Shinko FCD-13A User manual

Type
User manual
DIGITAL INDICATING CONTROLLER
FCD-13A
INSTRUCTION MANUAL
2
Preface
Thank you for purchasing our Digital indicating controller FCD-13A.
This manual contains instructions for the mounting, functions, operations and notes when
operating the FCD-13A.
To prevent accidents arising from the misuse of this controller, please ensure the operator
receives this manual
.
Abbreviations used in this manual
Symbol Term
PV Process variable
SV Desired value
MV Output manipulated variable
OUT1 Control output 1
OUT2 Control output 2 (option)
AT Auto-tuning
Characters used in this manual:
Indication
Number, /
-1 0 1 2 3 4 5 6 7 8 9
Indication
Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
3
Notes
• This instrument should be used in accordance with the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause a fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or
malfunction may occur.
• Specifications of the FCD-13A and the contents of this instruction manual are subject to change
without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if
there are any doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed through a control panel. If it is not, measures must be
taken to ensure that the operator cannot touch power terminals or other high voltage sections.
Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a
result of using this product, including any indirect damage.
SAFETY PRECAUTIONS (Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on the circumstances, procedures indicated by Caution may cause serious
results, so be sure to follow the directions for usage.
Warning
Warning
To prevent an electric shock or fire, only Shinko or other qualified service personnel may
handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only
be undertaken by Shinko or other qualified service personnel.
SAFETY PRECAUTIONS
To ensure safe and correct use, thoroughly read and understand this manual before using
this instrument.
This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after consulting purpose of use with our agency or main office.
(Never use this instrument for medical purposes with which human lives are involved.)
External protection devices such as protective equipment against excessive temperature rise,
etc. must be installed, as malfunction of this product could result in serious damage to the
system or injury to personnel. Also proper periodic maintenance is required.
This instrument must be used under the conditions and environment described in this manual.
Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring
due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the
manufacture of weapons of mass destruction (i.e. military applications, military equipment,
etc.), please investigate the end users and the final use of this instrument.
In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and
cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause
superficial to medium injury or physical damage or may degrade
or damage the product, if not carried out properly.
2
Preface
Thank you for purchasing our Digital indicating controller FCD-13A.
This manual contains instructions for the mounting, functions, operations and notes when
operating the FCD-13A.
To prevent accidents arising from the misuse of this controller, please ensure the operator
receives this manual
.
Abbreviations used in this manual
Symbol Term
PV Process variable
SV Desired value
MV Output manipulated variable
OUT1 Control output 1
OUT2 Control output 2 (option)
AT Auto-tuning
Characters used in this manual:
Indication
Number, /
-1 0 1 2 3 4 5 6 7 8 9
Indication
Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
3
Notes
• This instrument should be used in accordance with the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause a fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, serious injury or
malfunction may occur.
• Specifications of the FCD-13A and the contents of this instruction manual are subject to change
without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if
there are any doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed through a control panel. If it is not, measures must be
taken to ensure that the operator cannot touch power terminals or other high voltage sections.
Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
• Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a
result of using this product, including any indirect damage.
SAFETY PRECAUTIONS (Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on the circumstances, procedures indicated by
Caution may cause serious
results, so be sure to follow the directions for usage.
Warning
Warning
To prevent an electric shock or fire, only Shinko or other qualified service personnel may
handle the inner assembly.
• To prevent an electric shock, fire or damage to the instrument, parts replacement may only
be undertaken by Shinko or other qualified service personnel.
SAFETY PRECAUTIONS
To ensure safe and correct use, thoroughly read and understand this manual before using
this instrument.
This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after consulting purpose of use with our agency or main office.
(Never use this instrument for medical purposes with which human lives are involved.)
External protection devices such as protective equipment against excessive temperature rise,
etc. must be installed, as malfunction of this product could result in serious damage to the
system or injury to personnel. Also proper periodic maintenance is required.
This instrument must be used under the conditions and environment described in this manual.
Shinko Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring
due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the
manufacture of weapons of mass destruction (i.e. military applications, military equipment,
etc.), please investigate the end users and the final use of this instrument.
In the case of resale, ensure that this instrument is not illegally exported.
Caution
Procedures which may lead to dangerous conditions and
cause death or serious injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause
superficial to medium injury or physical damage or may degrade
or damage the product, if not carried out properly.
4
1
1
.
.
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
This instrument is intended to be used under the following environmental
conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 )
that does not change rapidly, and no icing
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current
is flowing
• No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
• Take note that ambient temperature of this unit must not exceed 50
(122 ) if
mounted through the face of a control panel. Otherwise the life of electronic
components (especially electrolytic capacitors) may be shortened.
Note: Avoid setting this instrument directly on or near flammable material even
though the case of this instrument is made of flame-resistant resin.
2
2
.
.
W
W
i
i
r
r
i
i
n
n
g
g
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
Do not leave wire remnants in the instrument, because they could cause a fire or malfunction.
• Use the solderless terminal with an insulation sleeve in which an M3 screw fits when
wiring the FCD-13A.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with
the terminal screw.
• Tighten the terminal screw within the specified torque. If excessive force is applied to
the screw when tightening, the screw or case may be damaged.
• Do not apply a commercial power source to the sensor connected to the input terminal
nor allow the power source to come into contact with the sensor, as the input circuit
may be burnt out.
• This controller has no built-in power switch, circuit breaker or fuse. It is necessary to
install them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
3
3
.
.
O
O
p
p
e
e
r
r
a
a
t
t
i
i
o
o
n
n
a
a
n
n
d
d
m
m
a
a
i
i
n
n
t
t
e
e
n
n
a
a
n
n
c
c
e
e
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
• It is recommended that AT be performed during the trial run.
• Do not touch live terminals. This may cause electric shock or problems in operation.
• Turn the power supply to the instrument OFF when retightening the terminal and
cleaning. Working or touching the terminal with the power switched ON may result
in severe injury or death due to Electric Shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
As the display section is vulnerable, do not strike or scratch it with a hard object or
press hard on it.
5
--- CONTENTS ---
1. Model
1.1 Model ---------------------------------------------------------------------------------------- 8
1.2 How to read the model label ----------------------------------------------------------- 9
2. Name and functions of sections
2.1 Name of sections ------------------------------------------------------------------------ 10
2.2 Keys ----------------------------------------------------------------------------------------- 11
3. Setup
3.1 Taking the internal assembly out ---------------------------------------------------- 12
3.2 Switch setting (multi-function) -------------------------------------------------------- 12
3.3 Insertion of the internal assembly --------------------------------------------------- 15
4. Mounting to the control panel
4.1 Site selection ----------------------------------------------------------------------------- 16
4.2 External dimensions (Scale: mm) --------------------------------------------------- 16
4.3 Panel cutout (Scale: mm) ------------------------------------------------------------- 16
4.4 Current transformer (CT) dimensions (Scale: mm) ----------------------------- 17
4.5 Mounting ----------------------------------------------------------------------------------- 17
5. Wiring
5.1 Terminal arrangement ------------------------------------------------------------------ 19
5.2 Wiring examples ------------------------------------------------------------------------- 20
6. Settings
6.1 Operation flowchart --------------------------------------------------------------------- 22
6.2 Settings
6.2.1 Main setting mode ------------------------------------------------------------------- 24
SV ------------------------------------------------------------------------------------------ 24
6.2.2 Sub setting mode
Set value memory number ----------------------------------------------------------- 25
AT Perform/Cancel --------------------------------------------------------------------- 25
OUT1 proportional band -------------------------------------------------------------- 25
OUT2 proportional band -------------------------------------------------------------- 25
Integral time ----------------------------------------------------------------------------- 25
Derivative time -------------------------------------------------------------------------- 25
OUT1 proportional cycle ------------------------------------------------------------- 26
OUT2 proportional cycle ------------------------------------------------------------- 26
Manual reset ---------------------------------------------------------------------------- 26
A1 value ---------------------------------------------------------------------------------- 26
A2 value ---------------------------------------------------------------------------------- 26
A3 value ---------------------------------------------------------------------------------- 27
A4 value ---------------------------------------------------------------------------------- 27
Heater burnout alarm value --------------------------------------------------------- 27
Loop break alarm time ---------------------------------------------------------------- 27
Loop break alarm span --------------------------------------------------------------- 27
4
1
1
.
.
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
This instrument is intended to be used under the following environmental
conditions (IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly, and no icing
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current
is flowing
• No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
• Take note that ambient temperature of this unit must not exceed 50 (122 ) if
mounted through the face of a control panel. Otherwise the life of electronic
components (especially electrolytic capacitors) may be shortened.
Note: Avoid setting this instrument directly on or near flammable material even
though the case of this instrument is made of flame-resistant resin.
2
2
.
.
W
W
i
i
r
r
i
i
n
n
g
g
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
Do not leave wire remnants in the instrument, because they could cause a fire or malfunction.
• Use the solderless terminal with an insulation sleeve in which an M3 screw fits when
wiring the FCD-13A.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with
the terminal screw.
• Tighten the terminal screw within the specified torque. If excessive force is applied to
the screw when tightening, the screw or case may be damaged.
• Do not apply a commercial power source to the sensor connected to the input terminal
nor allow the power source to come into contact with the sensor, as the input circuit
may be burnt out.
• This controller has no built-in power switch, circuit breaker or fuse. It is necessary to
install them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
3
3
.
.
O
O
p
p
e
e
r
r
a
a
t
t
i
i
o
o
n
n
a
a
n
n
d
d
m
m
a
a
i
i
n
n
t
t
e
e
n
n
a
a
n
n
c
c
e
e
p
p
r
r
e
e
c
c
a
a
u
u
t
t
i
i
o
o
n
n
s
s
Caution
• It is recommended that AT be performed during the trial run.
• Do not touch live terminals. This may cause electric shock or problems in operation.
• Turn the power supply to the instrument OFF when retightening the terminal and
cleaning. Working or touching the terminal with the power switched ON may result
in severe injury or death due to Electric Shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
As the display section is vulnerable, do not strike or scratch it with a hard object or
press hard on it.
5
--- CONTENTS ---
1. Model
1.1 Model ---------------------------------------------------------------------------------------- 8
1.2 How to read the model label ----------------------------------------------------------- 9
2. Name and functions of sections
2.1 Name of sections ------------------------------------------------------------------------ 10
2.2 Keys ----------------------------------------------------------------------------------------- 11
3. Setup
3.1 Taking the internal assembly out ---------------------------------------------------- 12
3.2 Switch setting (multi-function) -------------------------------------------------------- 12
3.3 Insertion of the internal assembly --------------------------------------------------- 15
4. Mounting to the control panel
4.1 Site selection ----------------------------------------------------------------------------- 16
4.2 External dimensions (Scale: mm) --------------------------------------------------- 16
4.3 Panel cutout (Scale: mm) ------------------------------------------------------------- 16
4.4 Current transformer (CT) dimensions (Scale: mm) ----------------------------- 17
4.5 Mounting ----------------------------------------------------------------------------------- 17
5. Wiring
5.1 Terminal arrangement ------------------------------------------------------------------ 19
5.2 Wiring examples ------------------------------------------------------------------------- 20
6. Settings
6.1 Operation flowchart --------------------------------------------------------------------- 22
6.2 Settings
6.2.1 Main setting mode ------------------------------------------------------------------- 24
SV ------------------------------------------------------------------------------------------ 24
6.2.2 Sub setting mode
Set value memory number ----------------------------------------------------------- 25
AT Perform/Cancel --------------------------------------------------------------------- 25
OUT1 proportional band -------------------------------------------------------------- 25
OUT2 proportional band -------------------------------------------------------------- 25
Integral time ----------------------------------------------------------------------------- 25
Derivative time -------------------------------------------------------------------------- 25
OUT1 proportional cycle ------------------------------------------------------------- 26
OUT2 proportional cycle ------------------------------------------------------------- 26
Manual reset ---------------------------------------------------------------------------- 26
A1 value ---------------------------------------------------------------------------------- 26
A2 value ---------------------------------------------------------------------------------- 26
A3 value ---------------------------------------------------------------------------------- 27
A4 value ---------------------------------------------------------------------------------- 27
Heater burnout alarm value --------------------------------------------------------- 27
Loop break alarm time ---------------------------------------------------------------- 27
Loop break alarm span --------------------------------------------------------------- 27
6
6.2.3 Auxiliary function setting mode 1
Set value lock --------------------------------------------------------------------------- 28
SV high limit ----------------------------------------------------------------------------- 29
SV low limit ------------------------------------------------------------------------------ 29
Sensor correction ---------------------------------------------------------------------- 29
Overlap/Dead band -------------------------------------------------------------------- 29
Remote/Local setting ------------------------------------------------------------------ 30
Instrument number --------------------------------------------------------------------- 30
Communication speed ---------------------------------------------------------------- 30
Communication protocol ------------------------------------------------------------- 30
6.2.4 Auxiliary function setting mode 2
Scaling high limit ----------------------------------------------------------------------- 31
Scaling low limit ------------------------------------------------------------------------ 31
Decimal point place ------------------------------------------------------------------- 31
PV filter time constant ---------------------------------------------------------------- 31
OUT1 high limit ------------------------------------------------------------------------- 31
OUT1 low limit -------------------------------------------------------------------------- 31
OUT1 ON/OFF hysteresis ----------------------------------------------------------- 32
OUT2 action mode --------------------------------------------------------------------- 32
OUT2 high limit ------------------------------------------------------------------------- 32
OUT2 low limit -------------------------------------------------------------------------- 32
OUT2 ON/OFF hysteresis ----------------------------------------------------------- 32
A3 type ----------------------------------------------------------------------------------- 32
A4 type ----------------------------------------------------------------------------------- 33
A1 action Energized/De-energized ------------------------------------------------ 33
A2 action Energized/De-energized ------------------------------------------------ 33
A3 action Energized/De-energized ------------------------------------------------ 33
A4 action Energized/De-energized ------------------------------------------------ 33
A1 hysteresis --------------------------------------------------------------------------- 33
A2 hysteresis --------------------------------------------------------------------------- 33
A3 hysteresis --------------------------------------------------------------------------- 34
A4 hysteresis --------------------------------------------------------------------------- 34
A1 action delay timer ----------------------------------------------------------------- 34
A2 action delay timer ----------------------------------------------------------------- 34
A3 action delay timer ----------------------------------------------------------------- 34
A4 action delay timer ----------------------------------------------------------------- 34
External setting input high limit ----------------------------------------------------- 35
External setting input low limit ------------------------------------------------------ 35
Transmission output ------------------------------------------------------------------- 35
Transmission output high limit ------------------------------------------------------ 35
Transmission output low limit ------------------------------------------------------- 35
Indication when control output OFF ----------------------------------------------- 35
SV rise rate ------------------------------------------------------------------------------ 35
SV fall rate ------------------------------------------------------------------------------- 36
Output status when input abnormal ------------------------------------------------ 36
7
6.2.5 Program mode ----------------------------------------------------------------------- 36
Fixed value control/Program control switching --------------------------------- 37
Step 1 time ------------------------------------------------------------------------------- 37
Step 2 time ------------------------------------------------------------------------------- 37
Step 3 time ------------------------------------------------------------------------------- 37
Step 4 time ------------------------------------------------------------------------------- 37
Step 5 time ------------------------------------------------------------------------------- 37
Step 6 time ------------------------------------------------------------------------------- 38
Step 7 time ------------------------------------------------------------------------------- 38
6.2.6 Auto/Manual control switching ---------------------------------------------------- 38
6.2.7 Control output OFF function ------------------------------------------------------ 38
6.2.8 MV, Remaining step time indication -------------------------------------------- 38
7. Set value memory function (SM option) ---------------------------------------- 39
8. Operation
8.1 When using the FCD-13A as a Temperature controller ------------------------ 40
8.2 When using the FCD-13A as a Simplified programmable controller ------- 41
9. Action explanations
9.1 OUT1 action ----------------------------------------------------------------------------- 42
9.2 Heater burnout alarm action (option) ---------------------------------------------- 42
9.3 ON/OFF control -------------------------------------------------------------------------- 43
9.4 Pattern end action ---------------------------------------------------------------------- 43
9.5 OUT2 (Heating/Cooling control) action (DR, DS, DA option) --------------- 44
9.5.1 OUT2 (Heating/Cooling control) action ---------------------------------------- 44
9.5.2 When setting Dead band ---------------------------------------------------------- 45
9.5.3 When setting Overlap band with Relay contact output -------------------- 46
9.6 Alarm 1 (A1) to Alarm 4 (A4) action ------------------------------------------------ 47
10. Control actions
10.1 Fuzzy self-tuning ---------------------------------------------------------------------- 49
10.2 PID ---------------------------------------------------------------------------------------- 49
10.3 AT (auto-tuning) of this controller ------------------------------------------------- 50
11. Attached functions ------------------------------------------------------------------- 51
12. Specifications
12.1 Standard specifications -------------------------------------------------------------- 52
12.2 Optional specifications --------------------------------------------------------------- 56
13. Troubleshooting ----------------------------------------------------------------------- 60
14. Character table ------------------------------------------------------------------------- 62
6
6.2.3 Auxiliary function setting mode 1
Set value lock --------------------------------------------------------------------------- 28
SV high limit ----------------------------------------------------------------------------- 29
SV low limit ------------------------------------------------------------------------------ 29
Sensor correction ---------------------------------------------------------------------- 29
Overlap/Dead band -------------------------------------------------------------------- 29
Remote/Local setting ------------------------------------------------------------------ 30
Instrument number --------------------------------------------------------------------- 30
Communication speed ---------------------------------------------------------------- 30
Communication protocol ------------------------------------------------------------- 30
6.2.4 Auxiliary function setting mode 2
Scaling high limit ----------------------------------------------------------------------- 31
Scaling low limit ------------------------------------------------------------------------ 31
Decimal point place ------------------------------------------------------------------- 31
PV filter time constant ---------------------------------------------------------------- 31
OUT1 high limit ------------------------------------------------------------------------- 31
OUT1 low limit -------------------------------------------------------------------------- 31
OUT1 ON/OFF hysteresis ----------------------------------------------------------- 32
OUT2 action mode --------------------------------------------------------------------- 32
OUT2 high limit ------------------------------------------------------------------------- 32
OUT2 low limit -------------------------------------------------------------------------- 32
OUT2 ON/OFF hysteresis ----------------------------------------------------------- 32
A3 type ----------------------------------------------------------------------------------- 32
A4 type ----------------------------------------------------------------------------------- 33
A1 action Energized/De-energized ------------------------------------------------ 33
A2 action Energized/De-energized ------------------------------------------------ 33
A3 action Energized/De-energized ------------------------------------------------ 33
A4 action Energized/De-energized ------------------------------------------------ 33
A1 hysteresis --------------------------------------------------------------------------- 33
A2 hysteresis --------------------------------------------------------------------------- 33
A3 hysteresis --------------------------------------------------------------------------- 34
A4 hysteresis --------------------------------------------------------------------------- 34
A1 action delay timer ----------------------------------------------------------------- 34
A2 action delay timer ----------------------------------------------------------------- 34
A3 action delay timer ----------------------------------------------------------------- 34
A4 action delay timer ----------------------------------------------------------------- 34
External setting input high limit ----------------------------------------------------- 35
External setting input low limit ------------------------------------------------------ 35
Transmission output ------------------------------------------------------------------- 35
Transmission output high limit ------------------------------------------------------ 35
Transmission output low limit ------------------------------------------------------- 35
Indication when control output OFF ----------------------------------------------- 35
SV rise rate ------------------------------------------------------------------------------ 35
SV fall rate ------------------------------------------------------------------------------- 36
Output status when input abnormal ------------------------------------------------ 36
7
6.2.5 Program mode ----------------------------------------------------------------------- 36
Fixed value control/Program control switching --------------------------------- 37
Step 1 time ------------------------------------------------------------------------------- 37
Step 2 time ------------------------------------------------------------------------------- 37
Step 3 time ------------------------------------------------------------------------------- 37
Step 4 time ------------------------------------------------------------------------------- 37
Step 5 time ------------------------------------------------------------------------------- 37
Step 6 time ------------------------------------------------------------------------------- 38
Step 7 time ------------------------------------------------------------------------------- 38
6.2.6 Auto/Manual control switching ---------------------------------------------------- 38
6.2.7 Control output OFF function ------------------------------------------------------ 38
6.2.8 MV, Remaining step time indication -------------------------------------------- 38
7. Set value memory function (SM option) ---------------------------------------- 39
8. Operation
8.1 When using the FCD-13A as a Temperature controller ------------------------ 40
8.2 When using the FCD-13A as a Simplified programmable controller ------- 41
9. Action explanations
9.1 OUT1 action ----------------------------------------------------------------------------- 42
9.2 Heater burnout alarm action (option) ---------------------------------------------- 42
9.3 ON/OFF control -------------------------------------------------------------------------- 43
9.4 Pattern end action ---------------------------------------------------------------------- 43
9.5 OUT2 (Heating/Cooling control) action (DR, DS, DA option) --------------- 44
9.5.1 OUT2 (Heating/Cooling control) action ---------------------------------------- 44
9.5.2 When setting Dead band ---------------------------------------------------------- 45
9.5.3 When setting Overlap band with Relay contact output -------------------- 46
9.6 Alarm 1 (A1) to Alarm 4 (A4) action ------------------------------------------------ 47
10. Control actions
10.1 Fuzzy self-tuning ---------------------------------------------------------------------- 49
10.2 PID ---------------------------------------------------------------------------------------- 49
10.3 AT (auto-tuning) of this controller ------------------------------------------------- 50
11. Attached functions ------------------------------------------------------------------- 51
12. Specifications
12.1 Standard specifications -------------------------------------------------------------- 52
12.2 Optional specifications --------------------------------------------------------------- 56
13. Troubleshooting ----------------------------------------------------------------------- 60
14. Character table ------------------------------------------------------------------------- 62
8
1 Model
1.1 Model
Alphanumeric characters to represent the control output, input or options are entered
where underlined.
[Example]
FCD-13A- R / M, A2
Alarm 2 (A2) output
Multi-range input
Relay contact output
Standard model
F C D – 1 3 A
/ M Series name: FCD-13A
Control action 3 PID control *1
Alarm 1 (A1)
A Alarm action *2
R Relay contact
S Non-contact voltage
Control output (OUT1)
A DC current
Input
M Multi-range input *3
*1: Fuzzy self-tuning PID, PID, PD and ON/OFF control are selectable by internal DIP
switch.
*2: 12 types of alarm plus no alarm action are selectable by internal Rotary and DIP switches.
*3: 16 types of input are selectable by internal Rotary and DIP switches: Thermocouple
(10 types), RTD (3 types), DC current (2 types) and DC voltage (1 type)
Optional specifications
Code
Name
A2
Alarm 2 (A2) output (including Pattern end 2 output)
SA Alarm 3 (A3), Alarm 4 (A4) output
DR
Relay contact
DS
Non-contact voltage
DA
Heating/Cooling
control output (OUT2)
DC current
TA
DC current (4 to 20mA DC)
TV
Transmission output
DC voltage (0 to 1V DC)
C5
RS-485
C
Serial communication
RS-232C
SM Set value memory number external selection
EA
DC current (0 to 20mA DC, 4 to 20mA DC)
EV
External setting
DC voltage (0 to 1V DC, 1 to 5V DC)
W
Single-phase
W3
Heater burnout alarm
Three-phase
LA
Loop break alarm output
P24
Insulated power output
BK
Color: Black
IP Drip-proof/Dust-proof
TC
Terminal cover
(For options in detail, see Section “12.2 Optional specifications”.)
9
Warning
Do not take the inner assembly out nor touch the terminal with the power
supply ON.
Touching the terminal with the power switched ON may result in severe
injury or death due to Electric Shock.
1.2 How to read the model label
Model labels are attached to the case and the inner assembly.
[Model label] [Example]
F C D – 1 3 A – R / M
A 2
W ( 2 0 A )
MULTI RANGE
N o .
(1): Model
(2): Option codes
For the Heater burnout alarm, the specified current value is entered in ( ).
(3): Serial number
Relay contact output, Multi-range input
Alarm 2 output
Heater burnout alarm out
p
ut
(
20A
)
(
1
)
(
2
)
(
3
)
8
1 Model
1.1 Model
Alphanumeric characters to represent the control output, input or options are entered
where underlined.
[Example]
FCD-13A- R / M, A2
Alarm 2 (A2) output
Multi-range input
Relay contact output
Standard model
F C D – 1 3 A / M Series name: FCD-13A
Control action 3 PID control *1
Alarm 1 (A1)
A Alarm action *2
R Relay contact
S Non-contact voltage
Control output (OUT1)
A DC current
Input
M Multi-range input *3
*1: Fuzzy self-tuning PID, PID, PD and ON/OFF control are selectable by internal DIP
switch.
*2: 12 types of alarm plus no alarm action are selectable by internal Rotary and DIP switches.
*3: 16 types of input are selectable by internal Rotary and DIP switches: Thermocouple
(10 types), RTD (3 types), DC current (2 types) and DC voltage (1 type)
Optional specifications
Code
Name
A2
Alarm 2 (A2) output (including Pattern end 2 output)
SA Alarm 3 (A3), Alarm 4 (A4) output
DR
Relay contact
DS
Non-contact voltage
DA
Heating/Cooling
control output (OUT2)
DC current
TA
DC current (4 to 20mA DC)
TV
Transmission output
DC voltage (0 to 1V DC)
C5
RS-485
C
Serial communication
RS-232C
SM Set value memory number external selection
EA
DC current (0 to 20mA DC, 4 to 20mA DC)
EV
External setting
DC voltage (0 to 1V DC, 1 to 5V DC)
W
Single-phase
W3
Heater burnout alarm
Three-phase
LA
Loop break alarm output
P24
Insulated power output
BK
Color: Black
IP Drip-proof/Dust-proof
TC
Terminal cover
(For options in detail, see Section “12.2 Optional specifications”.)
9
Warning
Do not take the inner assembly out nor touch the terminal with the power
supply ON.
Touching the terminal with the power switched ON may result in severe
injury or death due to Electric Shock.
1.2 How to read the model label
Model labels are attached to the case and the inner assembly.
[Model label] [Example]
F C D – 1 3 A – R / M
A 2
W ( 2 0 A )
MULTI RANGE
N o .
(1): Model
(2): Option codes
For the Heater burnout alarm, the specified current value is entered in ( ).
(3): Serial number
Relay contact output, Multi-range input
Alarm 2 output
Heater burnout alarm out
p
ut
(
20A
)
1
2
3
10
2 Name and functions of sections
2.1 Name of sections
(3) (2) (1)
(11)
(12)
(4) (13)
(5) (14)
(6) (15)
(7) (16)
(8) (17)
(9) (18)
(10) (19)
(Fig. 2.1-1)
(1) PV display (Red)
Indicates the PV or setting characters in the setting mode.
(2) SV/MV/TIME display (Green)
Indicates the SV, MV, Time or each set value in the setting mode.
(3) MEMO display (Yellow)
Indicates the Set value memory number.
(4) SV indicator (Green)
Lights while the SV is indicated on the SV/MV/TIME display.
(5) MV indicator (Red)
Lights while the MV is indicated on the SV/MV/TIME display.
(6) TIME indicator (Yellow)
Lights while the Time is indicated on the SV/MV/TIME display.
(7) MAN indicator (Red)
Lights during Manual control.
(8) OUT1 indicator (Green)
Lights when the Control output (OUT1) is on.
(For the DC current output type, it flashes in 125ms cycles corresponding to the MV.)
(9) OUT2 indicator (Yellow) (Option)
Lights when the Control output (OUT2) is on.
(For the DC current output type, it flashes in 125ms cycles corresponding to the MV.)
11
(10) TX/RX indicator (Green) (Option)
Lights during Serial communication [TX (transmitting) output].
(11) A1 indicator (including Pattern end 1 output) (Red)
Lights when the Alarm 1 (A1) output or Pattern end 1 output is on.
(12) A2 indicator (including Pattern end 2 output) (Option) (Red)
Lights when the Alarm 2 (A2) output or Pattern end 2 output is on.
(13) A3 indicator (Red) (Option)
Lights when the Alarm 3 (A3) output is on.
(14) A4 indicator (Red) (Option)
Lights when the Alarm 4 (A4) output is on.
(15) HB indicator (Red) (Option)
Lights when the Heater burnout alarm output is on.
(16) REMOTE indicator (Red) (Option)
Lights during Remote action.
(17) SB indicator (Red)
Lights when Sensor is burnt out.
(18) LA indicator (Red) (Option)
Lights when the Loop break alarm output is on.
(19) AT indicator (Yellow)
Flashes during AT (auto-tuning).
2.2 Keys
Main functions are described below, however, the keys have other functions depending
on modes. Refer to Section “6.1 Operation flowchart“.
Increase Key : Increases the numeric value on the SV/MV/TIME display
during setting mode.
Decrease Key : Decreases the numeric value on the SV/MV/TIME display
during setting mode.
Mode Key : Switches a setting mode and registers set values.
(To register each set value, press this key.)
OUT/OFF Key : Performs the control output ON or OFF.
Starts/Stops the program control.
Auto/Manual Key : Switches either Automatic control or Manual control.
Fast Key : Makes the numerical value change faster by pressing the
key with the or key simultaneously.
10
2 Name and functions of sections
2.1 Name of sections
(3) (2) (1)
(11)
(12)
(4) (13)
(5) (14)
(6) (15)
(7) (16)
(8) (17)
(9) (18)
(10) (19)
(Fig. 2.1-1)
(1) PV display (Red)
Indicates the PV or setting characters in the setting mode.
(2) SV/MV/TIME display (Green)
Indicates the SV, MV, Time or each set value in the setting mode.
(3) MEMO display (Yellow)
Indicates the Set value memory number.
(4) SV indicator (Green)
Lights while the SV is indicated on the SV/MV/TIME display.
(5) MV indicator (Red)
Lights while the MV is indicated on the SV/MV/TIME display.
(6) TIME indicator (Yellow)
Lights while the Time is indicated on the SV/MV/TIME display.
(7) MAN indicator (Red)
Lights during Manual control.
(8) OUT1 indicator (Green)
Lights when the Control output (OUT1) is on.
(For the DC current output type, it flashes in 125ms cycles corresponding to the MV.)
(9) OUT2 indicator (Yellow) (Option)
Lights when the Control output (OUT2) is on.
(For the DC current output type, it flashes in 125ms cycles corresponding to the MV.)
11
(10) TX/RX indicator (Green) (Option)
Lights during Serial communication [TX (transmitting) output].
(11) A1 indicator (including Pattern end 1 output) (Red)
Lights when the Alarm 1 (A1) output or Pattern end 1 output is on.
(12) A2 indicator (including Pattern end 2 output) (Option) (Red)
Lights when the Alarm 2 (A2) output or Pattern end 2 output is on.
(13) A3 indicator (Red) (Option)
Lights when the Alarm 3 (A3) output is on.
(14) A4 indicator (Red) (Option)
Lights when the Alarm 4 (A4) output is on.
(15) HB indicator (Red) (Option)
Lights when the Heater burnout alarm output is on.
(16) REMOTE indicator (Red) (Option)
Lights during Remote action.
(17) SB indicator (Red)
Lights when Sensor is burnt out.
(18) LA indicator (Red) (Option)
Lights when the Loop break alarm output is on.
(19) AT indicator (Yellow)
Flashes during AT (auto-tuning).
2.2 Keys
Main functions are described below, however, the keys have other functions depending
on modes. Refer to Section “6.1 Operation flowchart“.
Increase Key : Increases the numeric value on the SV/MV/TIME display
during setting mode.
Decrease Key : Decreases the numeric value on the SV/MV/TIME display
during setting mode.
Mode Key : Switches a setting mode and registers set values.
(To register each set value, press this key.)
OUT/OFF Key : Performs the control output ON or OFF.
Starts/Stops the program control.
Auto/Manual Key : Switches either Automatic control or Manual control.
Fast Key : Makes the numerical value change faster by pressing the
key with the or key simultaneously.
12
3. Setup
3.1 Taking the internal assembly out
Before the power supply to this instrument is turned on, take the internal assembly out
from the case in the direction indicated by the arrow by pushing the latch (bottom of the
instrument) while holding the instrument by the top and bottom.
(Fig. 3.1-1)
3.2 Switch setting (multi-function)
Using a small flat blade screwdriver and tweezers, set the following with the DIP and
Rotary switches.
Sensor input, Alarm 1 (A1) type, Alarm 2 (A2) type, Control action,
Heating (reverse)/Cooling (direct) action, Alarm 1 (A1) and Alarm 2 (A2)
standby function, Unit
/ and Program start Auto/Manual
Rotary switch (SW301) will be equipped only when A2 option is added.
Control action Alarm 2 (A2) type
Heating/Cooling action Alarm 1 (A1) type
Alarm 1 (A1) standby action Sensor input
Alarm 2 (A2) standby action
/
Sensor input
Program start Auto/Manual
(Fig. 3.2-1)
DIP switch
Rotary switch
13
The following items can be selected by the DIP switch (SW304).
Default value: All switches OFF
(Table 3.2-1)
Item
DIP
SW304
No.
Selection Switch status
Fuzzy self-tuning PID control No.1: OFF No.2: OFF
PID control No.1: ON No.2: OFF
PD control No.1: OFF No.2: ON
Control action
1
and
2
ON/OFF control No.1: ON No.2: ON
Heating (reverse) action No.3: OFF Heating/Cooling
action
3
Cooling (direct) action No.3: ON
No standby action No.4: OFF Alarm 1 (A1)
standby action
4
Standby action No.4: ON
No standby action No.5: OFF Alarm 2 (A2)
standby action
(*1)
5
Standby action No.5: ON
No.6: OFF
/
6
No.6: ON
K, J, R, B, N, PL- , Pt100, JPt100
No.7: OFF
Sensor input
(*2)
7
S, E, T, C, 4 to 20mA, 0 to 20mA,
0 to 1V, Pt100
No.7: ON
Manual start No.8: OFF Program start
Auto/Manual
(*3)
8
Automatic start No.8: ON
(*1): The standby function will work only when the A2 option is added.
(*2): Use the Rotary switch (SW303) and DIP switch (SW304) together for making a
selection.
(*3): Program start Auto/Manual: For program control
Manual start : The preset program starts by pressing the key.
Automatic start : The preset program automatically starts from Step 1 after 2 seconds
of warm-up status after power-on.
12
3. Setup
3.1 Taking the internal assembly out
Before the power supply to this instrument is turned on, take the internal assembly out
from the case in the direction indicated by the arrow by pushing the latch (bottom of the
instrument) while holding the instrument by the top and bottom.
(Fig. 3.1-1)
3.2 Switch setting (multi-function)
Using a small flat blade screwdriver and tweezers, set the following with the DIP and
Rotary switches.
Sensor input, Alarm 1 (A1) type, Alarm 2 (A2) type, Control action,
Heating (reverse)/Cooling (direct) action, Alarm 1 (A1) and Alarm 2 (A2)
standby function, Unit / and Program start Auto/Manual
Rotary switch (SW301) will be equipped only when A2 option is added.
Control action Alarm 2 (A2) type
Heating/Cooling action Alarm 1 (A1) type
Alarm 1 (A1) standby action Sensor input
Alarm 2 (A2) standby action
/
Sensor input
Program start Auto/Manual
(Fig. 3.2-1)
DIP switch
Rotary switch
13
The following items can be selected by the DIP switch (SW304).
Default value: All switches OFF
(Table 3.2-1)
Item
DIP
SW304
No.
Selection Switch status
Fuzzy self-tuning PID control No.1: OFF No.2: OFF
PID control No.1: ON No.2: OFF
PD control No.1: OFF No.2: ON
Control action
1
and
2
ON/OFF control No.1: ON No.2: ON
Heating (reverse) action No.3: OFF Heating/Cooling
action
3
Cooling (direct) action No.3: ON
No standby action No.4: OFF Alarm 1 (A1)
standby action
4
Standby action No.4: ON
No standby action No.5: OFF Alarm 2 (A2)
standby action
(*1)
5
Standby action No.5: ON
No.6: OFF
/
6
No.6: ON
K, J, R, B, N, PL- , Pt100, JPt100
No.7: OFF
Sensor input
(*2)
7
S, E, T, C, 4 to 20mA, 0 to 20mA,
0 to 1V, Pt100
No.7: ON
Manual start No.8: OFF Program start
Auto/Manual
(*3)
8
Automatic start No.8: ON
(*1): The standby function will work only when the A2 option is added.
(*2): Use the Rotary switch (SW303) and DIP switch (SW304) together for making a
selection.
(*3): Program start Auto/Manual: For program control
Manual start : The preset program starts by pressing the
key.
Automatic start : The preset program automatically starts from Step 1 after 2 seconds
of warm-up status after power-on.
14
Select a sensor type using the Rotary switch (SW303) and DIP switch (SW304).
Default value: K -200 to 1370
Note: If the input type is changed, Scaling high/low limit, External setting input
high/low limit (optional), Transmission output high/low limit (optional)
will become the altered input range high/low limit value.
(Table 3.2-2)
Scale range (DIP SW304 No.6)
Rotary
SW303
No.
DIP
SW304
No. 7
Sensor type
OFF ON
0 OFF K -200 to 1370 -320 to 2500
1 OFF J -200 to 1000 -320 to 1800
2 OFF R 0 to 1760 0 to 3200
3 OFF B 0 to 1820 0 to 3300
4 OFF PL- 0 to 1390 0 to 2500
5 OFF N 0 to 1300 0 to 2300
6 OFF Pt100 -199.9 to 850.0 -199.9 to 999.9
7 OFF JPt100 -199.9 to 500.0 -199.9 to 900.0
0 ON S 0 to 1760 0 to 3200
1 ON E 0 to 1000 0 to 1800
2 ON T -199.9 to 400.0 -199.9 to 750.0
3 ON C (W/Re5-26) 0 to 2315 0 to 4200
4 ON 4 to 20mA DC -1999 to 9999
5 ON 0 to 20mA DC -1999 to 9999
6 ON 0 to 1V DC -1999 to 9999
7 ON Pt100 -200 to 850 -320 to 1560
15
The alarm type and the pattern end output for program control can be selected by
the Rotary switch (SW302) and (SW301).
Rotary switch (SW301) will be equipped only when the A2 option is added.
Rotary SW302: Alarm 1 (A1) type or Pattern end 1 output
Rotary SW301: Alarm 2 (A2) type or Pattern end 2 output
Note: If an alarm type is changed, the alarm set value becomes 0 (0.0).
Default value: No alarm action
(Table 3.2-3)
Alarm 1 (A1) type
Rotary
SW302
No.
Alarm 2 (A2) type
Rotary
SW301
No.
No alarm action 0 No alarm action 0
High limit alarm 1 High limit alarm 1
Low limit alarm 2 Low limit alarm 2
High/Low limits alarm 3 High/Low limits alarm 3
High/Low limit range alarm 4 High/Low limit range alarm 4
Process high alarm 5 Process high alarm 5
Process low alarm 6 Process low alarm 6
Pattern end 1 output 7 Pattern end 2 output 7
3.3 Insertion of the internal assembly
After the setup is completed, insert the internal assembly into the case.
Firmly insert the assembly until it is locked by the latch at the bottom of the instrument.
(There will be a clicking sound.)
Caution
Do not confuse the top and bottom of the internal assembly.
If inserting the assembly into the case by force in the wrong direction, the PCB may be
damaged.
14
Select a sensor type using the Rotary switch (SW303) and DIP switch (SW304).
Default value: K -200 to 1370
Note: If the input type is changed, Scaling high/low limit, External setting input
high/low limit (optional), Transmission output high/low limit (optional)
will become the altered input range high/low limit value.
(Table 3.2-2)
Scale range (DIP SW304 No.6)
Rotary
SW303
No.
DIP
SW304
No. 7
Sensor type
OFF ON
0 OFF K -200 to 1370 -320 to 2500
1 OFF J -200 to 1000 -320 to 1800
2 OFF R 0 to 1760 0 to 3200
3 OFF B 0 to 1820 0 to 3300
4 OFF PL- 0 to 1390 0 to 2500
5 OFF N 0 to 1300 0 to 2300
6 OFF Pt100 -199.9 to 850.0 -199.9 to 999.9
7 OFF JPt100 -199.9 to 500.0 -199.9 to 900.0
0 ON S 0 to 1760 0 to 3200
1 ON E 0 to 1000 0 to 1800
2 ON T -199.9 to 400.0 -199.9 to 750.0
3 ON C (W/Re5-26) 0 to 2315 0 to 4200
4 ON 4 to 20mA DC -1999 to 9999
5 ON 0 to 20mA DC -1999 to 9999
6 ON 0 to 1V DC -1999 to 9999
7 ON Pt100 -200 to 850 -320 to 1560
15
The alarm type and the pattern end output for program control can be selected by
the Rotary switch (SW302) and (SW301).
Rotary switch (SW301) will be equipped only when the A2 option is added.
Rotary SW302: Alarm 1 (A1) type or Pattern end 1 output
Rotary SW301: Alarm 2 (A2) type or Pattern end 2 output
Note: If an alarm type is changed, the alarm set value becomes 0 (0.0).
Default value: No alarm action
(Table 3.2-3)
Alarm 1 (A1) type
Rotary
SW302
No.
Alarm 2 (A2) type
Rotary
SW301
No.
No alarm action 0 No alarm action 0
High limit alarm 1 High limit alarm 1
Low limit alarm 2 Low limit alarm 2
High/Low limits alarm 3 High/Low limits alarm 3
High/Low limit range alarm 4 High/Low limit range alarm 4
Process high alarm 5 Process high alarm 5
Process low alarm 6 Process low alarm 6
Pattern end 1 output 7 Pattern end 2 output 7
3.3 Insertion of the internal assembly
After the setup is completed, insert the internal assembly into the case.
Firmly insert the assembly until it is locked by the latch at the bottom of the instrument.
(There will be a clicking sound.)
Caution
Do not confuse the top and bottom of the internal assembly.
If inserting the assembly into the case by force in the wrong direction, the PCB may be
damaged.
16
4. Mounting to the control panel
4.1 Site selection
This instrument is intended to be used under the following conditions (IEC61010-1):
Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
(1) A minimum of dust, and an absence of corrosive gases
(2) No flammable, explosive gases
(3) No mechanical vibrations or shocks
(4) No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 )
that does not change rapidly, and no icing
(5) An ambient non-condensing humidity of 35 to 85%RH
(6) No large capacity electromagnetic switches or cables through which large current
flows
(7) No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
(8) Take note that ambient temperature of this unit must not exceed 50
(122 ) if
mounted through the face of a control panel. Otherwise the life of electronic
components (especially electrolytic capacitors) may be shortened.
4.2 External dimensions (Scale: mm)
(Fig. 4.2-1)
4.3 Panel cutout (Scale: mm)
Lateral close mounting
n: Number of units mounted
(Fig. 4.3-1)
92
+0.8
0
92
+0.8
0
130
n x 96-3
+0.5
0
10
100
91
106.2
96
106 (For TC option)
17
4.4 Current transformer (CT) dimensions (Scale: mm)
CTL-6S (for 20A) CTL-12-S36-10L1U (for 50A)
(Fig. 4.4-1)
4.5 Mounting
Mountable panel thickness is 1 to 8mm.
Insert the FCD-13A from the front of the panel.
Attach the mounting brackets to the slots at the top and bottom of the case,
and secure the controller in place with the screws provided.
Notice
As the case is made of resin, do not use excessive force while screwing in the
mounting bracket. The torque should be 0.12N•m.
(Fig. 4.5-1)
16
4. Mounting to the control panel
4.1 Site selection
This instrument is intended to be used under the following conditions (IEC61010-1):
Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
(1) A minimum of dust, and an absence of corrosive gases
(2) No flammable, explosive gases
(3) No mechanical vibrations or shocks
(4) No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly, and no icing
(5) An ambient non-condensing humidity of 35 to 85%RH
(6) No large capacity electromagnetic switches or cables through which large current
flows
(7) No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
(8) Take note that ambient temperature of this unit must not exceed 50 (122 ) if
mounted through the face of a control panel. Otherwise the life of electronic
components (especially electrolytic capacitors) may be shortened.
4.2 External dimensions (Scale: mm)
(Fig. 4.2-1)
4.3 Panel cutout (Scale: mm)
Lateral close mounting
n: Number of units mounted
(Fig. 4.3-1)
92
+0.8
0
92
+0.8
0
130
n x 96-3
+0.5
0
10
100
91
106.2
96
106 (For TC option)
17
4.4 Current transformer (CT) dimensions (Scale: mm)
CTL-6S (for 20A) CTL-12-S36-10L1U (for 50A)
(Fig. 4.4-1)
4.5 Mounting
Mountable panel thickness is 1 to 8mm.
Insert the FCD-13A from the front of the panel.
Attach the mounting brackets to the slots at the top and bottom of the case,
and secure the controller in place with the screws provided.
Notice
As the case is made of resin, do not use excessive force while screwing in the
mounting bracket. The torque should be 0.12N•m.
(Fig. 4.5-1)
18
5. Wiring
Warning
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in
severe injury or death due to Electric Shock.
Moreover, the instrument must be grounded before the power supply to the
instrument is turned on.
Caution
• Do not leave wire remnants in the instrument, because they could cause a fire or malfunction.
Use a solderless terminal with an insulation sleeve in which the M3 screw fits when
wiring the instrument.
Tighten the terminal screw using the specified torque. If excessive force is applied to
the screw when tightening, the terminal screw or case may be damaged.
The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened by the
terminal screw.
• Do not apply a commercial power source to the sensor which is connected to the input
terminal nor allow the power source to come into contact with the sensor.
Use a thermocouple and compensating lead wire according to the sensor input
specifications of this controller.
• Use a 3-wire RTD system corresponding to the input specifications of this controller.
• This controller does not have a built-in power switch, circuit breaker or fuse.
Therefore, it is necessary to install them in a circuit near the external controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
When using a relay contact output type, use a relay according to the load capacity to
protect the built-in relay contact.
When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or
load wires.
• Use a thick wire (1.25 to 2.0mm
2
) for grounding.
Lead wire solderless terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown
below. The torque should be 0.63N•m.
Solderless
terminal
Manufacturer Model Torque
Nichifu Terminal Industries CO.,LTD. TMEV1.25Y-3
Y type
Japan Solderless Terminal MFG CO.,LTD. VD1.25-B3A
Nichifu Terminal Industries CO.,LTD. TMEV1.25-3
Ring type
Japan Solderless Terminal MFG CO.,LTD. V1.25-3
0.63N•m
(Fig. 5-1)
3.2mm
5.8mm or less
3.2mm
5.8mm or less
19
11
12
13
14
15
16
17
18
19
20
3121
22
23
24
25
26
27
28
29
30
32
33
34
35
36
37
38
39
1
2
3
4
5
6
9
10
TX[YA(-)]
RX[YB(+)]
b0
b1
b2
COM
RS-232C
[RS-485]
SM
TA or TV
A3
A4
18
19
100 to 240V AC
or 24V AC/DC
A1/P.END1
H
OUT1(R/M) C
L
Ground
18
19
17
18
19
5
6
+
-
OUT1(S/M or A/M)
+
-
mA DC
+
-
V DC
A
B
B
RTD
TC
+
-
+
-
+
-
+
-
CT1
CT2
W or W3
R/L
A/M
COM
EA or EV
7
8
OUT2(DR)/A2/
P.END2/LA/P24
7
8
OUT2(DS, DA)/A2/
P.END2/LA/P24
+
-
5.1 Terminal arrangement
(Fig. 5.1-1)
Dotted lines show options, and no terminal is equipped unless specified.
If Alarm 2 (Pattern end 2 output) and Loop break alarm are added together, they
utilize common output terminals.
OUT1 Control output 1
OUT2 Control output 2
A1 to A4 Alarm 1 to Alarm 4 output
P.END1, 2 Pattern end 1, 2 output (simplified program controller function)
LA Loop break alarm output
P24 Insulated power output
RS-232C[RS-485] Serial communication
SM Set value memory number external selection
TC Thermocouple input
RTD RTD input
DC DC voltage, current input
TA or TV Transmission output
EA or EV External setting input
R/L, A/M External operation: Remote/Local, Auto/Manual (EA, EV option
should be added) (See p. 21.)
CT1, CT2 CT1 input (W, W3 option), CT2 input (W3 option)
W or W3 Heater burnout alarm output
18
5. Wiring
Warning
Turn the power supply to the instrument off before wiring or checking.
Working or touching the terminal with the power switched on may result in
severe injury or death due to Electric Shock.
Moreover, the instrument must be grounded before the power supply to the
instrument is turned on.
Caution
• Do not leave wire remnants in the instrument, because they could cause a fire or malfunction.
Use a solderless terminal with an insulation sleeve in which the M3 screw fits when
wiring the instrument.
Tighten the terminal screw using the specified torque. If excessive force is applied to
the screw when tightening, the terminal screw or case may be damaged.
The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened by the
terminal screw.
• Do not apply a commercial power source to the sensor which is connected to the input
terminal nor allow the power source to come into contact with the sensor.
Use a thermocouple and compensating lead wire according to the sensor input
specifications of this controller.
• Use a 3-wire RTD system corresponding to the input specifications of this controller.
• This controller does not have a built-in power switch, circuit breaker or fuse.
Therefore, it is necessary to install them in a circuit near the external controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
When using a relay contact output type, use a relay according to the load capacity to
protect the built-in relay contact.
When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or
load wires.
• Use a thick wire (1.25 to 2.0mm
2
) for grounding.
Lead wire solderless terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown
below. The torque should be 0.63N•m.
Solderless
terminal
Manufacturer Model Torque
Nichifu Terminal Industries CO.,LTD. TMEV1.25Y-3
Y type
Japan Solderless Terminal MFG CO.,LTD. VD1.25-B3A
Nichifu Terminal Industries CO.,LTD. TMEV1.25-3
Ring type
Japan Solderless Terminal MFG CO.,LTD. V1.25-3
0.63N•m
(Fig. 5-1)
3.2mm
5.8mm or less
3.2mm
5.8mm or less
19
11
12
13
14
15
16
17
18
19
20
31
21
22
23
24
25
26
27
28
29
30
32
33
34
35
36
37
38
39
1
2
3
4
5
6
9
10
TX[YA(-)]
RX[YB(+)]
b0
b1
b2
COM
RS-232C
[RS-485]
SM
TA or TV
A3
A4
18
19
100 to 240V AC
or 24V AC/DC
A1/P.END1
H
OUT1(R/M) C
L
Ground
18
19
17
18
19
5
6
+
-
OUT1(S/M or A/M)
+
-
mA DC
+
-
V DC
A
B
B
RTD
TC
+
-
+
-
+
-
+
-
CT1
CT2
W or W3
R/L
A/M
COM
EA or EV
7
8
OUT2(DR)/A2/
P.END2/LA/P24
7
8
OUT2(DS, DA)/A2/
P.END2/LA/P24
+
-
5.1 Terminal arrangement
(Fig. 5.1-1)
Dotted lines show options, and no terminal is equipped unless specified.
If Alarm 2 (Pattern end 2 output) and Loop break alarm are added together, they
utilize common output terminals.
OUT1 Control output 1
OUT2 Control output 2
A1 to A4 Alarm 1 to Alarm 4 output
P.END1, 2 Pattern end 1, 2 output (simplified program controller function)
LA Loop break alarm output
P24 Insulated power output
RS-232C[RS-485] Serial communication
SM Set value memory number external selection
TC Thermocouple input
RTD RTD input
DC DC voltage, current input
TA or TV Transmission output
EA or EV External setting input
R/L, A/M External operation: Remote/Local, Auto/Manual (EA, EV option
should be added) (See p. 21.)
CT1, CT2 CT1 input (W, W3 option), CT2 input (W3 option)
W or W3 Heater burnout alarm output
20
Single-phase
Ground
24V
SSR
Alarm unit
Thermocouple
Heater
CT
5.2 Wiring examples
FCD-13A-R/M
* To prevent the unit from harmful effects of unexpected level noise, it is recommended
that a surge absorber be installed between the electromagnetic switch coils.
(Fig. 5.2-1)
FCD-13A-S/M, W
The connectable SSRs in parallel are 4 units if the Shinko SSRs (SA-300 series)
are used.
For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
(Fig. 5.2-2)
3-phase
100 to 240V AC
Ground
Heater
Electric furnace
Thermocouple
Alarm unit
Electro-
magnetic
switch
Power supply
for Alarm unit
*
21
External operation input [Available only when External setting (EA, EV) option is added]
(Fig. 5.2-3)
Manual control : Close terminals 26 and 27.
Automatic control : Open terminals 26 and 27.
Remote setting : Close terminals 25 and 27.
Or open terminals 25 and 27, then select “Remote setting” using the
keypad.
Local setting : Open terminals 25 and 27 and select “Local setting” using the keypad.
25-27 Closed: Always Remote setting (Keypad operation is invalid.)
Current transformer 1, 2 (CT1, CT2) input (Option code: W, W3)
(1) This alarm is not available for detecting current under phase control.
(2) Use the current transformer (CT) provided, and pass one lead wire of the heater
circuit into the hole of the CT.
(3) When wiring, keep the CT wire away from AC sources and load wires to avoid the
external interference.
[Single-phase heater]
CT1
Power source
Heater
(Fig. 5.2-4)
[3-phase heater]
(Fig. 5.2-5)
34
35
36
37
3-phase heater
CT1
CT2
R
S
T
Power
source
R/L
A/M
COM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Shinko FCD-13A User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI