Texmate FL-B101D40-RPM Owner's manual

Type
Owner's manual
FL-B101D40-RPM (d0073)_UL manual Page 1
Smart Tri or Mono color digital bargraph
with four fully programmable set points
for RPM measurement.
• ThismeterhasbeendesignedspecificallyforRPMmeasurements.
JustenterthepulesperrevolutionandtheFL-B01D-RPMbargraph
willcalculateanddisplaytheRPMreading.
• Three ranges with resolution of 0.1 RPM, 1 RPM and 10 RPM
(99.99x1000rpmmax).
• Optionalisolated16bitanalogoutput.Userorfactoryscalable
to4to20mA,0to20mAor0to10Vacrossanydesireddigital
spanfrom±onecounttothefullscalerangeof0to9999.
• Standard101segmentRedBarandRed4-digitLEDdisplaywith
arangeof0to9999.OptionalGreenBarandGreenDigitaldis-
play.AlsoOptionalProgrammableTricolor(Red-Green-Orange)
Barisavailable.Verticaloroptionalhorizontalformat.
• FrontpanelLEDannunciatorsprovideindicationofsetpointstatus.
• Two9AmpFormC,andtwo4AmpFormArelaysavailable
• Provisiontoconnectanexternalprogramminglockoutswitch.
• ProvisionforexternalDIMswitchtoreducethebrightest
displaysettingby50%.
• OptionalNEMA-4frontcover.
• Automaticintelligentaveraging,smoothsnoisysignalswhile
providingafastdisplayresponsetoreallevelchanges.
• ULListed
General Features Specifications
Index
FL-B101D40-RPM
• Thebargraphcandisplay,full
scale,anydesiredportionof
thedigitalreading.
•
Bargraphcenterzerofunction.
•
Fourprogrammablesetpoints
withadjustableHysteresis.
• Setpoint1hasdelay-on-make
anddelay-on-breakplus
aspecial“pumponpump
off”modethatcreatesa
Software Features
HysteresisBandbetweenSP1
andSP2.
• Relayactivationcanbeselect-
edtooccurabove(hi)orbelow
(Lo)eachsetpoint.
• Digitaldisplayblanking.
• Decimalpointsetting.
• Four-levelbrightnesscontrol
accessedbythe buttonand
adjustedbythe
button.
BargraphCenterPointDisplayModeSelection... 6
BargraphColorProgrammingMode........ 9
CaseDimensions ....................... 7
ComponentLayout..................... 11
ConnectorPinouts ..................... 10
Connectors........................... 11
ControlsandIndicators.................. 2
CustomFaceplatesandScales ........... 19
DecimalPointandBrightnessSelection..... 5
ProgrammingConventions................ 2
SetpointSetting&RelayConfigurationMode....8-9
SoftwareFeatures...................... 1
SoftwareLogicTree ..................... 3
Specifications.......................... 1
StandardFaceplatesandScales .......... 18
TwoPointAnalogRangeSetting&Calibration .... 7
TwoPointDigitalCalibrationMode......... 4
DigitalSpanSelectionforDisplay.......... 5
DigitalSpanSelectionforAnalogRangeOutput... 6
FunctionalDiagram.................... 10
GeneralFeatures....................... 1
I-SeriesInputSignalConditioningModules...12-15
InputModuleCalibrationProcedures...... 17
InputModuleComponentGlossary........ 16
OrderingInformation................... 20
PinDescriptions ....................... 10
Input Specs:..............DependsonInputsignalconditioner
A/D Converter:..........14bitsingleslope
Accuracy:..................±(0.05%ofreading+2counts)
Temp. Coeff.:.............100ppm/°C(Typical)
Warm up time:...........2minutes
Conversion Rate:......10conversionspersecond(Typical)
Digital Display:..........
4 digit 0.31" LED red (std),green(optn)
Range
0to9999counts.
Bargraph Display:.....
101 segment 4” red vertical (std),
greenortricolor(optn),horizontal(optn)
Polarity:.....................Assumedpositive.Displays–negative
Decimal Selection:....Frontpanelbuttonselectable,X•X•X•X•
Positive Overrange:. . Bargraphandtopsegmentsofdigital
displayflash.
Negative Overrange:Firstsegmentofbargraphandbottom
segmentsofdigitaldisplayflash.
Relay Output:............Two4AmpFormArelaysandTwo
9AmpFormCrelays.
Analog Output:.........Isolated16bituserscalablemAorV
 OIC(mAout)...........
4-20mA@0to500Ωmaxloopresistance
OIV(voltsout).......... 0-10VDC@500Ωorhigherresistance
Power Supply:...........AC/DCAutosensingwiderangesupply
PS1 (std)................
85-265 VAC / 95-300 VDC, 50-400Hz 4.2W
 PS2.........................
18-48VAC/10-72VDC,50-400Hz4.2W
Operating Temp.:......0to50°C
Storage Temp:...........–20°Cto70°C
Relative Humidity:....95%(noncondensing)
Case Dimensions:....
9/64DIN(Bezel36Wx144Hmm)
Depthbehindbezel(5.83")148mm
Plus(0.7”)18mmforconnectors
Weight:.......................9.5oz.,12ozwhenpacked
101Segment,4Digit0.32”LEDs
ina9/64DINCASE
Page2 FL-B101D40-RPM(d0073)_UL manual
Front Panel Buttons
Program Button
The
P
buttonisusedtomovefromoneprogramsteptothenext.
When pressed at the same time as the button, it initiates the
calibration mode.Whenpressedatthesametimeasthe but-
ton,itinitiatesthesetpoint setting mode.
UP
Button
DOWN
Button
PROGRAM
Button
LED
Annunciators
forSetpoints
1-4
SevenSegment
LEDDisplay
101Segment
Bargraph
Up Button
Whenintheoperationaldisplay,pressingthe buttonallowsyou
toviewthesettingofthesaved Peak and Valley Values.
When setting a displayed parameter during programming, the
buttonisusedtoincreasethevalueofthedisplayedparameter.
Down Button
Whenintheoperationaldisplay,pressingthe buttonallowsyou
tochangethe Brightness Level aswellastoviewthesettingof
thesetpointsSP1, SP2, SP3 & SP4.
When setting a displayed parameter during programming, the
buttonisusedtodecreasethevalueofthedisplayedparameter.
Front Panel LED Display
Annunciator LEDs
TheannunciatorLEDsindicatethealarmstatus.Theyarelabeled
frombottomtotop:SP1,SP2,SP3,SP4.
Digital LED Displays
The digital LED displays are used to display the meter input
signal readings. They also display the programming  settings
duringprogramming.
Setpoint Indication
Thepositionofsetpointsonthebargraphdisplayareindicatedby
anONorOFFsegmentdependentonthebargraphdisplaybeing
aboveorbelowthesetpoint.
Setpoints
indicated
byanON
Segment
Setpoints
indicated
byanOFF
Segment--
Controls and Indicators
Thissymbolrepresentsthe
OPERATIONALDISPLAY.
ThisisthePROGRAMbutton.
ThisistheUPbutton.
ThisistheDOWNbutton.
When a button is shown, press and
releaseit to go onto the next step in the
direction indicated by the arrow. When
an alternative dotted line is shown, this
indicates that an alternative logic branch
will be followed when a particular option
ispresent.
Whentwobuttonsareshownsidebyside
andenclosedbyadottedline,theymust
bepressedatthesametimethenreleased
togoontothenextprogrammingstep.
IfanXappearsthroughadigit,itmeansthat
anynumberdisplayedinthatdigitisnotrel-
evanttothefunctionbeingexplained.
P
[Span]
[10000]
P
P
When the
and
buttons are shown
together,thedisplayvaluecanbeincreased
by pressing and releasing the
button
ordecreasedbypressingandreleasingthe
button.
When the
and
buttons are shown
with two displays, either display can be
selectedbypressingandreleasingthe
or
buttons.
When two displays are shown together
withbursts,thisindicatesthatthedisplayis
toggling(flashing)betweenthenameofthe
functionandthevalue.
Text or numbers shown between square
brackets in a procedure indicate the pro-
grammingcodenameofthefunctionorthe
valuedisplayedonthemeterdisplay.
Whentherearemorethantwodisplayselec-
tionstheyareshowninbracketsbelowthe
first display and are also selectable by
pressingandreleasingthe
or
buttons.
A dotted line enclosing an entire logic dia-
gram indicates that programming branch
willappear onlywhena particularoptionis
present.
Toexplainsoftwareprogrammingprocedures,logicdiagramsare
usedtovisuallyassistinfollowingtheprogrammingsteps.The
followingsymbolsareusedthroughoutthelogicdiagramsto
representthebuttonsandindicatorsonthemeter:
Programming Conventions
[X•XXX]
[XX•XX]
[XXX•X]
[XXXX•]
[XXXX]
FL-B101D40-RPM (d0073)_UL manual Page 3
TheFL-B101D40-RPMisanintelligentbargraphmeterwithahier-
archical software structure designed for easy programming and
operation,asshownbelowinthesoftwarelogictree.
Software Logic Tree
Peak
[PEAK]
Reset
PEAK
Reset
VALY
Valley
[VALY]
[orAn]
[rEd]
NOTE: Will only
appear if a tricolor
display is installed
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
BARGRAPH COLOR
PROGRAMMING MODE
See Page 9
Tricolor Bargraph
The tri-color bargraph is
designed like a traffic light, to
display either red, orange or
green, but only one color at a
time. The color to be displayed
is selected in two ways.
The first step is to select the
color to be displayed when the
bar is “below” whichever set
point is set to the lowest
position.
The second step is to select the
color to be displayed when the
bar is above each specific
setpoint, regardless of the order
or position to which the set
points are set.
However, if two or more
setpoints with differently
specified colors are positioned
at the same set point value, the
color specified for the set point
with the highest identifying
number will be displayed. When
setpoints are set to the same
value, the SP4 color overrides
the SP3 color, the SP3 color
overrides the SP2 color, and the
SP2 color overrides the SP1
color.
Set Setpoint 1
[SP1]
Delay-on-Make
[doM]
Delay-on-Break
[dob]
Relays
Activation
[rLYS]
(h) High the
relay
energizes
when the
setpoint is
exceeded.
(L) Low
the relay
energizes
below the
setpoint.
Setpoint 2
[SP2]
Setpoint 2
[SP2]
Setpoint 1
[SP1]
Setpoint 3
[SP3]
NOTE: [dom] [dob]
Functions are only
available for SP1
abd SP3
0 to 9999
seconds
0 to 9999
seconds
Hysteresis
[hYSt]
Hysteresis
[hYSt]
Bar Color
[coL]
Hysteresis
[hYSt]
Hysteresis
[hYSt]
Setpoint 3
[SP3]
Setpoint 4
[SP4]
Setpoint 4
[SP4]
Operational Display
MAIN MENU
PEAK & VALLEY
VIEW & RESET
BRIGHTNESS AND
SETPOINT VIEW MODE
Bargraph Center Point
Display Selection [cto]
This branch will
only appear if
the analog
output option
is installed
Back to
Operational
Display
Digital Display
ON/OFF
Selection [diSP]
Sub-menu MODE
Calibration Mode
Calibration
Input
Calibration
Output
Calibrate Analog
Output Low
[cLo]
Calibrate Analog
Output High
[chi]
Select the Digital
Reading at which
the Analog Output
Hi [chi] will occur
Select the Digital
Reading at which
the Analog Output
Lo [cLo] will occur
This branch will only appear
if the analog output option
is installed
DIGITAL SPAN SELECTION
FOR ANALOG RANGE OUTPUT
See Page 6
DIGITAL DISPLAY ON/OFF
See Page 6
BARGRAPH CENTER POINT
DISPLAY MODE SELECTION
See Page 6
TWO POINT ANALOG OUTPUT
RANGE SETTING AND CALIBRATION
See Page 7
Bargraph Display
Scale Lo Range
Setting [bLo]
Bargraph Display
Scale hi Range
Setting [bhi]
DIGITAL SPAN SELECTION
FOR BARGRAPH DISPLAY
See Page 5
Goes directly
to Zero setting
if Analog Output
is not installed
PULSES PER
REVOLUTION, RANGE
SELECTION
+
4.00
+
20.00
1 Dimmest
2 Dim
3 Bright
4 Brightest
SETPOINT SETTING AND
RELAY CONFIGURATION MODE
See Page 8
L or h
L or h
L or h
L or h
Display
Brightness
[br]
Delay-on-Make
[doM]
Delay-on-Break
[dob]
0 to 9999
seconds
0 to 9999
seconds
Sub-menu MODE
Software Version is Displayed on Power-up
Whenpowerisapplied,allsegmentsofthebargraphanddig-
italdisplaylightupfor3seconds.Theversionnumberofthe
installedsoftwareisthendisplayedfor2seconds,afterwhich,
theoperationaldisplayindicatestheinputsignal.
15 Second Program Timeout
ExceptforZEROandSPANsettingsintheTwoPointDigitalCalibrationMode
andtheAnalogOutputRangeSettingandCalibrationMode(cLoandchi),the
meter has a 15 second program timeout. If no buttons are pressed for 15
secondsinanyoftheotherprogrammingsequences,themeterwillexitthe
programmingmodeandreturntotheoperationaldisplay.Anyprogramchang-
esthatweremadepriortopressingthe
P
buttonintheprecedingstepwill
notbesaved.
Page 4 FL-B101D40-RPM(d0073)_UL manual
STEP A Enter the Calibration Mode
 1)
Pressthe
P
and buttonsatthesametime.Displaytog-
glesbetween[CAL]and[oFF].
2) Pressthe or button.Displaychangesfrom[oFF]to
[on].
 3)
Press the
P
 button. Display toggles between [CAL] and
[out].
Note:Ifatthispoint,thedisplayskipsdirectlytoSTEPCandtoggles
between [SPAn] and the previous [SPan] setting, the software is
detectingthattheoptionalanalogoutputhardwareisNOTinstalled.
STEP B
Select Pulese Per Revolution, Range Slection
1) Pressthe or buttontoselectCAL
[iP]forPulesePer
RevolutionSlection.
2) Pressthe
P
button.Display toggles between [PPr] and
thepreviousPulesePerRevolutionsetting.
STEP C Enter the Pulese Per Revolution (PPR)
1) Usingthe and buttons,enterthenumberofpulese
per revolution. Any number between 1 and 9999 may be
enterd.
2) Pressthe
P
button.Displaytogglesbetween[rg]andthe
previousrangesetting.
STEP D Select the Range
1) Usingthe and buttons,seletetherequiredrange.
There are three ranges with resolutions of 0.1 (max. 999.9
RPM),1(max.9999RPM)and10RPM(max.99.99x10000
RPM)
2) Pressthe
P
button.
Pulses Per Revolution and Range Selection
MAIN MENU
Operational Display
Sub-menu
MODE
STEP A Calibration
Mode
STEP B Calibration
Mode
STEP C PPR
STEP D Range
To Digital Span Selection for
Bargraph Display Page 5
cAL out/iP branch will only
appear if the analog output
option is installed, otherwise
cAL on goes directly to ZEro
setting
PULSES PER
REVOLUTION, RANGE
SELECTION
To Digital Span Selection
for Bargraph Display
See Page 6
To Two Point Analog
Output Range Setting
and Calibration
See Page 7
[0.1]
[1]
[10]
FL-B101D40-RPM (d0073)_UL manual Page 5
Example
Example
From Pulses Per
Revolution, Range
Selection Mode
See Page 4
STEP A
STEP B
See Example Above
of Bargraph Display
Scale Range
To Digital Span Selection
for Analog Range Output or
Bargraph Center Point
Display Mode Selection
on Page 6
DIGITAL SPAN SELECTION
FOR BARGRAPH DISPLAY
STEP A Enter the Calibration Sub Menu Mode
1) Pressthe
P
and buttonsatthesametime.Displaytoggles
between[CAL]and[oFF].
2) Press the
P
 button. Display toggles between [bhi] and the
previoussetting.
STEP B Set the Digital Span of the Bargraph Display
(See example
above)
1) Using the  and  buttons, adjust the display to the
desired highparameterreading,e.g.6000counts.
2) Press the
P
 button. Display toggles between [bLo] and the
previoussetting.
3) Using the  and  buttons, adjust the display to the
desired lowparameterreading,e.g.4000counts.
4) Pressthe
P
button.Displaychangesfrom[4000]to[dP].
Note: If at this point, the display skips directly to STEP E and toggles
between[Cto]and[oFF],thesoftwareisdetectingthattheoptionalanalog
outputhardwareisNOTinstalled.
Digital Span Selection For Bargraph Display
Bargraphdoesnotlightupfor
InputSignalsupto3999counts
BargraphlightsupforInput
Signalsabove4000counts
No bargraph
display
Digital display Digital display
%
100
0
10
30
50
70
90
20
40
60
80
4
3
2
1
P
SP
Bargraph display
ends at
6000 counts
Bargraph display
starts at
4000 counts
At 5000 counts
the bargraph display
will be at midpoint
%
100
0
10
30
50
70
90
20
40
60
80
4
3
2
1
P
SP
Example of Setting the Digital Span of the Bargraph Display
to be Different than the Digital Display Range
The bargraph can be set to display full scale (0-101 bars) any portion
ofthedigitalreadingfromaminimumof100countstoamaximumof
12,000 counts. This provides higher resolution bargraph indication for
thoseapplicationswherethenormaloperatinginputsignalrangeisless
thanthedesiredfullscaledisplayrangeofthedigitaldisplay.
For Example:
If the full scale range of the meter has been set from -1999 to
9999 (0-12,000 counts), but the normal operating range of the
input signal is between 4000 & 6000. The bargraph high parame-
ter [bhi] can be set to 6000 and the bargraph low parameter [bLo]
can be set to 4000.
This means that although the meter could digitally display a signal
from -1999 to 9999 (0-12,000 counts), the bargraph display only
begins to function at a reading of 4000, and reaches full scale
indication at a reading of 6000. Although the digital display will
continue reading up to 9999 before indicating overrange, the bar-
graph display will indicate its overrange by flashing for readings
above 6000.
Page 6 FL-B101D40-RPM(d0073)_UL manual
5000
Center
Point
Single
Bar Lit
0
2500
5000
Center
Point
0
2500
4000
As signal
increases
0
5000
Center
Point
2500
1000
As signal
decreases
+ 1 V
Center
Point
Single
Bar Lit
- 1 V
0 V
+ 1 V
Center
Point
- 1 V
0 V
0.800
As signal
increases
+ 1 V
- 1 V
0 V
Center
Point
-0.800
As signal
decreases
Example of Using the Center Point Bargraph Display Mode
with a Unipolar Input
If the meter's full scale range is set to 5000 counts, the midpoint would
be2500counts.Ifasignalof2500countsisappliedonlyonesegmentat
the2500countmarkwilllightup.Ifasignalof4000countsisappliedthe
segmentsbetweenthecenter segment(2500counts) andthe4000count
marklightup.
Ifasignalof1000countsisapplied,thesegmentsbetweenthecenterseg-
ment(2500counts)andthe1000countmarkwilllightup.
Example of Using the Center Point Bargraph Display Mode
with Bipolar Signal Inputs
Themetermayalsobecalibratedtodisplaysymmetricalbipolarsignalssuch
as±1Vor±10V.Whenthecenterpointdisplaymodeisselected,itwill
thenfunctionasacenterzerometer.Whenpositivesignalsareapplied,the
barwillgoupfromthecenterpoint,andwhennegativesignalsareapplied,
thebarwillgodownfromthecenterpoint.
STEP C Selecting the [Anhi] Digital Value for Analog High Output
1) Usingthe and buttons,adjustthedisplaytothedesired
digitalvalueatwhichthe[chi]CalibratedAnalogHighoutputwill
occur.Fordigitalreadingsoutsidethedigitalspanselected,the
analogoutputwilllinearlyriseabovethevaluesetforchi,uptothe
maximumanalogoutputcapability.However,theanalogoutputwill
notgolowerthanthecalibratedvaluesetforcLo(seebelow).
2) Pressthe
P
button.Displaytogglesbetween[AnLo]and
previous[AnLo]setting.
STEP D Selecting the [AnLo] Digital Value for Analog Low Output
1) Usingthe and buttons,adjustthedisplaytothedesired
digitalvalueatwhichthe[cLo]CalibratedAnalogLowoutputwill
occur.ForDigitalreadingsoutsidetheDigitalSpanselected,the
analogoutputwillnotgolowerthanthecalibratedvaluesetfor
cLo.
2) Pressthe
P
button.Thedisplaytogglesbetween[cto]and
[oFF].
Note:Anytwodigitalspan pointsfrom–1999to9999canbeselected. Thedigital
valuesfor[Anhi]analoghighand[AnLo]analoglowcanbereversedtoprovidea20to
4mAoutput.Thedigitalspanselectedcanbeassmallastwocounts,whenusingthe
analogoutputtofunctionasaControlorAlarmDriver.Smalldigitalspanswillcause
thehighresolution16bitDtoAtoincrementdigitallyinstaircasesteps.
Digital Span Selection for Analog Range OutputDigital Span Selection for Analog Range Output
Bargraph Center Point Display Mode Selection
STEP E
Bargraph Center Point Mode Selection (See example above)
1) Toselectbargraphcenterpointmode,pressthe or
 button.Displaychangesfrom[oFF]to[on].
2) Pressthe
P
button.Displaytogglesbetween[diSP]and
 [on]or[oFF].
STEP F Digital Display ON/OFF Selection
1) Tosetthedisplayto[oFF],pressthe or button.
 Displaytogglesbetween[diSP]and[oFF].
2) Pressthe
P
button.Thedisplayexitsthecalibrationmode
and returns to the operational display. Only the bargraph
 displayisonandthedigitaldisplayisoff.
Ifthedigitaldisplayisselectedtobeoff,pressinganybuttonto
makeprogrammingchangesortoviewsetpointsactivatesthedigitaldisplay.
Whenthe procedureiscomplete,the digital displaywillthen automatically
switchoff.
The Display/Bargraph settings are now complete.
Operational Display
STEP E
STEP F
See Example of Bargraph
Center Point Display Mode
Selection Above
From Digital Span Selection
for Analog Range Output Above
or Direct From Digital Span Selection
for Bargraph Display Page 5
if Analog Output Option is Not Present
BARGRAPH CENTER POINT
DISPLAY MODE SELECTION
STEP C
STEP D
This branch will only
appear if the analog
output option is installed
To Bargraph Center
Point Display Mode
Selection Below
From Digital Span
Selection for Bargraph
Display
See Page 5
DIGITAL SPAN SELECTION
FOR ANALOG RANGE OUTPUT
FL-B101D40-RPM (d0073)_UL manual Page 7
Clear Lockable NEMA 4X
Splash Proof Lens Cover
P/N.(OP-N4/144X36 )
133.5mm
(5.27")
Mosaic
Fitting
9/64 DIN
cutout
spacer
To open rear cover,
use a small flat
blade screw driver.
Press down lightly
to release catch and
leaver outwards.
SIDE VIEW
137.7mm
(5.42")
9/64 DIN
cutout
spacer 142.3mm
(5.62")
Max. panel thickness
43mm
(1.7")
For additional strength,
extra Mounting Slide Clips
can be ordered and doubled up
one behind the other.
P/N. (75-DMC144X36)
4.5mm
(0.18")
Metal Surround Case
P/N.(OP-MTL144X36) is pre-installed
at the factory and cannot be removed
without damage to the case.
Two bezel Trim
Strips are supplied with
each Panel Adaptor
Panel Adaptor to fit existing 6" Edgewise
Pointer Meter Cut-Outs P/N.(OP-PA/144x36)
Adaptor uses wide jaw mounting slide
clips.P/N.(75DMC14436B)
When extra panel
mounting tightness is
required,
order the optional
screw mount
clip.
P/N.(OPMTLCLIP)
FRONT VIEW
144mm
(5.69")
36mm
(1.42") 4mm
(0.16")
typical
9/64 DIN
36x144 mm
100
0
10
30
50
70
90
20
40
60
80
4
3
2
1
P
SP
PANEL CUTOUT
138mm
(5.45")
33mm
(1.3")
Snug
Fitting
Loose
Fitting
8 places
7.5mm(0.3")
3.5mm(0.14")
4 places
4 places
32.2 mm
(1.27")
Mosaic
Fitting
133mm
(5.25")
135.2mm
(5.34")
3mm(0.12")
9/64 DIN
cutout
spacer
Case will mount in standard DIN cutouts
Various
bezel colors
are available.
Black is
standard.
The Metal Surround
case uses Metal
Screw Mount Clips
and has a max.
panel thickness
mounting of
7mm(0.28")
TOP VIEW
5mm
(0.20") 117.5mm
(4.64")
18.3mm (0.72")
Straight-thru
Connector
31mm
(1.22")
34mm
(1.34")
Mosaic Fitting
Right-angled
Connector
6mm
(0.24")
10mm
(0.39")
26.5mm (1.05")
Push-On Connector
for FI series IO board
The adapter snaps on
the 36x144 mm
(1.42"x5.69") case and
enables single unit or
stack mounting in an
existing 6" edgewise
pointer meter cut-out.
100
0
25
50
75
100
0
25
50
75
SP1 SP2 SP3 SP4
Zero Span Zero Span
Panel adaptor plates are
available to retrofit most
existing panel cutouts.
31mm
(1.22")
These dimensions are
increased by 2mm (0.08") when
the metal surround case is installed.
For extra strength in portable applications,
the 8 DIN spacers should be snipped
off and the Mosaic fitting cutout used.
Case Dimensions
Operational Display
Sub-menu
MODE
STEP A Calibration
Mode
STEP B Calibration
Mode
STEP E
Calibrate
Analog
Output
Lo
STEP F
Calibrate
Analog
Output
Hi
Will only appear if the analog
output option is installed
To Digital Span Selection
for Bargraph Display
See Page 5
To Two Point Digital
Calibration Mode
See Page 4
Operational Display
TWO POINT ANALOG OUTPUT
RANGE SETTING AND CALIBRATION
+x
x
4.00
+x
x
20.00
DetermineiftheAnalogOutputSelectionHeaderisinthe4to20mA(0-20mA)positionorthe0
to10VDCposition.Ifnecessary,themodulemayhavetoberemovedandtheheaderposition
changed(seeComponentLayoutbelow).
Note: Always disconnect power from the meter before removing the analog output module to
adjustthemAorVoltsoutputselectionheaderandreinstallingit.Whenpowerisreconnected,the
meter’ssoftwarewillautomaticallydetectthepresenceorabsenceoftheanalogoutputmodule.
