3
30 LB. GAUGE
1/4” N.P.T. PIPE
COUPLING
CONNECTION — 3390
1/4-IN. FUEL GAS
HOSE WITH
STANDARD FITTINGS;
LENGTH AS DESIRED
Fig. 3 – TEST GAUGE HOOK-UP
5. The H-14 and H-16 protective devices incorporate
a feature that stops fuel flow when subjected to
flows substantially above the devices rated capac-
ity. When this condition happens the rubber sleeve
is forced against the outer wall of the device pre-
venting fuel flow. If this happens, turn off fuel sup-
ply pressure to the H-14 or H-16, bleed the fuel
gas pressure from the torch by momentarily open-
ing then closing the fuel gas valve at the torch,
then slowly turn on fuel supply pressure. If normal
operation is not restored when the flow is at maxi-
mum capacity or less, do the following.
Make sure fuel gas supply pressure is no higher
than maximum allowable settings and try torch
operation again (H-14 acetylene - 15 psig), (H-16
other fuel gasses - 200 psig). If normal fuel flow
and torch operation are restored no further
action is required. If fuel flow is not restored the
unit must be disassembled, the rubber sleeve re-
turned to its position on the mandrel, and reas-
sembled. The H-14 or H-16 can then be returned
to service (see Sec. V, Maintenance Instructions).
Important: If a flashback occurs, immediately close
the torch oxygen valve and then the torch
fuel gas valve. Wait about one minute -
then resume operation. If a flashback re-
occurs stop operation immediately and re-
place the torch.
IV. PERIODIC INSPECTION
The following inspection should be made regularly in
order to obtain safe and reliable service:
1. Regularly drain the moisture trap.
A. Close the station shutoff valve and lift the re-
lief valve operating lever.
B. Remove the drain cap and let all water run out.
Using Teflon tape or suitable pipe-compound
on the male thread, promptly replace the drain
cap.
2. Every two weeks operate the Relief Valve. Lift
the valve operating lever for an instant to unseat
the valve. This guards against sticking of the valve.
3. Every six months inspect the H-14 or H-16 for
leakage and the condition of the rubber sleeve
as follows:
A. Preparation
a. Test for leaks to the atmosphere as instructed
in II-B.
b. Attach a 30 psig pressure gauge to the outlet
connection. (See Fig. 3.)
B. Testing
a Crack the shutoff valve very slightly to allow
the pressure to build up to 5 psig, then close
the valve tight.
b. Watch the pressure gauge for several minutes.
If the pressure falls, inspect the relief valve as
outlined in F-9373, Instructions and Parts List
for RV-27, 28, and 29 Relief Valves (packed
with H-14 and H-16).
c. Loosen the pipe union on the relief valve vent
piping one or two turns. Then slowly loosen
the pipe union between the shutoff valve and
the H-14 or H-16 to relieve the pressure from
the inlet piping. Uncouple this pipe union and
rotate the H-14 or H-16 and its connected pip-
ing, in its supporting clamp, enough to move
the union 1/8 turn forward. Watch the pres-
sure gauge to make sure the 5 psig has been
maintained. Check the rubber sleeve for
backflow leakage with a film of leak test solu-
tion or soapy water across the union face. If
no leakage is observed, reassemble the pip-
ing operate the relief valve, and remove the
pressure gauge. If there is leakage, the cause
should be corrected as outlined in Section V,
Maintenance Instructions.
V. MAINTENANCE INSTRUCTIONS
A. Before taking any action to repair, adjust, or disas-
semble the H-14 or H-16, or its relief valve, be sure
you have closed the station shutoff valve in the
supply line and relieved all pressure.
B. Make no repairs or replacements other than those
described below. When installing new parts, use
only genuine OXWELD
®
parts shown on the back
page.