Tripp Lite BP240V1037C-1PH Owner's manual

Category
UPS batteries
Type
Owner's manual
1
Table of Contenets
1. Introduction 2
2. Important Safety Instructions 3
3. Battery Cabinet Installation 5
3.1 Preparation 5
3.2 Transportation 5
3.3 Mechanical Check 5
3.4 Internal Wiring (Typical) 6
3.5 Preliminary Electrical Check 6
3.6 Battery Cabinet Placement 6
3.7 Electrical Connection 7
3.8 Battery Charger Electrical Connection (Select Models) 7
3.9 Final Electrical Check 7
3.10 Daisy-Chaining Multiple Battery Cabinets 8
4. Operation and Charging 9
4.1 Determine Charging Voltages 9
4.2 Initial Charge 9
4.3 Operational Check 9
4.4 Acceptance Test (Optional) 9
5. Maintenance 10
5.1 Maintenance Schedule 10
5.2 Fuse Replacement 10
6. Diagrams 11
6.1 Battery Cabinet Diagram (3 Shelves) 11
6.2 Battery and Breaker Diagrams 12
6.3 Integrated Battery Charger (Select Models) 13
7. Specifications 14
7.1 Dimensions and Floor Loading 14
7.2 Recommended Torque 14
8. Storage and Service 15
9. Warranty 15
Owner’s Manual
Extended-Run Single-Phase
Battery Cabinet
Not suitable for mobile applications.
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
Warranty
Registration:
register online today for a
chance to win a FREE Tripp Lite
product—www.tripplite.com/warranty
2
1. Introduction
Tripp Lite’s Extended-Run Single-Phase Battery Cabinets connect to SmartOnline 3-Phase UPS Systems to provide long-lasting battery
backup for data centers, telecommunications, networks, industrial facilities, security, emergency systems and other mission-critical
applications that require high capacity, high availability and extended runtime.
Features
• Battery cabinets are available in voltages from 192 VDC through 240 VDC and capacities from 33 to 720 ampere-hours with a
constant power rating of up to 595 kW @ 15-minute rate.
• Battery cabinets contain multiple 6 or 12 VDC batteries connected in series for higher voltages or in series-parallel for higher voltages
and capacities. Multiple battery cabinets may be connected in series for increased runtime.
• Depending on the number of individual batteries contained, each battery cabinet will have 3 tiers with 8 to 10 individual batteries
(maximum) per tier.
• The battery cabinet structure is rated up through Seismic Zone 4 applications in compliance with the Uniform Building Code.
Removable access panels facilitate periodic maintenance. There is a minimum of 6 inches of clearance above the individual batteries
for access to terminals.
• Battery cabinet frame and rails are 10 gauge steel; exterior panels are 16 gauge steel. Baked powder coat finish provides chip and
corrosion resistance.
• Battery cabinet is shipped bolted to pallet with a double layer of protective stretch wrap and integrated corner and top protection.
• Appropriate ventilation and convection cooling of the individual batteries is provided via ½-inch spacing between batteries. Front and
rear vents allow the free flow of warmer air out of the battery cabinet.
• The internal battery series or series-parallel circuits are completely wired. The negative leg of each series string of batteries terminates
into an insulated terminal block.
• An optional molded case circuit breaker is available for over-current protection. (The molded case circuit breaker can be fitted with a
UV relay, shunt trip and auxiliary contacts as additional options.)
• User-supplied power output cables can be fed into the battery cabinet through built-in 8-inch conduit knockouts in the top or sides of
the cabinet (gland plate included). Shorting bars provide a positive landing power connection for parallel strings in a single cabinet.
All available power connection points are at the top of the cabinet, above the topmost tier of batteries.
• For improved safety, higher power density and minimized maintenance, the cabinet systems use Valve-Regulated Lead-Acid (VRLA)
recombinant batteries. The electrolyte in these batteries is immobilized in either an absorbent mat separator or a gelling medium,
eliminating the spilling hazards and maintenance requirements of free liquid electrolyte. There is no need to add water or measure
specific gravity.
• Because the batteries are recombinant cells that employ an oxygen recombination cycle, minimal gasses are emitted during normal
float charging. Each cell contains an individual valve which releases the gas products of overcharge and prevents pressure build-up
within the cell.
• Select battery cabinets (“C” models) include an integrated battery charger.
3
2. Important Safety Instructions
SAVE THESE INSTRUCTIONS
All sections of this manual contain instructions and warnings that must be followed during the installation and operation of the
battery cabinet described in this manual. Read ALL instructions thoroughly before attempting to move, install or connect your battery
cabinet. Failure to comply may invalidate the warranty and cause serious property damage and/or personal injury.
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual
and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and
property damage.
Installation and Location Warnings
• Install the battery cabinet in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and
gasses, conductive contaminants, dust and direct sunlight.
• Install the battery cabinet in a level, structurally sound location.
• The battery cabinet is extremely heavy; be extremely careful when moving or lifting the unit.
• Operate the battery cabinet at indoor temperatures between 32° F and 104° F (0° C and 40° C) only. For best results, maintain an
indoor temperature of 77° F (25° C).
• Leave adequate space around all sides of the battery cabinet for proper ventilation. Do not block, cover or insert objects into the
external ventilation openings of the battery cabinet.
• Do not place any object on the battery cabinet, especially containers of liquid.
• Do not attempt to stack the battery cabinet. Attempting to stack the battery cabinet may cause permanent damage and create a
potential for serious personal injury.
• Do not attempt to unpack or move the battery cabinet without assistance. Use appropriate handling equipment rated to bear the
weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread forks
to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.)
• For emergency use, install a fire extinguisher rated for energized electrical equipment fires (Class C rating or exact equivalent, with a
non-conductive extinguishing agent) near the battery cabinet.
Connection Warnings
• The battery cabinet contains hazardous high voltages that have the potential to cause personal injury or death from electric shock.
• The battery cabinet has its own energy source. The output terminals may be live even when the battery cabinet is not connected to a
UPS system.
• The battery cabinet must be suitably grounded according to all applicable electrical wiring regulations.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of
the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
• De-energize all input and output power sources before installing cables or making electrical connections.
• Use flexible cable of sufficient length to permit battery cabinet servicing.
• Use ferrule caps to cover termination cables and prevent frayed ends from shorting on terminal blocks. Use cabling rated VW-1, FT-1
or better. Use cable sleeves and connector clamps.
• Confirm that all cables are marked correctly according to their purpose, polarity and diameter.
• Observe proper polarity by connecting negative to negative and positive to positive. Failure to observe proper polarity may damage the
batteries and create a serious risk of personal injury and property damage.
• Wiring should be performed by trained, qualified electricians only.
• If the battery cabinet does not include the shunt trip option, the final installation must include an easy-access disconnect device
between the battery and the load. The disconnect device must be suitably rated in accordance with applicable electrical codes and
the battery cabinet rating.
• Do not connect the integrated battery charger (included with “C” models only) to the UPS system output. The integrated
battery charger requires a separate AC supply circuit.
4
2. Important Safety Instructions (continued)
Battery Warnings
• The battery cabinet does not require routine maintenance by the user. There are no user-serviceable parts inside. Only qualified,
knowledgeable service personnel familiar with all required precautions should open the access panels for any reason. Keep
unauthorized personnel away from batteries.
• The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries. Do not attempt to add water to these batteries
or sample the electrolyte specific gravity.
• Valve-regulated recombinant lead-acid (VRLA) batteries can contain an explosive mixture of hydrogen gas. DO NOT SMOKE when near
batteries. DO NOT cause flames or sparks near batteries. Discharge static electricity from body before touching batteries. DO NOT
open or mutilate batteries—released electrolyte is harmful to the skin and eyes and may be toxic. DO NOT dispose of batteries in a
fire—they may explode.
• Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be
performed only by qualified service personnel, observing proper precautions. Use tools with insulated handles. Remove watches, rings
or other metal objects. Wear rubber gloves and boots. Do not short or bridge the battery terminals with any object. Do not lay tools or
metal parts on top of batteries.
• Replace batteries with equivalent batteries (same number and type) available from Tripp Lite.
• The batteries are recyclable. Refer to local codes for disposal requirements. Do not dispose of batteries except through approved
channels in accordance with all applicable local, state and national regulations.
• Fuses should be replaced by qualified service personnel only. Blown fuses must be replaced with the same number and type of fuses.
• Do not connect or disconnect batteries when the UPS system is operating from the battery supply or when the unit is not in bypass
mode. Disconnect the charging source prior to connection or disconnecting battery terminals.
• If the charging source remains off for an extended period of time, it should be turned on periodically to allow the batteries to
recharge. The charging source should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period
every 3 months. Failure to recharge the batteries periodically may cause permanent battery damage.
• Allow batteries to charge uninterrupted for 24 hours after installation.
• Do not attempt to service the integrated battery charger (included with “C” models only). Contact Tripp Lite if service is required.
Note on Labeling
These symbols may appear on the product label:
V~ AC Voltage
V DC Voltage
Ground
+ Battery Positive
- Battery Negative
Refer to the product label for model numbers, voltage ratings
and other important information.
5
3. Battery Cabinet Installation
Read Section 2 – Important Safety Instructions Before Installation
3.1 Preparation
1. At your site, prepare to off-load the battery cabinet from the delivery truck and transport it to the final installation location. Consider
both the packaged weight and dimensions.
2. Assure that the floor can bear the load of the specific battery cabinet being installed. The battery cabinet must be installed in a
structurally sound area with a level floor that is able to bear the weight of the battery cabinet and other equipment that will be
installed nearby.
3. Draw a wiring schematic representing the cables connected between the battery cabinet’s output terminal blocks and any external
disconnect device, junction box and/or load/rectifier.
4. If you plan to store the battery cabinet for an extended period before or after installation, follow the instructions in
Section 8 – Storage and Service.
3.2 Transportation
1. Inspect the shipping container(s) for visible damage. (Do not remove the stretch wrap around the unit until it has been transported
to the final installation location.) Confirm that the model name and rating match the unit you ordered. If you determine that the unit
has been damaged during shipping, or if anything appears to be missing, contact Tripp Lite for assistance. Do not attempt to use the
unit if it has been damaged or mishandled.
2. Do not attempt to move or unpack the battery cabinet without assistance. Use appropriate handling equipment rated to bear the
weight and bulk of the battery cabinet, such as freight elevators, pallet jacks and forklifts. (Fully extend forks under load. Spread
forks to maximum possible width under load. Lift cabinet from bottom only. Wear safety shoes.) Confirm that load limits for freight
elevators, handling equipment and floors along the transport route will not be exceeded by the combined weight of the packaged
battery cabinet, handling equipment and personnel. Confirm that the packaged unit will pass through any doorways along the
intended route.
3. The battery cabinet is secured with stretch wrap to protect it during shipping and movement within a facility. Remove the stretch
wrap from the battery cabinet when the unit is in the final installation location—not before.
3.3 Mechanical Check
While the assembled cabinet battery system is still on the shipping pallet, inspect all sides for impact or other damage.
1. Remove front access panels and set them aside, being careful not to scratch the finish.
2. Confirm that all individual batteries are secure in the battery cabinet and that no batteries have been damaged.
3. Confirm that none of the internal parts (terminal blocks, fuse blocks, fuses, circuit breakers and other parts) have been damaged.
4. If the battery cabinet includes an integrated battery charger (“C” models only), examine the wires at the DC output terminal closely.
If any of the leads are bent or otherwise damaged from shipping, contact Tripp Lite. Damaged leads could cause a battery short
circuit.
5. Note the individual battery model number and refer to Section 7-2 for the battery’s terminal type and recommended torque.
6. Use insulated tools to tighten all the battery terminal connections to the recommended torque.
7. Use insulated tools to tighten the cables from the positive and negative output terminals at the end batteries to the output terminal
block, fuse block or circuit breaker.
6
3. Battery Cabinet Installation (continued)
3.4 Internal Wiring (Typical)
• Battery cabinets use multiple 12 VDC batteries connected in series to provide nominal DC voltages ranging from 192 VDC to 240
VDC.
• Internal cabling is sized for specific application load currents. The insulated cables can be 2 AWG, 4 AWG, 2/0 AWG, 4/0 AWG or dual
2/0 AWG.
• Each battery cabinet includes a specific wiring diagram. Some battery cabinets may contain series-parallel battery strings. Others
may require a single series string that occupies more than one cabinet. The installer must complete the series connections between
separate cabinets when the series string occupies more than one cabinet. The cables, hardware and instructions required to
complete the connection will be inside one of the cabinets.
• Battery cabinets that include a molded case circuit breaker may or may not use a fuse.
• All fuses, disconnect switches and circuit breakers are in the top tier of the battery cabinet.
• Terminal blocks, copper bussing or direct circuit breaker connections for connecting to the load are in the top tier of the battery
cabinet.
• All load connection polarities will be marked by a POS (+) or NEG (-) label.
• Some battery cabinets are provided with a two-pole branch circuit overcurrent protection device. These cabinets may be wired directly
to the load or UPS.
• Some battery cabinets are not provided with branch circuit overcurrent protection. The installer must supply an easy-access
disconnect and branch circuit overcurrent protection device rated in accordance with all applicable electrical codes. WARNING: To
reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection rated in accordance
with the National Electrical Code (NEC), ANSI/NFPA 70.
• If the battery cabinet includes an integrated battery charger (“C” models only), the internal cabinet wiring will be preinstalled and
the charger will include fusing for 120 VAC input. The charger input must be connected to a separate AC supply circuit, not the UPS
system.
3.5 Preliminary Electrical Check
1. Measure the battery cabinet output voltage at the output load connection points. (Measure voltage with a digital voltmeter.)
2. The measured voltage should approximately match the voltage listed on the battery cabinet nameplate. The battery cabinet output
voltage will be equal to the number of individual batteries installed in series multiplied by the unit voltage. (For example: 40 batteries
x 12.84 VDC = 513.6 VDC output; 40 batteries x 6.42 VDC = 256.8 VDC output.)
3. If the measured voltage is significantly different than anticipated, determine the cause (e.g. low charge, shorted cell, reversed
battery, faulty wiring) and correct the voltage disparity before proceeding.
3.6 Battery Cabinet Placement
Place the battery cabinet in a cool location with free airflow that is away from direct heat sources. The lifespan of a battery can be
affected dramatically by elevated temperature, decreasing 50% for each 15° above 77° F.
1. Prepare the surface where the cabinet will be placed. The surface must be clean, flat and able to support the battery cabinet and
other equipment installed nearby. (See Section 7-1 for floor loading specifications.)
2. Allow adequate clearance around the battery cabinet for ventilation and maintenance. The front panel must be accessible and
removable to allow easy access to internal batteries, internal fuses and other overcurrent protection devices. (See Section 7-1 for
dimensions. See Section 6-1 or 6-2 for detailed battery cabinet measurements.)
3. If the cabinet will be anchored to the floor, install appropriate anchor bolts in the mounting hole at the bottom of the cabinet. Use
washers to create a level surface between the mounting areas around the anchor bolts.
4. Using extreme caution, remove the bolts securing the battery cabinet to the shipping pallet.
5. Forklift forks should be at maximum width within the cabinet clearance opening and fully inserted to prevent tipping. Lift cabinet from
bottom only. Be careful not to damage the sheet metal floor of the cabinet with the forks.
6. If the battery cabinet will be secured to the floor, carefully align and lower the battery cabinet down on the floor anchor bolts and
secure it in place.
7. If the cabinet will not be secured to the floor, lower it into the designated space and then level it using shims. (Leveling does not
affect performance but does align the battery cabinet with other equipment in the facility.)
7
3. Battery Cabinet Installation (continued)
3.7 Electrical Connection
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual and
all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property
damage.
• The battery cabinet should be connected to the load through a DC disconnect switch or a DC circuit breaker. This allows the battery to
be disconnected from the load and charger for maintenance and/or repair.
• The DC rated fuses and DC molded case circuit breakers are UL-listed for branch circuit protection. If replacement is required, UL-
listed components with the same voltage and current rating must be used.
• The size of the load connection cables must consider maximum allowable voltage drop as well as the cables’ continuous ampere
capacity and anticipated ampere discharge rate of the individual battery cabinet. A maximum voltage drop of 1.5 VDC in the load
connection cables is recommended.
• Refer to all applicable local, state and national codes (including NEC) for appropriate cable size and ratings.
• External circuit protection devices (fuses or circuit breakers) must consider the discharge rate of the battery, the wiring to be
protected and the DC short circuit current of the battery.
• When the battery cabinets are connected in parallel, they should be joined together with separate output cables of equal total length
at a junction box or other suitable distribution panel.
• If the battery cabinet includes an integrated battery charger (“C” models only), the charger input must be connected to an AC supply
circuit separate from the UPS system.
1. Remove the battery cabinet’s access panels to access internal components. Use a digital voltmeter when voltage measurements are
required.
2. Determine if the battery has been inadvertently grounded by measuring the voltage between the battery cabinet grounding lug and
the positive load connection point within the cabinet. This voltage should measure 0 (zero) VDC. If the measured voltage is not zero,
determine the cause and correct before proceeding.
3. Place the internal circuit breaker in an open position during the connection of the output cables to prevent damage if the cables are
accidentally shorted.
4. The top and sides of the battery cabinet include knockouts for load connection cable entry. Punch out the appropriate knockout and
connect the conduit or cable bushing.
5. The output terminal blocks, fuse blocks, disconnect switches and circuit breakers will accommodate cables up to 500 MCM
(500 kcmil).
6. Feed the positive and negative cable from the open external disconnect switch through the conduit/cable bushing and connect to
the respective output terminals inside the battery cabinet.
7. Reinstall any internal cabinet fuses that were removed in step 2 (above). All disconnect switches or circuit breakers must remain in
the open position during reinstallation of the fuses.
8. Connect an appropriate equipment grounding cable to the grounding lug mounted in the top of the battery cabinet or to the
grounding pad on the rear leg of the battery cabinet.
3.8 Battery Charger Electrical Connection (Select Models)
1. Select battery cabinets (“C” models only) include an integrated battery charger. The charger includes fusing for 120 VAC input.
Refer to Section 6-5 for a terminal block diagram and additional battery charger information.
2. Set the battery cabinet input voltage to 120 VAC by jumpering these terminals: 2 and 3, 3 and 4, 5 and 6.
3. Connect charger terminals 7 and 8 to a 30-amp, 120 VAC, 60 Hz power source. WARNING: Do not connect the battery charger
to the UPS system output. The battery charger requires a separate AC supply circuit.
3.9 Final Electrical Check
Before closing any connecting circuit breaker or disconnect switch, complete these verification steps:
1. Verify that the battery cabinet output voltage is correct.
2. If battery cabinets will be operated in parallel, verify that the individual system output voltages match within 2 VDC.
3. Verify that the voltage measured between either output terminal and the battery cabinet ground is zero.
4. If any of the above verification steps shows an irregularity, determine and correct the cause before proceeding.
8
Figure 3.10a
Figure 3.10b
Figure 3.10c
3. Battery Cabinet Installation (continued)
3.10 Daisy-Chaining Multiple Battery Cabinets
Additional battery strings can be daisy-chained to the UPS internal battery system via a unique connector inside the UPS battery
compartment (Figure 3.10a).
A 15-ft. BP240EXTNDR15DL cable is required to connect the first battery cabinet to the UPS system (Figure 3.10b). Cabling for all
additional built-to-order cabinet installations is the sole responsibility of the electrician performing the installation.
To connect the cable to the UPS, remove the cover plate (Figure
3.10c) and insert the Delta connector into the slot until it is
seated firmly. After removing the cover plate, run the ring terminal
ends through the opening and connect to the breaker (see
Section 6.2). Make sure to use the correct electrician-provided
strain relief at the cover plate.
WARNING: When connecting to the breaker, make sure that
youu maintain proper polarity (positive to positive, etc.).
Failure to do so may result in damage to your UPS and will
void your warranty claim.
Battery
Connection
Battery
Connection
Front of
Cabinet
Conduit
Knockouts
9
4. Operation and Charging
4.1 Determine Charging Voltages
To determine the appropriate equalization (freshening) charge voltage and float charge voltage, multiply the number of batteries
connected in series in the battery cabinet by the recommended charging voltage per unit.
For example:
A +/- 240 VDC cabinet containing 40 each of the UPS12-400MR batteries in series would use the following charging voltages:
Freshening/Equalization Charge Voltage = 20 x 14.4 VDC/unit average= +/- 288 VDC
Float Charge Voltage = 20 x (13.5 to 13.8 VDC/unit average) = +/- 270 to 276 VDC
Note: Some battery cabinets may contain more than one series string connected in parallel within the cabinet. The calculation for
properly charging the battery cabinet should follow the procedure above, considering the number of batteries in a single series string.
4.2 Initial Charge
After the correct charging voltages have been calculated, follow these steps:
1. Adjust the charger/rectifier equalization and float voltage outputs to the appropriate level.
2. Place the charger/rectifier in equalization mode,
3. Close the disconnect switch/circuit breaker connection from the charger/rectifier to the battery cabinet(s) and start a 24-hour
freshening charge at the equalization charge.
4. After a few minutes on charge, monitor the voltage across several of the individual batteries to assure they are charging at the
proper value.
5. Following completion of the freshening charge, place the charger/rectifier in float charge mode.
6. After the battery cabinet has been on float for 1 to 24 hours, complete the operational check (Section 4-3).
4.3 Operational Check
1. Measure and record the total system float voltage. Measure at the battery terminals.
2. Measure and record the system float current using a clamp-on ammeter.
3. Measure and record the float voltage of individual battery units.
4. Measure and record the temperature of several of the batteries. (Measure battery temperature with a digital thermometer by placing
the surface thermocouple on the flat surface of the negative terminal—not the “L” connection surface. An infrared temperature
monitor can also be used.)
5. Optional: Perform impedance and conductance tests on individual battery units. These tests require special equipment, but the
data can be useful in trending the system over time or identifying suspect units during later periodic checks. It may be necessary to
disconnect the battery system from the charger/load during these checks.
6. If the acceptance test is being performed, proceed to Section 4-4. If the acceptance test is not being performed, reinstall the
cabinet’s access panels. The battery cabinet is now in operation
4.4 Acceptance Test (Optional)
1. Remove the battery cabinet’s access panels to access internal components. Use a digital voltmeter when voltage measurements are
required.
2. Determine the discharge rate (e.g. 15 seconds, 5 minutes, 15 minutes) at which the battery is to be tested.
3. Select a battery from the center of the battery cabinet and measure the temperature at the flat surface of the negative terminal. If
the temperature is below 74° F or above 80° F, the test load should be temperature compensated accordingly.
4. Review the final check data and assure that all unit float voltages are acceptable.
5. During the acceptance discharge test, monitor the cabinet system output voltage at the cabinet, the output current and discharge
time as a back-up to monitoring at the critical load.
6. Run the test in accordance with the IEEE standard.
7. Reinstall the cabinet’s access panels. The battery cabinet is now in operation.
10
The battery cabinet contains valve-regulated recombinant lead-acid (VRLA) batteries, which are maintenance-free relative to the
electrolyte. You cannot add water to these batteries or sample the electrolyte specific gravity. It is necessary, however, to periodically
check the charging voltage, temperature and connections of the individual battery units.
5.1 Maintenance Schedule
Quarterly Check
1. Measure individual battery unit temperature. (Measure with a digital thermometer by placing the surface thermocouple on the flat
surface of the negative terminal—not the “L” connection surface. An infrared temperature monitor can also be used. Temperatures
below 77° F reduce battery performance and temperatures above 77° F reduce battery lifespan. Battery lifespan is reduced by 50%
for each 15° above 77° F. For example, battery lifespan will be reduced by half at 92° F.)
2. Measure individual battery unit float charging voltages. (Measure voltage with a digital voltmeter. Measured voltage should be
between 13.2 VDC and 14.2 VDC. Battery units outside this range should be replaced.)
3. Measure total battery cabinet float charging voltage.
Semiannual Check
1. Repeat quarterly check.
2. (Optional) Measure impedance or conductance of individual battery units.
3. (Optional) Perform a high-rate, 100 A, 10 second performance capacity test of individual battery units. (The performance capacity
test is identical to the acceptance test in Section 4-4, and the same procedure should be followed.)
Annual Check
1. Repeat semiannual check.
2. Use insulated tools to tighten all connections to the recommended torque. (See Section 7-2 for recommended torque values.)
3. (Optional) Measure inter-battery connection resistance.
5.2 Fuse Replacement
WARNING: Fuses should be replaced by qualified service personnel only. Blown fuses must be replaced with the same
number and type of fuses.
1. The battery cabinet may contain a UL-listed, branch-rated fuse in the positive output (upper front of cabinet).
2. Before attempting to replace the fuse, open the disconnect between the battery cabinet and the load/charger.
3. Remove the front panel from the battery cabinet. Before attempting to replace the fuse, confirm that the battery is not shorted to
the cabinet. Use a digital voltmeter to measure the voltage between the cabinet and both sides of the fuse holder. This voltage
should measure 0 (zero) VDC. If the measured voltage is not zero, determine the cause and correct before proceeding.
4. Wearing rubber gloves and using insulated tools, remove any cables and/or terminal plates from the output side of the fuse holder.
Using the appropriate hex socket, remove the fuse from the holder.
5. The replacement fuse must have the same voltage and current rating as the fuse being replaced (check the label on the fuse being
replaced).
6. For nominal battery cabinet voltages less than or equal to 384 VDC, use fuses rated at 500 VDC. For nominal battery cabinet
voltages greater than 384 VDC, use fuses rated at 700 VDC.
7. Install the replacement fuse and reconnect the output cables and/or terminal plates to the output side of the fuse holder.
8. Reinstall the battery cabinet front panel and close the disconnect between the battery cabinet and the load/charger.
5. Maintenance
11
Note: All dimensions are in inches.
6. Diagrams
6.1 Battery Cabinet Diagram (3 Shelves)
28.80
6.00
32.4
6.00
Battery
Charger
Battery
Charger
3.25
4.50
4.50
Battery
Charger
4.00
3.50
10.58
13.50
14.50
29.00
13.50
13.50
15.40
60.00
15.75
2.25
8.25
11.00
16.00
AC Input for
Battery Charger
Breaker
Mounting
Plate
12
6. Diagrams (continued)
6.2 Battery and Breaker Diagrams
240 VDC Battery Diagram 192 VDC Battery Diagram 192/240 VDC Breaker Diagram
Notes
• All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.
• Terminal block is UL-recognized and rated for 600 VDC.
• Breaker is UL-listed and rated for 100 A, 600 VDC, 25 KAIC.
• Cabinets with breakers are shipped with the breaker in the off/open position.
• Battery arrangements shown are typical but may vary depending on cabinet and battery type.
Shelf #2
Shelf #2
Shelf #3
Shelf #1 (Bottom)
Shelf #1 (Bottom)
To UPS Positive
To UPS Negative
AC Input for
Battery Charger
To Fuse or Breaker Termination
To Fuse or Breaker Termination
Battery
Positive
Battery
Negative
UL Listed Breaker
Shelf #2
Shelf #2
Shelf #3
Shelf #1 (Bottom)
Shelf #1 (Bottom)
To UPS Positive
To UPS Negative
AC Input for
Battery Charger
To Fuse or Breaker Termination
To Fuse or Breaker Termination
Battery
Positive
Battery
Negative
UL Listed Breaker
Shelf #2
Shelf #2
Shelf #3
Shelf #1 (Bottom)
Shelf #1 (Bottom)
To UPS Positive
To UPS Negative
AC Input for
Battery Charger
To Fuse or Breaker Termination
To Fuse or Breaker Termination
Battery
Positive
Battery
Negative
UL Listed Breaker
13
6. Diagrams (continued)
6.3 Integrated Battery Charger (Select Models)
Notes:
• All dimensions are in inches.
• AC input is preset with fuses for 120V 30 A, but can be rewired for 208 and 240 VAC, 60 Hz by a qualified electrician.
• Constant voltage output.
• Electronic current limiting and high voltage shutdown.
• Temperature compensation with remote battery temperature sensor.
• Auxiliary output circuit for “Charger OK” indicator.
AC
0.5
12.5
13.5
6.25
MAX
Input
WARNING: Do not connect the battery charger
AC input to the UPS system output. The battery
charger requires a separate AC supply circuit.
L N
120 VAC
Output
– +
Output
Input Voltage Selection
For 120 VAC Jumper:
2 & 3, 3 & 4, 5 & 6
For 208 VAC Jumper:
1 & 2, 4 & 5
For 240 VAC Jumper:
2 & 3, 4 & 5
14
7. Specifications
7.1 Dimensions and Floor Loading
Battery Cabinet Model Shelves
Dimensions
(Width x Depth x Height)
Weight Floor Loading
BP240V557C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1250 lb
(567.5 kg)
193 lb/ft
2
(943 kg/m
2
)
BP240V787C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1850 lb
(840 kg)
285 lb/ft
2
(1395 kg/m
2
)
BP240V1037C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1983 lb
(900.3 kg)
306 lb/ft
2
(1496 kg/m
2
)
BP240V1407C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
2463 lb
(1118.2 kg)
380 lb/ft
2
(1857 kg/m
2
)
BP192V557C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1130 lb
(513 kg)
174 lb/ft
2
(852 kg/m
2
)
BP192V787C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1628 lb
(739.1 kg)
251 lb/ft
2
(1228 kg/m
2
)
BP192V1037C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1773 lb
(804.9 kg)
274 lb/ft
2
(1337 kg/m
2
)
BP192V1407C-1PH 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
2070 lb
(939.8 kg)
319 lb/ft
2
(1561 kg/m
2
)
BP192V557C-16K 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1130 lb
(513 kg)
174 lb/ft
2
(852 kg/m
2
)
BP192V787C-16K 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1628 lb
(739.1 kg)
251 lb/ft
2
(1228 kg/m
2
)
BP192V1037C-16K 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1773 lb
(804.9 kg)
274 lb/ft
2
(1337 kg/m
2
)
BP192V1407C-16K 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
2070 lb
(939.8 kg)
319 lb/ft
2
(1561 kg/m
2
)
BP240V787C-1PHX 3
32.4 x 28.8 x 60 inches
(82.3 x 73.2 x 152.4 cm)
1850 lb
(840 kg)
285 lb/ft
2
(1395 kg/m
2
)
7.2 Recommended Torque
Battery Cabinet Model Terminal Type Torque
BP240V557C-1PH 10-32 Threaded Insert 25 in·lb (2.8 N·m)
BP240V787C-1PH 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP240V1037C-1PH 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP240V1407C-1PH 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP192V557C-1PH 10-32 Threaded Insert 25 in·lb (2.8 N·m)
BP192V787C-1PH 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP192V1037C-1PH 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP192V1407C-1PH 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP192V557C-16K 10-32 Threaded Insert 25 in·lb (2.8 N·m)
BP192V787C-16K 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP192V1037C-16K 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP192V1407C-16K 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
BP240V787C-1PHX 1/4-20 Threaded Insert 110 in·lb (12.4 N·m)
15
Storage
The battery cabinet must be stored in a clean, secure environment with a temperature less than 40° C (104° F) and a relative humidity
less than 90% (non-condensing). Store the battery cabinet in its original shipping container if possible. Charge the batteries for at least
24 hours prior to use. Do not rely on the battery cabinet to provide backup power to connected equipment until the batteries are fully
charged. Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to
recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every
3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
Service
The battery cabinet is covered by the limited warranty described in this manual. Site survey service programs, start-up service programs,
preventative maintenance service programs and on-site warranty options (2, 3 or 4 years) are also available. For more information, call
Tripp Lite Customer Service at +1.773.869.1234.
Limited Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a
period of 1 year from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair
or replace the product, in its sole discretion. Service under this Warranty includes parts and Tripp Lite service center labor. On-site service plans are
available from Tripp Lite through authorized service partners (in most areas). Contact Tripp Lite Customer Service at +1.773.869.1234 for details.
International customers should contact Tripp Lite support at [email protected].
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO
EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL
IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET
FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations
on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above
limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to
jurisdiction.)
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since
individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these
devices for any specific application.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The
series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance
information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of
the product.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Made in China.
8. Storage and Service
9. Warranty
16
201111193-93-2847B
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Tripp Lite BP240V1037C-1PH Owner's manual

Category
UPS batteries
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI