof
thePCB.Followthecautionsbelow:
• Establishagroundfortheindoorandoutdoorunitsandperipheraldevices.
• Cutpower(breaker)off.
• Touch metal part of the indoor and outdoor units for more than 10 seconds to
discharge static electricity charged in the body.
• DonottouchterminalsofpartsandpatternsimplementedonPCB.
(1) Useringterminalswithinsulatingsleevesasshowninthegurebelowtoconnectto
the terminal block.
(2) Securelyclamptheringterminalstothecablesusinganappropriatetoolsothatthe
cables do not come loose.
(3) Usethespeciedcables,connectthemsecurely,andfastenthemsothatthereisno
stress placed on the terminals.
(4) Useanappropriatescrewdrivertotightentheterminalscrews.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Donottightentheterminalscrewstoomuch,otherwise,thescrewsmaybreak.
(6) Seethetablefortheterminalscrewtighteningtorques.
(7) Pleasedonotx2powersupplycableswith1screw.
Strip10mm
Sleeve
Screwwithspe-
cial washer
Screwwith
special washer
Ring terminal
Cable
Cable
Terminal block
Ring terminal
Ring
terminal
WARNING
• Useringterminalsandtightentheterminalscrewstothespeciedtorques,otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside
the unit.
Tightening torque
M4screw
1.2to1.8N·m
(12to18kgf·cm)
9374815173-04_IM.indb 10 9/21/2011 1:45:23 PM
En-11
6.1. Wiring system diagram
ConnectioncabletooutdoorunitorBRANCHBOX
INDOORUNIT
OUTDOORUNITor
BRANCHBOX
TERMINAL
Type60245IEC57
Cablesize1.5mm
2
(Inter-unit)
Powerlines
Groundingline
Powerline
Controlline
Pleaseconnectitto
thespeciedterminal.
Wired remote controller cable
*Groundtheremotecontroller
(Pleaseconnectitwhennecessary.)
Red
White
Black
Indoor
unit side
CAUTION
Tighten the indoor unit connection cable and power supply indoor and outdoor unit,
branch box terminal board connections rmly with the terminal board screws.Faulty
connectionmaycauseare.
If the indoor unit connection cable and power supply are wired incorrectly, the air
conditioner may be damaged.
Connect the indoor unit connection cable by matching the numbers of the outdoor,
branch box and indoor units terminal board numbers as shown in terminal label.
Earth both the indoor and outdoor, branch box units by attaching a earth cable.
Unitshallbegroundedincompliancewiththeapplicablelocalandnationalcables.
CAUTION
Besuretorefertotheabovediagramfordocorrecteldwiring.Wrongwiringcauses
malfunction of the unit.
Checklocalelectricalrulesandalsoanyspecicwiringinstructionsorlimitation.
6.2. Connection cable preparation
Keep the earth wire longer than the other wires.
Powersupplycable
or connection cable
20mm
30mmormore
Earth wire
•Usea4-corewirecable.
6.3. Connection of wiring
(1) Removethecontrolboxcoverfromthecontrolbox.
Screw
Controlboxcover
Removethe4screws
and remove the control
box cover from the
control box.
(2) Cableconnection
• Connect the connection cable to the terminal board.
• Connecttheremotecontrollercabletotheterminalboard.
• Fixtheremotecontrollercabletothecontrolboxcoverwithanylonclamp.
Remote controller cable
1:Red
2:White
3:Black
Earth
Binder(Medium)
(Accessories)
Powersupplycable
Binder(Medium)
(Accessories)
Remote controller cable
Powersupplycable
9374815173-04_IM.indb 11 9/21/2011 1:45:24 PM
En-12
.
7. REMOTE CONTROLLER SETTING
CAUTION
When detecting the room temperature using the remote con-
troller, please set up the remote controller according to the
following conditions. If the remote controller is not located prop-
erly, the correct room temperature will not be detected, and
thusabnormalconditions like“not cooled”or“not heated”will
occur even if the air-conditioner is running normally.
• Locatewhereanaveragetemperaturefortheroombeing
air conditioned will be sensed.
• Donotlocatedirectlyexposedtotheoutletairfromthe
air-conditioner.
• Locateoutofdirectsunlight.
• Locateawayfromtheinuenceofotherheatsources.
DonottouchtheremotecontrollerPCboardandPCboardpartsdirectlywithyourhands
.
Do not wire the remote controller cable together with or parallel to the connection ca-
bles,andpowersupplycableofthe INDOORUNITandOUTDOORUNIT,BRANCH
BOX.Itmaycauseerroneousoperation.
When installing the bus wire near a source of electromagnetic waves, use shielded wire
.
DonotsettheDIPswitches,eitherontheairconditionerortheremotecontroller,inany
way other than indicated in this manual that is supplied with the air conditioner. Doing
so may result in improper operation.
7.1. Installing the remote controller
Opentheoperationpanelonthefrontoftheremotecontroller,removethe2screwsindi-
catedinthefollowinggure,andthenremovethefrontcaseoftheremotecontroller.
When installing the remote controller, remove the connector from the front case. The
wires may break if the connector is not removed and the front case hangs down.
When installing the front case, connect the connector to the front case.
Screws
SET BACK
Front case
(backside)
Rear case
Connector
When remote controller cable is concealed
(1) Concealtheremotecontrollercable.
(2) Passtheremotecontrollercablethroughtheholeintherearcaseandconnectthe
remotecontrollercabletotheremotecontrollerterminalboardspeciedingure.
(3) Clamptheremotecontrollercablesheathwiththebinderasshowningure.
(4) Cutofftheexcessbinder.
(5) Installtherearcasetothewall,box,etc.,with2screwsgure.
Binder
(Small)
1.Red
2. White
3. Black
CAUTION
When connecting the remote controller
wires, do not overtighten the screws.
Hole
[Example]
Remote
controller cable
Box
Screws
Connector
Rear case
Groundtheremotecontrollerifithasagroundwire.
Wrap the connector and remote
controller wires with vinyl tape
or some other type of insulation
asshowninthegure.
Remote controller
Temperature
sensor
30
120
17
120
45.3
33.5
Hole
15.3
23
8
4.5
4.5
4.5 12.5
Hole×3
Hole×2
83.5
63.5
6
Unit:mm
CAUTION
Install the remote controller wires so as not to be direct touched with your hand.
Donot touchthe remote controllerPC boardand PC boardparts directly withyour
hands.
7.2. Setting the dip switches
SettheremotecontrollerDIPswitches.
[Example]
ON
ON
OFF
1
2
3
4
5
6
DIPswitch1
Frontcase(backside)
NO.
SW state
Detail
OFF ON
DIP-
switch 1
1
Cannotbeused.
(Donotchange)
2
Dual remote controller setting
*Referto2.DUALREMOTECONTROL-
LERSin7.5.SpecialInstallationMethods.
3
Cannotbeused.
(Donotchange)
4
Cannotbeused.
(Donotchange)
5
Cannotbeused.
(Donotchange)
6
Invalidity Validity
Memorybackupsetting
*SettoON tousebatteries forthememory
backup. If batteries are not used, all of the
settings stored in memory will be deleted if
there is a power failure.
(
Factorysetting)
9374815173-04_IM.indb 12 9/21/2011 1:45:25 PM
En-13
7.3. Function setting
This procedure changes the function settings used to control the indoor unit according to
the installation conditions. Incorrect settings can cause the indoor unit to malfunction. This
procedure should be performed by authorized installation or service personnel only.
Performthe“FUNCTIONSETTING”accordingtotheinstallationconditionsusingtheremote
controller.(Refertotheindoorunitinstallationmanualfordetailsonthefunctionnumbers
andsettingvalues.)
(1) PresstheSETTEMP.buttons(
)( )andFANbuttonsimultaneouslyformorethan
5 seconds to enter the function setting mode.
SU
MO
TU
WE
TH FR
SA
(2) PresstheSETBACKbuttontoselecttheindoorunitnumber.
SU
MO
TU
WE
TH FR
SA
UnitnumberofINDOORUNIT
SETBACK
(3) PresstheSETTIME( )buttonstoselectthefunctionnumber.
Function number
SU
MO
TU
WE
TH FR
SA
(4) PresstheSETTEMP.buttons( )( )toselectthesettingvalue.
Thedisplayashesasshowntotherightduringsettingvalueselection.
Settingvalue
SU
MO
TU
WE
TH FR
SA
(5) PresstheTIMERSETbuttontoconrmthesetting.
PresstheTIMERSETbuttonforafewsecondsuntilthesettingvaluestopsashing.
Ifthesettingvaluedisplaychangesorif“--”isdisplayedwhentheashingstops,the
setting value has not been set correctly.
(Aninvalidsettingvaluemayhavebeenselectedfortheindoorunit.)
(6) Repeatsteps2to5toperformadditionalsettings.
PresstheSETTEMP.buttons(
)( )andFANbuttonsimultaneouslyagainfor
more than 5 seconds to cancel the function setting mode. In addition, the func-
tionsettingmodewillbeautomaticallycanceledafter1minuteifnooperationis
performed.
(7) AftercompletingtheFUNCTIONSETTING,besuretoturnoffthepowerandturniton
again.
Function Details
(1) Filter Sign
Theindoorunithasasigntoinformtheuserthatitistimetocleanthelter.Selectthe
timesettingfortheltersigndisplayintervalinthetablebelowaccordingtotheamount
ofdustordebrisintheroom.Ifyoudonotwishtheltersigntobedisplayed,selectthe
settingvaluefor“Noindication”.
(♦...Factorysetting)
Setting description
Function
number
Setting value
Standard(400hours)
11
00
Longinterval(1000hours) 01
Shortinterval(200hours) 02
♦
No indication 03
(2) Static pressure
Selectappropriatestaticpressureaccordingtotheinstallationconditions.
(♦...Factorysetting
)
Setting description
Function
number
Setting value
0Pa
26
00
10Pa 01
20Pa 02
30Pa 03
40Pa 04
50Pa 05
60Pa 06
70Pa 07
80Pa 08
90Pa 09
♦25Pa[Standard] 31
Rangeofstaticpressureisdifferentfrom1modeltoother.
Range of static pressure 0to90Pa
(3) Cooling room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be selected as shown in the table below.
(♦...Factorysetting)
Setting description
Function
number
Setting value
♦
Standard
30
00
Slightlylowercontrol 01
Lowercontrol 02
Warmer control 03
Whenusingoorconsoleinstallation,changethesettingvalueto“01”.
(4) Heating room temperature correction
Depending on the installed environment, the room temperature sensor
may require a
correction.
The settings may be changed as shown in the table below.
(♦...Factorysetting)
Setting description
Function
number
Setting value
♦
Standard
31
00
Lowercontrol 01
Slightlywarmercontrol 02
Warmer control 03
Whenusingoorconsoleinstallation,changethesettingvalueto“01”.
(5) Auto restart
Enable or disable automatic system restart after a power outage.
(♦...Factorysetting)
Setting description
Function
number
Setting value
♦
Yes
40
00
No 01
9374815173-04_IM.indb 13 9/21/2011 1:45:25 PM
En-14
*Autorestartisanemergencyfunctionsuchasforpowerfailureetc.Donotstartandstop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
(6) Indoor room temperature sensor switching function
(OnlyforWiredremotecontroller)
The following settings are needed when using the Wired remote controller temperature
sensor.
(♦...Factorysetting)
Setting description
Function
number
Setting value
♦
No
42
00
Yes 01
*Ifsettingvalueis“00”:
Room temperature is controlled by the indoor unit temperature sensor.
*Ifsettingvalueis“01”:
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
(7) Wireless remote controller signal code
ChangetheindoorunitSignalCode,dependingonthewirelessremotecontrollers.
(♦...Factorysetting)
Setting description
Function
number
Setting value
♦
A
44
00
B 01
C 02
D 03
(8) External input control
“Operation/Stop”modeor“Forcedstop”modecanbeselected.
(♦...Factorysetting)
Setting description
Function
number
Setting value
♦
Operation/Stopmode
46
00
(Settingforbidden) 01
Forced stop mode 02
Setting record
Record any changes to the settings in the following table.
Setting Setting Value
(1)Filtersign
(2)Staticpressure
(3)Coolingroomtemperaturecorrection
(4)Heatingroomtemperaturecorrection
(5)Autorestart
(6)Indoorroomtemperaturesensorswitchingfunc-
tion
(7)Wirelessremotecontrollersignalcode
(8)Externalinputcontrol
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
SETTING THE ROOM TEMPERATURE DETECTION
LOCATION
The detection location of the room temperature can be selected from the following 2 examples.
Choosethedetectionlocationthatisbestfortheinstallationlocation.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor
.
(1) WhentheTHERMOSENSORbuttonispressed,thelockdisplayashesbecausethe
function is locked at the factory.
Indoor unit
B. Indoor unit/remote controller setting (room tempera-
ture sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect
the room temperature.
(1) EnabletheroomtemperaturesensorselectioninFUNCTIONSETTING,whichwillbe
previous page.
(2) PresstheTHERMOSENSORbuttonfor5secondsormoretoselectthetemperature
sensor of the indoor unit or the remote controller.
Indoor unit
NOTES
IfthefunctiontochangethetemperaturesensorisusedasshowninexamplesA(other
thanexampleB),besuretolockthedetectionlocation.Ifthefunctionislocked,thelock
display
willashwhentheTHERMOSENSORbuttonispressed.
7.4. Jumper wire setting
(1) Drainage function setting (JM1)
If contained drainpumpisnotused,setthedrainagefunctionto“Invalid”inthedrainage
function switching.
Ifcontaineddrainpumpisnotuse:
Whenusedunder“WALLMOUNTEDTYPE/FLOORSTANDINGCONCEALEDTYPE”.
Whenusedinnaturaldrainageunder“CEILINGCONCEALEDTYPE”.
(♦...Factorysetting)
JM1 Drainage function
♦
Connect Valid
Disconnect Invalid
(2) Auto louver grille setting (JM2) (Optional parts)
(♦...Factorysetting)
JM2 Auto louver grille setting
♦
Connect Invalid
Disconnect Valid
(3) Fan delay setting (JM3)
It is a function to delay the stop of cooling fan when the air conditioner is stopped.
(♦...Factorysetting)
JM3 Fan delay
♦
Connect Invalid
Disconnect Valid
• Switching position
JM3
JM2
JM1
Jumperwires
9374815173-04_IM.indb 14 9/21/2011 1:45:26 PM
En-15
7.5. Special installation methods
CAUTION
• WhensettingDIPswitches,donottouchanyotherpartsonthecircuitboarddirectly
with your bare hands.
• Besuretoturnoffthemainpower.
7.5.1. Group control system
CAUTION
• Groupcontrolcannotbeusedwhenusingitbythemultitype.
A number of indoor units can be operated at the same time using a single remote control-
ler.
(1) Wiringmethod(indoorunittoremotecontroller)


  
Indoor
unit 1
Bus wire
Remote
controller cable
Remote controller
When ground wire is necessary
Indoor
unit 2
Indoor
unit 3
Indoor
unit 4
(2) DIPswitchsetting(Indoorunit)
SettheunitnumberofeachindoorunitusingtheDIPswitchesontheindoorunit
circuitboard.(Seethefollowingtableandgure.)
TheDIPswitchesarenormallysettomaketheunitnumber00.
Indoor unit
Unit number
DIP SWITCH No.
1 2 3 4
1
00 OFF OFF OFF OFF
2
01 ON OFF OFF OFF
3
02 OFF ON OFF OFF
4
03 ON ON OFF OFF
5
04 OFF OFF ON OFF
6
05 ON OFF ON OFF
7
06 OFF ON ON OFF
8
07 ON ON ON OFF
9
08 OFF OFF OFF ON
0
09 ON OFF OFF ON
A
10 OFF ON OFF ON
B
11 ON ON OFF ON
C
12 OFF OFF ON ON
D
13 ON OFF ON ON
E
14 OFF ON ON ON
F
15 ON ON ON ON
7.5.2. Dual remote controllers
• 2separateremotecontrollerscanbeusedtooperatetheindoorunits.
•
The timer and self-diagnosis functions cannot be used on the slave units.
(1) Wiringmethod(indoorunittoremotecontroller)
Remote controller cable
Indoor unit
Remote controller
SlaveunitMasterunit
(2) RemotecontrollerDIPswitch1setting
SettheremotecontrollerDIPswitch1No.2accordingtothefollowingtable.
Number of remote
controllers
Master unit Slave unit
DIP SW 1 No. 2 DIP SW 1 No. 2
1(Normal) OFF
2(Dual) OFF ON
8. TEST RUN
CAUTION
• Alwaysturnonthepower12hourspriortothestartoftheoperationinordertoensure
compressor protection.
CHECK ITEMS
(1) Isoperationofeachbuttonontheremotecontrollernormal?
(2) Doeseachlamplightnormally?
(3) Donotairowdirectionlouversoperatenormally?
(4) Isthedrainnormal?
(5)
Isthereanyabnormalnoiseandvibrationduringoperation?
• Donotoperatetheairconditionerintestrunforalongtime.
[OPERATION METHOD]
• Fortheoperationmethod,refertotheoperatingmanual.
(1) Stoptheairconditioneroperation.
(2)
Pressthemastercontrolbuttonandthefancontrolbuttonsimultaneouslyfor2seconds
or more to start the test run.
Test run display
(3) Pressthestart/stopbuttontostopthetestrun.
If“C0”appearsintheunitnumberdisplay,thereisaremotecontrollererror.Refertothe
installation manual included with the remote controller.
Unit number Error code Content
Incompatible indoor unit is connected
Indoor unit
remote controller communication
error
[Using the wireless remote controller for test run] (Option)
• Fortheoperationmethod,refertotheoperatingmanual.
•
The outdoor unit may not operate depending on the room temperature. In this case,
press the test run button on the wireless remote controller while the air conditioner is
running.(Pointthetransmittersectionofthewirelessremotecontrollertowardtheair
conditionerandpressthetestrunbuttonwiththetipofaball-pointpen,etc.)
Transmitter section
Test run button
•
Toendtestoperation,pressthewirelessremotecontrollerSTART/STOPbutton.
(Whentheairconditionerisrunbypressingthetestrunbutton,theOPERATIONindicator
lampandTIMERindicatorlampwillsimultaneouslyashslowly.)
9374815173-04_IM.indb 15 9/21/2011 1:45:27 PM
En-16
9. OPTIONAL PARTS
]
WARNING
•
Regulation of cable differs from each locality, refer in accordance with local rules.
This air conditioner can be connected with the following optional kits. Refer to each
installation manual for the method of installing optional parts.
• Wiredremotecontroller
• Simpleremotecontroller
• Externalconnectkit
• Remotesensorunit
• IRReceiverunit
• Autolouvergrille
9.1. Wired remote controller (Simple remote controller)
Pleasereferto[6.ELECTRICALWIRING]and[7.REMOTECONTROLLERSETTING].
9.2. External input and external output
Connection methods
Wiremodication:
Useatooltocut offtheterminal onthe endof the
wire, and then remove the insulation from the cut
end of the wire.
Connectthewirewithconnectingwirewithsolder.
Important:
Be sure to insulate the connection between the
wires.
• Connectionterminals
Outputterminal(CN103)
InputNoVoltageterminal(CN102)
• Wiringarrangement
Binder(Medium/Accessories)
Bind with this cable.
]
1
9.3. Remote sensor (Optional parts)
Connection method
• Connectionterminals
Remote sensor
terminal(CN8)
• Wiringarrangement
Binder(Medium/Accessories)
Bind with this cable.
• Removetheexistingconnectorandreplaceitwiththeremotesensorconnector(ensure
thatthecorrectconnectorisused).
• Theoriginalconnectorshouldbeinsulatedtoensurethatitdoesnotcomeintocontact
with other electrical circuitry.
Settingforroomtemperaturecorrection
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
• SetFunctionNumber“30”(Coolingroomtemperaturecorrection)to“01”
• SetFunctionNumber“31”(Heatingroomtemperaturecorrection)to“01”
1
9.4. IR Receiver Unit (Optional parts)
Connection method
• Connectionterminals
Receiver unit
terminal(CN13)
Optionalparts
Externalinput/
output wire
Insulated
connection
Cable
(Fieldsupply)
9374815173-04_IM.indb 16 9/21/2011 1:45:28 PM
En-17
• Wiringarrangement
Binder(Medium/Accessories)
Bind with this cable.
• Use7pinsforreceiverunitcable.
•
Atrst,connectthereceiverunitcabletotheReceiverunitterminal(CN13).
]
1
9.5. Auto louver grille (Optional parts)
Connection method
• Connectionterminalandjumperwires
Auto louver grille
terminal(CN11)
JM3
JM2
JM1
Jumperwires
• CutJumperwireJM2
• Wiringarrangement
Binder(Medium/Accessories)
Bushing(Accessoryofoptionalparts)
Bind with this cable.
Auto louver grille cable
Bushing(Accessory
ofoptionalparts)
Binder(Medium/Accessories)
Openingthis
knockout hole
]
1
9.6. Optional parts cable binding
Auto louver
grille cable
Remote controller
cable
Otheroptional
parts cables
Powersupply
cable
Avoid touching the
ceiling with the wiring.
*Useanaccessoryofindoorunitoroptionalpartsforbinder.
**Useanaccessoryofoptionalpartsforbushing.
Ceiling
Avoid covering the air
inlet with the wirings.
Binders*
Air inletBinder*
Knockout hole
Bushing**
• Donotbindthepowersupplycableandothercablestogether.
CAUTION
• To protect the cable insulation after opening a knockout hole, remove any burrs from
the edge of the hole.
10. CUSTOMER GUIDANCE
Explainthefollowingtothecustomerinaccordancewiththeoperatingmanual:
(1)Startingandstoppingmethod,operationswitching,temperatureadjustment,timer,air
owswitching,andotherremotecontrolleroperations.
(
2)Airlterremovalandcleaning,andhowtousetheairlouvers.
(3)Givetheoperatingandinstallationmanualstothecustomer.
(4)Ifthesignalcodeischanged,explaintothecustomerhowitchanged(thesystem
returnstosignalcodeAwhenthebatteriesintheremotecontrollerarereplaced).
*(4)isapplicabletousingwirelessremotecontroller.
9374815173-04_IM.indb 17 9/21/2011 1:45:28 PM
En-18
11. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote
controller display. If you use a wireless remote controller, the lamps on the IR receiver
unitwilloutputerrorcodesbywayofblinkingpatterns.Seethelampblinkingpatterns
and error codes in the table below. An error display is displayed only during operation.
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp
(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(1)
(1)
Serialcommunicationerror
(1)
(2)
Wired remote controller
communication error
(1)
(5)
Checkrununnished
(2)
(1)
UnitnumberorRefrigerantcircuit
address setting error
[SimultaneousMulti]
(2)
(2)
Indoor unit capacity error
(2)
(3)
Combinationerror
(2)
(4)
Connectionunitnumber •
error(indoorslaveunit)
[SimultaneousMulti]
Connectionunitnumbererror•
(indoorunitorbranchunit)
[FlexibleMulti]
(2)
(7)
Masterunit,slaveunitset-up
error[SimultaneousMulti]
(3)
(2)
IndoorunitPCBmodel
information error
(3)
(5)
Manualautoswitcherror
(4)
(1)
Room temp. sensor error
(4)
(2)
IndoorunitHeatEx.Middletemp.
sensor error
(5)
(1)
Indoor unit fan motor error
(5)
(3)
Drain pump error
(5)
(7)
Damper error
(5)
(15)
Indoor unit error
(6)
(2)
OutdoorunitmainPCBmodel
information error or
communication error
(6)
(3)
Inverter error
(6)
(4)
Activeltererror,PFCcircuit
error
(6)
(5)
TripterminalLerror
(6)
(10)
DisplayPCBmicrocomputers
communication error
(7)
(1)
Discharge temp. sensor error
(7)
(2)
Compressortemp.sensorerror
(7)
(3)
OutdoorunitHeatEx.liquid
temp. sensor error
(7)
(4)
Outdoortemp.sensorerror
(7)
(5)
SuctionGastemp.sensorerror
(7)
(6)
2-way valve temp. sensor error•
3-way valve temp. sensor error•
(7)
(7)
Heatsinktemp.sensorerror
(8)
(2)
Sub-coolHeatEx.gasinlet•
temp. sensor error
Sub-coolHeatEx.gasoutlet•
temp. sensor error
(8)
(3)
Liquidpipetemp.sensorerror
(8)
(4)
Currentsensorerror
(8)
(6)
Discharge pressure sensor •
error
Suctionpressuresensorerror•
Highpressureswitcherror•
(9)
(4)
Trip detection
(9)
(5)
Compressorrotorposition
detectionerror(permanentstop)
(9)
(7)
Outdoorunitfanmotorerror
(9)
(9)
4-wayvalveerror
(10)
(1)
Discharge temp. error
(10)
(3)
Compressortemp.error
(10)
(4)
Highpressureerror
(10)
(5)
Lowpressureerror
(13)
(2)
Branch boxes error
[FlexibleMulti]
Display mode
:0.5sON/0.5sOFF
:0.1sON/0.1sOFF
():Numberofashing
[Troubleshooting at the remote controller LCD]
This is possible only on the wired remote controller.
[Self-diagnosis]
Ifanerroroccurs,thefollowingdisplaywillbeshown.(“Er”willappearinthesetroom
temperaturedisplay.)
Error code
EX.Self-diagnosis
9374815173-04_IM.indb 18 9/21/2011 1:45:32 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19

Fujitsu RDG12LLTA Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI