A. Installation must conform to the requirements
of the authority having jurisdiction or, in the
absence of such requirements, to the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or
Natural Gas and Propane Installation Code, CAN/
CSA B149.1. Where required by the authority
having jurisdiction, the installation must conform
to the Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1.
B.
combustible
carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local
listed clearances from combustible material and
recommended service clearance. Recommended
service clearance may be reduced but should not
be less thean clearances to combustible.
D. Protect gas ignition system components from
water (dripping, spraying, rain, etc.) during boiler
operation and service (circulator replacement,
condensate trap, control replacement, etc.).
E. Provide combustion and ventilation air in
accordance with applicable provisions of local
building codes, or: USA - National Fuel Gas Code,
ANSI Z223.1/NFPA 54, Air for Combustion and
Ventilation; Canada - Natural Gas and Propane
Installation Code, CAN/CSA-B149.1, Venting
Systems and Air Supply for Appliances.
F. The boiler should be located so as to minimize
the length of the vent system. Ensure air intake
pipe termination away from areas that may
contaminate combustion air (see Table 4). In
particular, avoid areas near chemical products
removers, cleaning solvents and detergents.
Avoid areas containing saw dust, loose insulation
NOTICE
Due to the low water content of the boiler, mis-
sizing of the boiler with regard to the heating
system load will result in excessive boiler
cycling and accelerated component failure.
Thermal Solutions DOES NOT warrant failures
caused by mis-sized boiler applications.
DO NOT oversize the boiler to the system.
Multiple boiler installations greatly reduce the
likelihood of boiler oversizing.
Avoid operating this boiler in an environment
wall dust, etc. are present. If boiler is operated
under these conditions, the burner interior
and ports must be cleaned and inspected daily
to insure proper operation.
Ensure all labels on the boiler are fully visible
at all times for the purpose of maintenance and
inspections.
WARNING
Apply supplied dielectric grease to gasket inside
vent connector. Failure to apply the grease
installation or gasket deterioration due to
condensate exposure.
Adequate combustion and ventilation air must
be provided to assure proper combustion.
Install combustion air intake per Section IV
“Venting”.
Installation of this boiler should be undertaken
only by trained and skilled personnel from
instructions exactly. Improper installation,
adjustment, service, or maintenance can cause
property damage, personal injury or loss of life.
Do not change or modify any boiler accessories
or parts or jump-out any safety limit devices.