STEP A Enter the Calibration Mode
1) Pressthe
P
and buttonsatthesametime.Displaytogglesbetween[cAL]and[oFF].
2) Pressthe or button.Displaychangesfrom[oFF]to[on].
3) Pressthe
P
button.Displaytogglesbetween[cAL]and[out]inputcalibration.
Note:IfatthispointthedisplayskipsdirectlytotogglebetweenZeroandthepreviousZero
setting,thesoftwareisdetectingthattheoptionalanalogoutputhardwareisNOTinstalled.
STEP B
EntertheTwoPointAnalog[ouT]OutputRangeSettingandCalibrationMode
1) Pressthe
P
button.Displaytogglesbetween[cLo]andaninternalscalefactor.
STEP E SetorCalibrate[cLo]theLowAnalogValueoftheAnalogOutputRange
1) Connectamultimetertoanalogoutputpins17and18(seeRearPanelPinouts
onpage10).Usingthe and buttons,adjusttheanalogoutputtothedesired
lowvalueasmeasuredonthemultimeter.cLomaybeadjustedtoanyvaluefrom
–0.3mAto18mA(mAoutputselected)orfrom–0.6Vto8V(voltoutputselected).
However,theoutputofcLomustalwaysbelessthanthevalueselectedforchi.If
a reversed analog output is desired, the values selected to establish the Digital
Spancanbereversed(seetopofpage6).FordigitalreadingsoutsidetheDigital
Spanselected,theanalogoutputwillnotgoanylowerthanthecalibratedvalueset
forcLo.However,theanalogoutputwilllinearlyriseabovethevaluesetforchi,up
tothethemaximumanalogoutputcapability(seechibelow).
2) Pressthe
P
button.Displaytogglesbetween[chi]andaninternalscalefactor.
STEP F SetorCalibrate[chi]theHighAnalogValueoftheAnalogOutputRange
1) Usingthe and buttons,adjusttheanalogoutputtothedesiredhighvalue
asmeasuredonthemultimeterdisplay.chimaybeadjustedtoanyvaluefrom18
mAto24mA(mAoutput)orfrom8Vto10.3V(voltoutput).However,thevalue
mustbehigherthanthevalueselectedforcLo.Fordigital readingsoutsidethe
DigitalSpanselected,theanalogoutputwilllinearlyriseabovethevaluesetforchi,
uptothemaximumanalogoutputcapability.
2) Pressthe
P
button.Themeterexitsthecalibrationmodeandreturnstothe
operationaldisplay.
Note:TheanalogoutputrangeestablishedbythevaluesselectedforcLoandchiwilloccur,auto-
maticallyscaled,betweenthetwodigitalvaluesselectedforAnHiandAnLo.However,
theanalog
outputcan linearly rise above the chi valueset for digital readingsoutside the digital span
selected.SeeDigitalSpanSelectiononpage6.
Two Point Analog Output Range Setting and CalibrationTwo Point Analog Output Range Setting and Calibration
Page 8 FL-B101D40-RPM(d0073)_UL manual
Operational Display
SETPOINT SETTING
AND RELAY
CONFIGURATION MODE
STEP A
STEP B
STEP C
STEP D
STEP E
STEP F
STEP G
STEP H
STEP I
STEP J
STEP K
STEP L
STEP M
To Step N of Setpoint
Setting and Relay
Configuration Page 9
0 to 9999
seconds
0 to 9999
seconds
0 to 9999
seconds
0 to 9999
seconds
Thefollowingprogrammingstepsarerequiredtoenterthesetpointvaluesandconfiguretherelayfunctions
inameterwithfourrelaysusingfoursetpoints.Generallyiflessthanfourrelaysareinstalled,thesetpoints
withoutrelaysareoperationalinsoftwarefortri-colorcontrolordisplayonlypurposes.Toremoveunwanted
setpointindications,setthemto9999or-1999dependingontherelayactivationmodeselected.
STEP A Enter the Setpoint Mode
1) Pressthe
P
and buttonsatthesametime.Displaytogglesbetween[SP1]andtheprevious
SP1setting.
STEP B Set Setpoint 1 [SP1]
1) Usingthe and buttons,adjustthedisplaytothedesiredSP1value.
2) Pressthe
P
button.Displaytogglesbetween[doM]andtheprevious[doM]setting.
STEP C Set the SP1 Delay-on-Make [doM] Delay Time Setting
 1)
Usingthe and buttons,adjustthedisplaytothedesired[doM]value(0to9999seconds).
Thereadingmustcontinuouslyremaininanalarmconditionuntilthisdelaytimehaselapsedbefore
therelaywillmakecontact(energize).
2) Pressthe
P
button.Displaytogglesbetween[dob]andtheprevious[dob]setting.
STEP D Set the SP1 Delay-on-Break [dob] Delay Time Setting
 1)
Usingthe and buttons,adjustthedisplaytothedesired[dob]value(0to9999seconds).
Thereadingmustcontinuouslyremaininanon-alarm condition until this delay time has elapsed
beforetherelaywillbreakcontact(de-energize).
2) Pressthe
P
button.Displaytogglesbetween[hYSt]andtheprevious[hYSt]setting.
STEP E Set the Hysteresis [hYSt] Setting for Setpoint 1
 1)
Usingthe and buttons,adjustthedisplaytothedesiredhysteresis[hYSt]value.
2) Pressthe
P
button.Displaytogglesbetween[SP2]andtheprevious[SP2]setting.
STEP F Set Setpoint 2 (SP2)
1) Usingthe and buttons,adjustthedisplaytothedesiredSP2value.
2) Pressthe
P
button.Displaytogglesbetween[hySt]andtheprevious[hySt]setting.
STEP G Set the Hysteresis [hYSt] Setting for Setpoint 2
1) Usingthe and buttons,adjustthedisplaytothedesired
hysteresis[hYSt]value
.
2) Pressthe
P
button.Displaytogglesbetween[SP3]andtheprevious[SP3]setting.
STEP H Set Setpoint 3 (SP3)
 1)
Usingthe and buttons,
adjustthedisplaytothedesiredSP3value
.
2) Pressthe
P
button.Displaytogglesbetween[SP3]andtheprevious[SP3]setting.
STEP I Set the SP3 Delay-on-Make [doM] Delay Time Setting
1)
Usingthe and buttons,adjustthedisplaytothedesired[doM]value(0to9999seconds).
Thereadingmustcontinuouslyremaininanalarmconditionuntilthisdelaytimehaselapsedbefore
therelaywillmakecontact(energize).
2) Pressthe
P
button.Displaytogglesbetween[dob]andtheprevious[dob]setting.
STEP J Set the SP3 Delay-on-Break [dob] Delay Time Setting
 1)
Usingthe and buttons,adjustthedisplaytothedesired[dob]value(0to9999seconds).
Thereadingmustcontinuouslyremaininanon-alarm condition until this delay time has elapsed
beforetherelaywillbreakcontact(de-energize).
2) Pressthe
P
button.Displaytogglesbetween[hYSt]andtheprevious[hYSt]setting.
STEP K Set the Hysteresis [hYSt] Setting for Setpoint 3
 1)
Usingthe and buttons,adjustthedisplaytothedesiredhysteresis[hYSt]value
2) Pressthe
P
button.Displaytogglesbetween[SP4]andtheprevious[SP4]setting.
STEP L Set Setpoint 4 (SP4)
 1)
Usingthe and buttons,
adjustthedisplaytothedesiredSP4value
.
2) Pressthe
P
button.Displaytogglesbetween[hySt]andtheprevious[hySt]setting.
STEP M Set the Hysteresis [hYSt] Setting for Setpoint 4
 1)
Usingthe and buttons,adjustthedisplaytothedesiredhysteresis[hYSt]value
2) Pressthe
P
button.Displaytogglesbetween[rLYS]andthepreviousrelaysetting.
Please Continue On Next Page.
Setpoint Setting and Relay Configuration Mode
FL-B101D40-RPM (d0073)_UL manual Page 9
STEP N
STEP O
STEP P
STEP Q
STEP R
STEP S
STEP T
STEP U
STEP V
[orAn]
[rEd]
NOTE: Will only
appear if a tricolor
display is installed
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
BARGRAPH COLOR
PROGRAMMING MODE
Operational Display
Operational Display
From From Step L of
Setpoint Setting and Relay
Configuration Page 8
L or h
L or h
L or h
L or h
Tocomplywiththelatestsafetyrequirements,thetri-colorbargraphisdesignedlikeatrafficlight,to
displayeither red,orange orgreen,but only onecolorat a time. When thebarreachesa selected
colorchangepoint,theentirebarwillchangetothecolordesignatedforthatzone.Thiseliminatesany
ambiguityastothesignalstatus,especiallyjustaftertransitioningtoanewzone.
First (StepQ)istoselectthecolortobedisplayed,whenthebaris“below*”,whicheversetpointisset
tothelowestposition.
Second (StepsR,S,T,andU)istoselectthecolortobedisplayedwhenthebarisaboveeachspecific
setpoint,regardlessoftheorderorpositiontowhichthesetpointsareset.
However,iftwoormoresetpointswithdifferentlyspecifiedcolorsarepositionedatthesamesetpoint
value,thecolorspecifiedforthesetpointwiththehighestidentifyingnumberwillbedisplayed.When
setpointsaresettothesamevalue,theSP4coloroverridestheSP3color,theSP3coloroverridesthe
SP2color,andtheSP2coloroverridestheSP1color.
STEP Q Select Bargraph Color when the bar is BELOW* the Setpoint that is set to the lowest
position
1) Usingthe and buttons,selectthedesiredbargraphcolor[grn],[oran]or[red]
2) Pressthe
P
button.Displaytogglesbetween[CSP1]andthepreviouscolorsetting.
STEP R Select Bargraph Color when the bar is ABOVE* SP1 Setpoint
1) Usingthe and buttons,selectthedesiredbargraphcolor[grn],[oran]or[red]
2) Pressthe
P
button.Displaytogglesbetween[CSP2]andthepreviouscolorsetting.
STEP S Select Bargraph Color when the bar is ABOVE* SP2 Setpoint
1) Usingthe and buttons,selectthedesiredbargraphcolor[grn],[oran]or[red]
2) Pressthe
P
button.Displaytogglesbetween[CSP3]andthepreviouscolorsetting.
STEP T Select Bargraph Color when the bar is ABOVE* SP3 Setpoint
1) Usingthe and buttons,selectthedesiredbargraphcolor[grn],[oran]or[red]
2) Pressthe
P
button.Displaytogglesbetween[CSP4]andthepreviouscolorsetting.
STEP U Select Bargraph Color when the bar is ABOVE* SP4 Setpoint
1) Usingthe and buttons,selectthedesiredbargraphcolor[grn],[oran]or[red]
2) Pressthe
P
button.Themeter exitsthesetpoint modeandreturnstothe operational
display.
The Bargraph Color programming mode is now complete.
STEP N Set Relay Activation mode [rLYS] for SP1
 (h)Hightherelayenergizeswhenthesetpointisexceeded.(L)Lowtherelayenergizesbelow
thesetpoint.ThesetpointisindicatedfromlefttorightSP1,SP2,SP3,SP4.
1) Usingthe and buttons,select(L)or(h)forthefirstdigit,whichcorrespondstoSP1.
2) Pressthe
P
button.TheSP2RelayActivationdigitbeginstoflash,anditsdecimalpointislit.
STEP O Set High (h) or Low (L) for SP2
1)
Usingthe and buttons,select(L)or(h)fortheseconddigit,whichcorrespondstoSP2.
2)
Pressthe
P
button.TheSP3RelayActivationdigitbeginstoflash,anditsdecimalpointislit.
STEP p Set High (h) or Low (L) for SP3
1) Usingthe and buttons,select(L)or(h)forthethirddigit,whichcorrespondstoSP3.
 2)
Pressthe
P
button.TheSP4RelayActivationdigitbeginstoflash,anditsdecimalpointislit.
STEP Q Set High (h) or Low (L) for SP4
 1)
Usingthe and buttons,select(L)or(h)forthefourthdigit,whichcorrespondstoSP4.
2) Pressthe
P
button.
Ifamono-colorredorgreendisplayisinstalledthentheSetpointRelayProgrammingModeisnowcompleteandthe
meterreturnstotheoperationaldisplay.
IfatricolorbargraphdisplayisinstalledthentheBargraphColorProgrammingModewillbeenteredand
displaytogglesbetween[CoL]andtheprevioussetting.Colorselectionmenuwillbedisplayed.
Setpoint Setting and Relay Configuration Mode Continued
Bargraph Color Programming Mode
1234
SP
P
*Note:Forhorizontaldisplayfor-
matsBELOW*shouldbereadas,
“totheleft”andABOVE*should
bereadas,“totheright”.
Page 10 FL-B101D40-RPM(d0073)_UL manual
Standardplug-inscrewterminalblocksprovidedbyTexmate:
WARNING
AC and DC input signals and power
supply voltages can be hazardous.
Do Not connect live wires to ter-
minal blocks, and do not insert,
remove or handle terminal blocks with live
wires connected.
!
Connectors
!
WARNING: AC and DC input signals and power supply
voltages can be hazardous. Do Not connect live wires to
screw terminal plugs, and do not insert, remove or handle
screw terminal plugs with live wires connected.
SP3
NOSP1/3
COM
SP1
NC SP1
NO
SP4
NOSP2/4
COM
SP2
NC SP2
NO
LOCK
COMM
DIM
SP3 SP4
SP1
COM 1&3
NO3
NC1
COM 2&4
NC2
NO4
NO1
NO2
SP2
8910 11 12 13 14 15 17 18 19 20 21 23 24
1 2 3
Analog
Output +
Analog
Output – AC
Neutral AC
Line
– DC + DC
or
Signal Input
+24V EXC
(50mA MAX)
GND
This meter uses plug-in type screw terminal connectors for all
input and output connections. The power supply connections
(pins23and24)haveauniqueplugandsocketoutlinetoprevent
cross connection. The main board uses standard right-angled
connectors.
Replacement 2-, 3-, and 4-pin plug connectors are available
(seeAccessories onpage20).
Pins 1 to 3 – Input Signal
Pin 1 Signal Input
Pin 2 +24V Excitation (50mV Max)
Pin 23 GND
Pins 8 to 15 – Relay Output Pins
Pin 8 SP3 NO.NormallyOpen4AmpFormA.
Pin 9 SP1/3 COM.CommonforSP1andSP3.
Pin 10 SP1 NC.NormallyClosed9AmpFormC.
Pin 11 SP1 NO.NormallyOpen9AmpFormC.
Pin 12 SP4 NO.NormallyOpen4AmpFormA.
Pin 13 SP2/4 COM.CommonforSP2andSP4.
Pin 14 SP2 NC.NormallyClosed9AmpFormC.
Pin 15 SP2 NO.NormallyOpen9AmpFormC.
Pins 17 to 21 – Rear Panel Switches
Pin 17 ANALOG OUTPUT (+).mA(0to20mA/4to20mA)
orV(0to10V)outputisheaderselectable.
Pin 18
ANALOG OUTPUT (–).mA(0to20mA/4to20mA)
orV(0to10V)outputisheaderselectable.
Pin 19 Programming LOCK.ByconnectingtheLOCKpin 
totheCOMMONpin,themeter'sprogrammed 
parameterscanbeviewedbutnotchanged.
Pin 20 COMMON.ToactivatetheLOCKorDIMfunctions 
fromtherearofthemeter,therespectivepinshave 
tobeconnectedtotheCOMMONpin.Thispinis 
connectedtotheinternalpowersupplyground.
Pin 21 DIM.Byconnectingthedisplaydim(DIM)pinto
 theCOMMONpin,thedisplaybrightnesssetting
 ishalved.
Pins 23 and 24 – AC/DC Power Input
Auto-sensingAC/DCpowersupply.Forvoltagesbetween
85-265VAC/95-300VDC(PS1)or18-48VAC/10-72V
DC(PS2).
Pin 23 AC Neutral / –DC.Neutralpowersupplyline.
Pin 24 AC line / +DC.Livepowersupplyline.
Connector Pinouts
Pin Descriptions
Note:Thesequenceofsetpointoutputsisnow3-1-4-2,enablingdelay
onmake(dom) anddelay on break(dob)to be usedwith bothForm
“C”relays.
FL-B101D40-RPM (d0073)_UL manual Page 11
Component Layout
IF05
RPM
INPUT MODULE
MAIN BOARD
Low-passFilterHeader
20kHz,2kHz,200Hz SignalTypeHeader
AC,mVordigitallogic
SensorHeader
Mag,Namur,Source,Sink
De-couplingHeader
20mHzhighpasslter
Low Voltage
Hi Voltage
COUPLING
INPUT SIGNAL FILTER
MAG
NAMUR
SOURCE
SINK
LOAD
AC
20KHz
2KHz
200Hz
OFF
DC
MAG/AC
LOGIC
GND
+24V
INPUT
High Accuracy Digital Measurement
NPN
Open Collector
Proximity Switch
Normally Pin 1 is at 24V
When sensor is activated Pin 1 goes to 0V
Using NPN Open Collector Proximity Switch 330B
IF05:
Universal Frequency / RPM
PleasegotoIF05inputmoduledatasheetformoredetail
https://www.texmate.com/media/pdf/2018/09/Texmate_IF05.pdf
FL-B101D40-RPM (d0073)_UL manual Page 13
Installation Guidelines
Installation
1.Installandwiremeterperlocalapplicablecodes/reg-
ulations,theparticularapplication,andgoodinstallation
practices.
2.Installmeter in alocationthat does notexceedthe
maximum operating temperature and that provides
goodaircirculation.
3. Separate input/output leads from power lines to
protect the meter from external noise.  Input/output
leads should be routed as far away as possible from
contactors,controlrelays,transformersandothernoisy
components.Shieldingcablesforinput/outputleadsis
recommended with shield connection to earth ground
nearthemeterpreferred.
4.A circuit breaker ordisconnectswitchisrequiredto
disconnect power to the meter.  The breaker/switch
shouldbeincloseproximitytothemeterandmarkedas
thedisconnectingdeviceforthemeterormetercircuit.
Thecircuitbreakerorwallswitchmustberatedforthe
appliedvoltage(e.g.,120VACor240VAC)andcurrent
appropriate for the electrical application (e.g., 15A or
20A).
5.SeeCase Dimensions sectionforpanelcutoutinfor-
mation.
6.SeeConnector Pinouts sectionforwiring.
7. Use 28-12 AWG wiring, minimum 90˚C (HH) tem-
perature rating.  Strip wire approximately 0.3 in. (7-8
mm).
8.Recommendedtorqueonallterminalplugscrewsis
4.5lb-in(0.51N-m).
!
Page 14 FL-B101D40-RPM(d0073)_UL manual
FL-B101D40-RPM
Add to the basic model number the order code suffix for each standard option required. The last suffix is to
indicate how many different special options and or accessories that you may require to be included with this product.
Ordering Example: FL-B101D40-RPM-VRR-PS1-IF05-OIC-R11-OA2 plus ZR and an OP-N4/144X36
Ordering Information
WARRANTY
Texmatewarrantsthatitsproductsarefreefromdefectsinmaterialandworkmanshipunder
normaluseandserviceforaperiodofoneyearfromdateofshipment.Texmate’sobligations
underthiswarrantyarelimitedtoreplacementorrepair,atitsoption,atitsfactory,ofanyof
theproductswhichshall,withintheapplicableperiodaftershipment,bereturnedtoTexmate’s
facility, transportation charges pre-paid, and which are, after examination, disclosed to the
satisfactionofTexmatetobethusdefective.Thewarrantyshallnotapplytoanyequipment
which shall have been repaired or altered, except by Texmate, or which shall have been
subjectedtomisuse,negligence,oraccident.InnocaseshallTexmate’sliabilityexceedthe
originalpurchaseprice. The aforementionedprovisions do not extendtheoriginal warranty
periodofanyproductwhichhasbeeneitherrepairedorreplacedbyTexmate.
USER’S RESPONSIBILITY
We are pleased to offer suggestions on the use of our various products either by way of
printedmatterorthroughdirectcontactwithoursales/applicationengineeringstaff.However,
sincewehavenocontrolovertheuseofourproductsoncetheyareshipped,NOWARRANTY
WHETHER OF MERCHANTABILITY, FITNESS FOR PURPOSE, OR OTHERWISE is made
beyondtherepair,replacement,orrefundofpurchasepriceatthesolediscretionofTexmate.
Usersshalldeterminethesuitabilityoftheproductfortheintendedapplicationbeforeusing,
and the users assume all risk and liability whatsoever in connection therewith, regardless
ofanyof oursuggestionsorstatementsastoapplicationor construction.Inno eventshall
Texmate’sliability,inlaworotherwise,beinexcessofthepurchasepriceoftheproduct.
Texmatecannot assumeresponsibilityforany circuitrydescribed. Nocircuitpatentor soft-
warelicensesareimplied.Texmatereservestherighttochangecircuitry,operatingsoftware,
specifications,andpriceswithoutnoticeatanytime.
BASIC MODEL NUMBER
FL-B101D40-RPM RPM,
101 Seg. Bargraph, 4 Digit ................
Standard Options for this Model Number
Order Code Suffix Description List
DISPLAY
VRR.....Red LED Bargraph w/4 Digit Red DPM, Vertical.......................N/C
VGG ....Green LED Bargraph w/4 Digit Green DPM, Vertical ......................
VGR ....Green LED Bargraph w/4 Digit Red DPM, Vertical ....................... $15
VRG ....Red LED Bargraph w/4 Digit Green DPM, Vertical ....................... $10
VTG.....Tri-Color Bargraph w/4 Digit Green DPM, Vertical ........................ $55
VTR .....Tri-Color Bargraph w/4 Digit Red DPM, Vertical .........................$45
HRR ....Red LED Bargraph w/4 Digit Red DPM, Horizontal ....................... $5
HGG ....Green LED Bargraph w/4 Digit Green DPM, Horizontal.................... $30
HGR ....Green LED Bargraph w/4 Digit Red DPM, Horizontal ..................... $20
HRG ....Red LED Bargraph w/4 Digit Green DPM, Horizontal ..................... $15
HTG ....Tri-Color Bargraph w/4 Digit Green DPM, Horizontal...................... $60
HTR.....Tri-Color Bargraph w/4 Digit Red DPM, Horizontal ....................... $50
DSGG ...Dual Scale Green LED Vertical Bargraph w/4 Digit Green DPM.............. $30
DSGR ...Dual Scale Green LED Vertical Bargraph w/4 Digit Red DPM ............... $20
DSRG ...Dual Scale Red LED Vertical Bargraph w/4 Digit Green DPM ............... $15
DSRR ...Dual Scale Red LED Vertical Bargraph w/4 Digit Red DPM................. $5
DSTG ...Dual Scale Tri-Color Vertical Bargraph w/4 Digit Green DPM................ $60
DSTR ...Dual Scale Tri-Color Vertical Bargraph w/4 Digit Red DPM .................$50
POWER SUPPLY
PS1 .....85-265VAC/95-300VDC ...........................................N/C
PS2 .....15-48VAC/10-72VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $35
INPUT MODULES
(Partial List. See www.texmate.com)
Unless otherwise specified Texmate will ship all modules precalibrated with factory pre-
selected ranges and/or scalings as shown in
BOLD
type.
IF05....Universal Frequency / RPM ............................... $40
ANALOG OUTPUT
OIC .....Isolated 16 Bit Current Output, 4-20mA ............................... $35
OIV .....Isolated 16 Bit Voltage Output, 0-10VDC ..............................$35
RELAY OUTPUT
R1 ......Single 4A Form A Relay ........................................... $37
R2 ......Dual 4A Form A Relays ............................................ $68
R11 .....Single 9A Form C Relay ........................................... $35
R12 .....Dual 9A Form C Relays ........................................... $70
R13 .....Dual 9A Form C & One 4A Form A Relays ............................. $100
R14 .....Dual 9A Form C & Dual 4A Form A Relays ............................. $130
R15 .....Single 9A Form C & Dual 4A Form A Relays ............................ $95
R16 .....Single 9A Form C & Single 4A Form A Relays........................... $65
Special Options and Accessories
Part Number Description List
SPECIAL OPTIONS
(Specify Inputs or Outputs & Req. Reading
)
ZR ............... Calibrated Range Change to another Standard Range ...........$20
ZS ............... Custom display scaling within standard ranges .................$24
ZS-AO............ Custom scaling of analog output ............................$60
ACCESSORIES
(Specify Serial # for Custom Artwork Installation)
75-DMC14436B ..... Side Slide Brackets-Wide opening (2 pc).................... $10
75-DMC144X36 ..... Side Slide Brackets-stand. (2 pc) - extra set ................. $10
93-PLUG2P-DP...... Extra Screw Terminal Conn., 2 Pin Power Plug ...............$3
93-PLUG2P-DR ..... Extra Screw Terminal Conn., 2 Pin Plug..................... $3
93-PLUG3P-DR ..... Extra Screw Terminal Conn., 3 Pin Plug..................... $5
93-PLUG4P-DR ..... Extra Screw Terminal Conn., 4 Pin Plug..................... $6
93-PLUG5P-DR ..... Extra Screw Terminal Conn., 5 Pin Plug..................... $7
OP-MTL144x36...... Metal Surround Case, includes screw mounting clips ..........$35
OP-MTLCLIP........
Screw Mounting Clips (2 pc) - to screw tighten slide brackets ........$10
OP-N4/144X36 . . . . . .
144x36mm clear lockable front cover-NEMA 4X, splash proof..........$35
OP-PA/144X36 ...... Panel Adapter for 144x36mm from 6 inch cutout .............$15
For Custom Face Plates and Scales see page 14.
Prices subject to change without notice.
1934KelloggAve.,Carlsbad,CA92008
Tel:1-760-598-9899•USA1-800-839-6283•1-800-TEXMATE
Fax:1-760-598-9828•Email:[email protected]•Web:www.texmate.com
FL-B01Q-RPM Technical Manual Copyright © 2019 Texmate Inc. All rights
reserved. Published by: Texmate Inc. USA. Information in this Technical Manual
is subject to change without notice due to correction or enhancement. The
information described in this manual is proprietary to Texmate, Inc. and may
not be copied, reproduced or transmitted, in whole or in part, in connection with
the design, manufacture, or sale of apparatus, device or private label product
without the express written consent of Texmate, Inc.
POWER SUPPLY INPUT MODULES ANALOG OUTPUT RELAY OUTPUT
OA____
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13

Texmate FL-B101D40-RPM Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI