2. The Air Intake connection is to the right of the exhaust.
3. Remove all burrs and debris from the joints and
fittings.
4. Horizontal lengths of exhaust vent must be installed
with a slope of not less than 1/4" per foot (21 mm per
meter) toward the boiler to allow condensate to drain
from the vent pipe. If the vent pipe must be piped
around an obstacle that causes a low point in the
piping, a drain with an appropriate trap must be
installed.
5. All piping must be fully supported. Use pipe hangers at
a minimum of 4 foot (1.22 meter) intervals to prevent
sagging of the pipe.
6. Exhaust and air inlet piping is to be supported
separately and should not apply force to the boiler.
7. Penetration openings around the vent pipe and air
intake piping are to be fully sealed to prevent exhaust
gases from entering building structures.
8. PVC & CPVC Piping:
a. Use only solid PVC or CPVC Schedule 40 or 80
pipe for exhaust venting. Cellular core PVC or
CPVC is not approved for exhaust vent.
b. All joints in vent pipe, fittings, and all vent
termination joints must be properly cleaned,
primed and cemented. Use only cement and
primer approved for use with PVC or CPVC pipe
that conforms to ANSI/ASTM D2564. Boiler
connections do NOT require cement.
c. A straight coupling is to be used as an
outside vent termination. One of the two
screens is to be installed to prevent birds or
rodents from entering.
d. An air intake tee should be used as an air intake
termination. A screen is to be installed to prevent
birds or rodents from entering.
e. The following are optional combination air
intake/exhaust terminations that are available
separately from your PB Heat, LLC distributor for
use with Series PBC™ boilers.
f. Refer to Figures 3.4 through 3.8 for sidewall
venting options using PVC or CPVC pipe.
g. Refer to Figures 3.9 through 3.13 for vertical
venting options using PVC or CPVC pipe.
F. EXHAUST TAPPING FOR VENT SAMPLE
To properly install the Series PBC™ boiler, carbon dioxide
(CO2) and carbon monoxide (CO) levels in the exhaust
vent must be determined from a sample of combustion
products. To do this use the built in sampling port in the
3-in-1 adapters. Be sure to replace the cap after sampling
the combustions.
G. BOILER REMOVAL FROM COMMON
VENTING SYSTEM
At the time of removal of an existing boiler, follow these
steps with each appliance remaining connected to the
common venting system placed in operation, while the
other appliances remaining connected to the common
venting system are not in operation:
Retrait de la chaudière d’un système d’évacuation
commun. Au moment de retirer une chaudière existante,
il est important de suivre les étapes suivantes pour chaque
appareil raccordé au système d’évacuation commun qui
sont en service, alors que les autres appareils demeurant
raccordés au système d’évacuation commun ne sont pas
en service:
1. Seal any unused openings in the common venting
system.
Sceller toute ouverture du système d’évacuation
commun non utilisée.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
Effectuer un contrôle visuel du système d’évacuation
pour vérifier la taille et la pente horizontale et
s’assurer qu’il n’existe aucun blocage ou obstruction,
fuite, corrosion ni tout autre problème pouvant
menacer la sécurité.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building.
Dans la mesure du possible, fermer toutes les portes
et fenêtres de l’immeuble ainsi que toutes les portes
entre l’espace dans lequel les appareils qui demeurent
raccordés au système d’évacuation commun se
trouvent et le reste de l’immeuble.
4. Turn on any clothes dryers and any appliance not
connected to common venting system. Turn on any
exhaust fans, such as range hoods and bathroom
exhausts, so they will operate at maximum speed. Do
not operate a summer exhaust fan.
VENTING & AIR INLET PIPING
3" 2"
Description
Stock
Code Description
Stock
Code
Sidewall Termination Kit
– PolyPro 3PPS-HK 54498 Sidewall Termination Kit
– PolyPro 2PPS-HKL 54837
Vertical Vent Termination
Kit – PolyPro 3PPS-VK 54500 Vertical Vent Termination
Kit – PolyPro 2PPS-VKL 54838
Table 3.4: Concentric Vent Termination Kits
This appliance uses a positive pressure venting
system. All joints must be sealed completely to
prevent leakage of flue products into living spaces.
Failure to do this may result in severe personal injury,
death or major property damage.
WARNING