Emerson SiteLink-4E can be used to communicate with up to four Liebert unit controllers. The device has built-in surge and transient protection circuitry to protect incoming power and network communications connections. It has a 10/100Base-T Fast Ethernet port, an ARC156 Port for ARCNET156 or EIA-485 communication, and a TPI Port S1 that can be configured for EIA-232/422/485 communication. SiteLink-4E also has four EIA-422/485 ports that can be individually set for different protocols and baud rates.

Emerson SiteLink-4E can be used to communicate with up to four Liebert unit controllers. The device has built-in surge and transient protection circuitry to protect incoming power and network communications connections. It has a 10/100Base-T Fast Ethernet port, an ARC156 Port for ARCNET156 or EIA-485 communication, and a TPI Port S1 that can be configured for EIA-232/422/485 communication. SiteLink-4E also has four EIA-422/485 ports that can be individually set for different protocols and baud rates.

1
SITELINK-E
Product Specification/Installation Sheet
Description
The Liebert SiteLink-E is a product
platform that comes in three models:
SiteLink-12E, -4E and -2E. The models
differ only in the number of Emerson
family ports at the bottom of the module.
SiteLink-E supports Emerson interfaces
as a BACnet router that provides the
communications link between Liebert
units and other protocols and modules.
The SiteLink-E is designed to
communicate with Liebert equipment—
environmental units, UPSs and Power
Distribution Units—and route the
information over a BACnet, Modbus or
LONWorks™ network to a Building
Automation System (BAS) workstation.
Module Dimensions and Layout
SiteLink-12E
10/100 BaseT
Ethernet Port
100 LAN LINK
Xnet +
Xnet -
Gnd
Xnet
Remote
Expansion
Local Access
2 wire 4 wire
Rx -
Net-
Net+
n/c
Tx -
Tx +
Rx +n/c
EIA-232
DCD
Rx
Tx
DTR
Signal Ground
Port S1
EIA-485
EIA-232
485-4w
485-2w
Ext. Batt.
Int. Batt.
External
Battery
Gnd
+3V
On Off
Power
Module
Address
10's 1's
3V Lithium Battery
CR-123A
Archive Valid
Port S1 Receive
Port S1 Transmit
Battery low
ARCNET Receive
ARCNET Transmit
Shield
Net -
Net +
®
BACnet
Over ARCNET156 KBaud
BT485
ARCNET
Rnet
Gnd
Rnet +
Rnet -
+12V
24ac/26dc
Ground
Format
IP Addr
Default
Assigned
Address
Enable
Disable
on S1
On
Off
MSTP
Enable
Disable
on S1
PTP
Enhanced Access
on Rnet
+100
0
Status
Module
Blinking Dot = 'Run'
Error Codes
0 = Download required
1 = Control Program Error
2 = RAM full
3 = Comm setup error
4 = System error
8 = Formatting
Chase = OK
Port 1 Port 2 Port 3 Port 4 Port 5 Port 6 Port 7 Port 8 Port 9 Port 10 Port 11 Port 12
Net+
Net-
Net+
Net-
Net+
Net-
Net+
Net-
Net+
Net-
Net+
Net-
Net+
Net-
Net+
Net-
Net+
Net-
Net+Rx
Net-Rx
Net+
Net-
Net+Rx
Net-Rx
Net+
Net-
Net+Rx
Net-Rx
Net+
Net-
Net+Rx
Net-Rx
24Vac, 24VA, 1A, 50-60 Hz
26Vdc, 10W, 0.4A
SiteLink-12E
EIA-485
EIA-232
Net+, Net-, Net+Rx, Net-Rx
Tx, Rx, Gnd, Gnd
Port 9-12
BT485
Ethernet
port
Port S1
Local
access port
7.5"
(190.5mm)
Diagnostic
LED
indicators
Xnet
remote
expansion
port
Rnet port
BACnet
port
5.5"
(139.7mm)
1"
(25.4mm)
11.3"
(287mm)
0.23"
(5.8mm)
Power connector
1"
(25.4mm)
2
Enclosure Mounting
The enclosure may be mounted on a wall or on the floor. Refer to the following diagrams for
your application.
Enclosure Mounting Diagrams
DETAIL A
12.5"
(317.5mm)
0.4"
(10.2mm)
0.188"
(4.76mm)
R
0.107"
(2.71mm)
R
1"
(25.4mm)
11"
(279.4mm)
0.88"
(22.2mm)
1"
(25.4mm)
0.88"
(22.2mm)
12.5"
(317.5mm)
1"
(25.4mm)
11"
(279.4mm)
0.88"
(22.2mm)
1"
(25.4mm)
0.88"
(22.2mm)
A
3
Enclosure Mounting Diagrams (continued)
3.35"
(85mm)
12"
(304.8mm)
14.25"
(362mm)
5.88"
(149.2mm)
5.88"
(149.2mm)
3.92"
(99.6mm)
2.5"
(63.5mm)
1.5"
(38.1mm)
1.5"
(38.1mm)
1.5"
(38.1mm)
1.5"
(38.1mm)
1.5"
(38.1mm)
1.5"
(38.1mm)
DETAIL B
1.13"
(28.6mm)
0.88"
(22.2mm)
0.6"
(15.1mm)
1.15"
(29.3mm)
5.25"
(133.4mm)
1.25"
(31.8mm)
B
4
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-27218_REV0_01-07
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
Specifications
Wiring Specifications
Ordering Information
Power 24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W, 48VDC
Dimensions
W x D x H: in. (mm)
Module: 11.3 x 0.56 x 7.5 (287 x 14.2 x 190.5)
Enclosure (brushed aluminum): 14.25 x 2.85 x 12 (362 x 72.4 x 304.8)
Communication Ports
Ethernet Port 10/100Base-T Fast Ethernet port.
ARC156 Port
ARCNET156 or EIA-485 communication. In ARCNET156 mode, the port communicates via
BACnet ARC156.
TPI Port S1
EIA-232/422/485 configurable port for interaction with 3rd-party building automation systems
via software-selectable protocols. May also be configured for remote modem access.
EIA-422/485
Ports 1-12 - for
communication with
equipment via
software-selectable
protocols & baud
rates
Each port can be individually set for different protocols & baud rates.
The number of ports varies by model:
SiteLink-2E (SSW-2E) SiteLink-4E (SSW-4E) SiteLink-12E (SSW-12E)
Ports 11-12
These two ports include
an option for EIA-232
connection.
Ports 9-12
These four ports include
an option for EIA-232
connection.
Ports 1-12
Four of these 12 ports (9-12)
include an option for EIA-232
connection.
Environmental
Operating Range
20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing
Note: Control modules should be installed within the building.
Memory 16 MByte non-volatile battery-backed SDRAM and 8 MByte Flash
Protection
Built-in surge and transient protection circuitry - internal solid state polyswitches on incoming
power and network communications connections
Battery 3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation
Fault Detection Hardware watchdog timer
Agency Listings UL, cUL, CE, FCC
Connection Supported Wire Types Maximum Wire Length Rating
Ethernet 10 BaseT CAT 5 328 ft. (100m) N/A
BACnet Port MAGNUM Cable P/N A3-ARC-156-2 3000 ft. (915m) N/A
Port S1 EIA-485
18-22 AWG Stranded & Shielded; 18 AWG (recommended)
Non Plenum - Belden 9461; Plenum - Belden 88761
1000 ft. (300m) N/A
Port S1 EIA-232
18-22 AWG Stranded & Shielded; 18 AWG (recommended)
Non Plenum - Belden 9461; Plenum - Belden 88761
50 ft. (15m) N/A
Quantity Part # Description
SSW-12E SiteLink-12E with enclosure - communicates with up to 12 Liebert unit controllers
SSW-12EWO SiteLink-12E without enclosure - communicates with up to 12 Liebert unit controllers
SSW-4E SiteLink-4E with enclosure - communicates with up to 4 Liebert unit controllers
SSW-4EWO SiteLink-4E without enclosure - communicates with up to 4 Liebert unit controllers
SSW-2E SiteLink-2E with enclosure - communicates with up to 2 Liebert unit controllers
SSW-2EWO SiteLink-2E without enclosure - communicates with up to 2 Liebert unit controllers
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Emerson SiteLink-4E User manual

Category
Networking
Type
User manual
This manual is also suitable for

Emerson SiteLink-4E can be used to communicate with up to four Liebert unit controllers. The device has built-in surge and transient protection circuitry to protect incoming power and network communications connections. It has a 10/100Base-T Fast Ethernet port, an ARC156 Port for ARCNET156 or EIA-485 communication, and a TPI Port S1 that can be configured for EIA-232/422/485 communication. SiteLink-4E also has four EIA-422/485 ports that can be individually set for different protocols and baud rates.