MGE UPS Systems EX RT CLA User manual

Type
User manual
Charger Module
EX RT CLA
Installation and User Manual
86-86000-04 A0
www.mgeups.com
Standard Features
EX RT CLA Module is a long
back-up charger to be used
with a power module and
external power battery
cabinet.
CLA Module (Long backup time charger)
(Part number 86004)
Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA module.
IMPORTANT The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.
Battery backup time chart.
Battery Backup Time Recommended Batteries
EX 5 RT EX 7 RT EX 11 RT
2 hours 50 Ah 65 Ah 100 Ah
4 hours 100 Ah 130 Ah 200 Ah
8 hours 200 Ah 200 Ah 400 Ah
Total battery voltage : 240 V DC (20 x 12V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization sect
STEP 1 EX RT CLA Module Unpacking and Parts Check
EX RT CLA Module
EX RT CLA Module Installation2 86-86000-04 AO
EX RT CLA Module
Installation and
User Manual
Power Cable
EX RT CLA Module Box Contents
Tower Stand Expanders
Battery Detection Cable
Stabilizer Bracket
(4 screws included)
Installation and User Manual
STEP 2 EX RT CLA Module Tower Configurations
EX RT CLA Module Installation 386-86000-04 AO
Follow the numerical sequence to assemble the
footer supports as shown here with optional transformer.
ww
w
.
m
ge
ups
.
c
o
m
w
ww
.m
g
eu
p
s
.
c
o
m
O
F
F
O
N
1
1
2
2
5
4
4
4
4
3
3
Power Module
CLA Module
EX RT
CLA
EX
1
1 RT
EX RT CLA Module
4 86-86000-04 AO
STEP 3 EX RT CLA Module Rack Configuration (Requires optional Rail Kits 86001, 86002. See
System Installation and User Manual for details.)
EX RT CLA Module Installation
3. Install Front Mounting Brackets
to each side of the CLA Module.
3
2
1
1
1
1
4
4
3
2. Attach rails together
with provided wing nuts.
1. Attach both rails to rear and front
of rack chassis with supplied screws.
4. Use caution when sliding unit into rack mount,
secure unit to rack with supplied screws.
(For this step, it is possible to adjust the position
of both front mounting brackets.)
B. Rack Installation
w
w
w
.
m
g
e
u
p
s
.
c
o
m
E
X
1
1
R
T
O
F
F
O
N
E
X
1
1
R
T
O
F
F
O
N
w
w
w
.m
g
e
u
ps
.
c
o
m
w
w
w
.
m
ge
u
ps
.
c
o
m
E
X
1
1
R
T
O
F
F
O
N
E
X
1
1
R
T
O
FF
O
N
w
w
w
.
m
g
e
u
p
s
.
c
o
m
1
2
3
FINISHED PANEL
(rack orientation)
1
2
3
A. Prepare the front panel logo and LCD display for rack orientation,
Apply to all modules. Power Module shown.
Stack-up sequence in Rack configuration
ww
w
.
m
g
e
u
p
s
.
c
o
m
O
F
F
O
N
E
X
1
1
R
T
w
w
w
.
m
g
e
u
p
s
.
c
o
m
E
X
R
T
T
r
a
n
s
f
o
r
m
e
r
2. POWER MODULE
(bottom, EX 5/7/11 RT)
1. EX RT CLA MODULE
(Top, EX 5/7/11 RT)
Installation and User Manual
STEP 4 EX RT CLA Module Connections
EX RT CLA Module Installation 586-86000-04 AO
CLA
EX 5RT /
EX 7RT /
EX 11RT
~
5
0A
(cable not included)
Typical High Power
Battery Cabinet
(not included)
Utility
AC Source
(cable not included)
(see section 2.12 in EX 5/7/11 RT
Installation and user manual for cable
connection information)
A. System Connections with Battery Cabinet
See System Installation and User Manual for initial start-up procedures.
1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636
www.mgeups.com
Contact MGE
United States
MGE UPS SYSTEMS
1660 Scenic Ave.
Costa Mesa, CA 92626
Tel: (714) 557-1636
(800) 523-0142
Fax: (714) 557-9788
www: mgeups.com
Canada
MGE UPS SYSTEMS
#9, 2789 Thamesgate Drive
Mississauga, ON L4T 4E8
Tel: (905) 672-0990
(877) 672-0990
Fax: (905) 672-7667
www: mgeups.com
Latin America and
Other International
MGE UPS SYSTEMS
1660 Scenic Ave.
Costa Mesa, CA 92626
Tel: (714) 513-7831
(800) 523-0142 ext. 7831
Fax: (714) 434-0199
www: mgeups.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

MGE UPS Systems EX RT CLA User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI