Remote Automation Solutions FB3000 Remote Terminal Unit (RTU) User manual

Type
User manual
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Remote Automation Solutions
Emerson FB3000 Remote Terminal Unit (RTU)
Instruction Manual
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
ii
Device Safety Considerations
Reading these Instructions
Before operating the device, read these instructions carefully and understand their safety implications. In some
situations, improperly using this device may result in damage or injury. Keep this manual in a convenient location
for future reference. Note that these instructions may not cover all details or variations in equipment or cover every
possible situation regarding installation, operation, or maintenance. Should problems arise that are not covered
sufficiently in the text, immediately contact Customer Support for further information.
Protecting Operating Processes
A failure of this device – for whatever reason -- may leave an operating process without appropriate protection and
could result in possible damage to property or injury to persons. To protect against this, you should review the
need for additional backup equipment or provide alternate means of protection (such as alarm devices, output
limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.). Contact Remote
Automation Solutions for additional information.
Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility to ensure that the
equipment has been cleaned to safe levels, as defined and/or determined by applicable federal, state and/or local
law regulations or codes. You also agree to indemnify Remote Automation Solutions and hold Remote Automation
Solutions harmless from any liability or damage which Remote Automation Solutions may incur or suffer due to
your failure to ensure device cleanliness.
Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with relevant safety
standards. For the USA, refer to OSHA rules and regulations as specified in Design Safety Standards for Electrical
Systems, 29 CFR, Part 1910, Subpart S, dated: May 16, 1981 (OSHA rulings are in agreement with the National
Electrical Code). For international locations, refer to IEC 60364-4-41: PROTECTION AGAINST ELECTRIC SHOCK.
You must also ground mechanical or pneumatic instruments that include electrically operated devices such as
lights, switches, relays, alarms, or chart drives. The FB3000 includes a chassis ground lug. Unless specifically noted,
the chassis ground is isolated from ground terminals on individual modules installed in the device to prevent noise.
The chassis ground lug provides a path to earth ground for electrical safety, static discharge, and stray voltages. Do
not connect the chassis ground lug directly to a lightning arrestor/lightning rod.
Important: Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring
personnel safety. The guidelines and recommendations in this manual are intended to meet or exceed applicable
codes and regulations. If differences occur between this manual and the codes and regulations of authorities
having jurisdiction, those codes and regulations must take precedence.
Protecting from Electrostatic Discharge (ESD)
This device contains sensitive electronic components which can be damaged by exposure to an ESD voltage.
Depending on the magnitude and duration of the ESD, it can result in erratic operation or complete failure of the
equipment. Ensure that you correctly care for and handle ESD-sensitive components.
System Training
A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure,
program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills
and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel
to acquire essential system expertise. Our full-time professional instructors can conduct classroom training at several of
our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality
training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and
further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at
Ethernet Connectivity
This automation device is intended to be used in an Ethernet network which does not have public access. The inclusion
of this device in a publicly accessible Ethernet-based network is not recommended.
FB3000 - CSA Approval Information
CD9411K
Issued: January 19, 2021
CSA-1
CSA Approval Information
SAFETY FIRST
Read this document carefully before installing an Emerson FB3000 RTU. Refer to the other
sections of the instruction manual for general information. In the event of a conflict between the
other sections of this manual and this document, always follow the instructions in this document.
Note
If the equipment is used in a manner not specified by the manufacturer, the protection provided by
the equipment may be impaired.
Module
Part Number(s)
Ordering Code
FB3000 8 Slot Chassis Assembly (Backplane) 400246-01-0, 510000-01-0 3CH08C
FB3000 Power Module Assembly 400223-01-0, 510008-01-0 3PWBLK
FB3000 CPU Module Assembly 400224-01-0, 510009-01-0 3CPU16
FB3000 CPU Personality Module Assembly 400225-01-0, 510007-01-0 3CPUSG
FB3000 8-Slot DIN Rail Assembly 510001-01-0 3DIN08
FB3000 12 Mixed I/O (12MIO) Module
Assembly
510006-01-0
400226-01-0
3MIX12
FB3000 12 Mixed I/O (12MIO) Personality
Module Assembly
510076-01-0 3MSG12
FB3000 I/O CPU Scanner Module 510121-01-0 3IOCPU
General Information:
Manufacturer: Bristol Inc. d.b.a. Remote Automation Solutions
CSA Master Contract Number: 179806
SRAM Backup Battery in Power
Modules (for memory and real-time
clock)
3V coin lithium battery BT1
(Renata model CR2450HT)
(Maxell model CR2450HR)
(Panasonic model BR2450A)
(Murata model CR2450W)
Rated Capacity: 490 mAh
Operating Temperature: 40oC to +125oC
SRAM Backup Battery in CPU Module
(for memory and real-time clock)
3V coin lithium battery BT1
(Renata model CR1632).
Rated Capacity: 125 mAh
Operating Temperature: 40oC to +85oC
Protective earthing (PE) conductor
(ground wire)
#14 AWG (2.1mm2)
Fuses Littelfuse® 0453010.MR Surface Mount Nano2 Fuse
10 Amps @ 125VDC
FB3000 - CSA Approval Information
CD9411K
Issued: January 19, 2021
CSA-2
Equipment Ratings:
Mode of Operation: Continuous
Pollution Degree: 2
Installation Category: DC supplied
Altitude: 2000 m
Humidity: 95% to temperatures up to 31oc decreasing linearly to
50% r.h. at 40oc; max 80 % r.h. non-condensing
Electrical Supply Rating: Input rating: 10.5-30Vdc
Controller Circuit: Max 5A at10.5 - 30V dc
Field Circuit: Max 5A at10.5 - 30V dc
Ambient Temperature Range:
(Tamb)
-40oC to +75oC
Temperature Code: T4
Vibration: 1.0 g for 10 to 150 Hz for 30 minutes; 0.5 g for 150 to
2000 Hz for 30 minutes
Locations: The
Emerson FB3000 Remote Terminal Unit (RTU)
is
listed by the Canadian Standards Association (CSA) as
suitable for use in Class I, Division 2, Groups A, B, C and
D hazardous locations (when installed in a suitably-
rated enclosure), and in Class I, Zone 2, AEX/Ex ec IIC
Gc hazardous locations (when installed in an IP54
enclosure per requirements of standards CSA/UL
60079-0 and CSA/UL 60079-7).
If no suitably-rated enclosure is provided, may only be
used in non-hazardous indoor locations.
Representative Power Supplies: 24V power supply at 10A to 20A as approved to
standard UL 60950-1.
Typical: Phoenix Contact
Quint-PS/1AC/24DC/10
or
Quint-PS/1AC/24DC/20
Extended Backplane Supported Configurations:
Voltage (Control/Loop)
Max number of
12MIO/12MIO Personality
Modules installed
Max number of 12MIO/12MIO
Personality Modules with loop
power enabled
30V 31 26
24V ≤ V < 30V 31 21
12V≤ V < 24V 21 10
10.5V≤ V < 12V 18 8
FB3000 - CSA Approval Information
CD9411K
Issued: January 19, 2021
CSA-3
Conditions of Use:
Wiring to or from this device, which either enters or leaves the user-provided enclosure, must
adhere to wiring methods suitable for Class I, Zone 2 and Division 2 Hazardous locations, as
appropriate for the installation and is subject to the acceptance of CSA or the inspection authority
having jurisdiction.
Install this device in a user-provided enclosure that provides a minimum entry protection of IP 54,
in accordance with IEC 60079-0:11.
Install the racks in a left to right horizontal direction (wall mount on DIN-rails) inside of the end user
system enclosure. Never mount the racks in a vertical stacked direction
When using DIN-rail mounting as the method of installation for the extended backplane
configuration, use DIN-rail end brackets at the two ends of the extended backplane to prevent side
movements of the equipment on the DIN-rail. Refer to the Emerson FB3000 RTU Instruction Manual
(D301851X012) for details.
CSA evaluates this equipment according to the following standards:
CAN/CSA-C22.2 No. 0-10
August 2011
General requirements Canadian Electrical Code, Part
II
CAN/CSA Standard C22.2 No. 213-17
UL 121201
Non-incendive Electrical Equipment for Use in Class I
and II Division 2 and Class III Division 1 and 2 Hazardous
Locations
CAN/CSA C22.2 No. 60079-7:16 Explosive atmospheres Part 7: Equipment protection
by increased safety “e”
UL 60079-7:17 Explosive atmospheres Part 7: Equipment protection
by increased safety “e”
CAN/CSA C22.2 No. 60079-0:15 Explosive atmospheres Part 0: Equipment – General
Requirements
UL 60079-0:13 Explosive atmospheres Part 0: Equipment – General
Requirements
IEC 60079-0:2011 Explosive atmospheres Part 0: Equipment – General
Requirements
IEC 60079-7:2017 Explosive atmospheres Part 7: Equipment protection
by increased safety “e”
FB3000 - CSA Approval Information
CD9411K
Issued: January 19, 2021
CSA-4
WARNING
EXPLOSION HAZARD CONNECT OR DISCONNECT ONLY IN A NON-HAZARDOUS AREA.
WARNING
EXPLOSION HAZARD DO NOT REMOVE OR REPLACE WHILE CIRCUIT IS LIVE UNLESS THE AREA IS
FREE OF IGNITABLE CONCENTRATIONS.
WARNING
EXPLOSION HAZARD DO NOT REMOVE OR REPLACE FUSE WHEN ENERGIZED.
DANGER
EXPLOSION HAZARD: BATTERIES MUST ONLY BE CHANGED IN AN AREA FREE OF IGNITABLE
CONCENTRATIONS
WARNING
DO NOT USE THE USB CONNECTOR UNLESS THE AREA IS KNOWN TO BE NON-HAZARDOUS.
FB3000 - CSA Approval Information
CD9411K
Issued: January 19, 2021
CSA-5
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Contents iii
Contents
Section 1: Introduction 1
1.1 Safety Labels ........................................................................................................................ 2
1.2 Features ............................................................................................................................... 2
1.3 FB3000 RTU Chassis ............................................................................................................. 3
1.4 Central Processing Unit (CPU) ............................................................................................... 3
1.4.1 Memory ................................................................................................................... 3
1.5 I/O ........................................................................................................................................ 4
1.6 Power ................................................................................................................................... 5
1.7 Communications .................................................................................................................. 5
1.8 Software Tools ..................................................................................................................... 6
Section 2: Installation 7
2.1 Hazardous Locations ............................................................................................................ 7
2.2 Required Tools ..................................................................................................................... 7
2.3 Site Considerations .............................................................................................................. 8
2.3.1 Connecting Extension Chassis .................................................................................. 8
2.4 General Wiring Guidelines .................................................................................................. 10
2.5 Grounding .......................................................................................................................... 11
2.5.1 Chassis Ground Lug ................................................................................................ 11
2.5.2 Internal System Bus Ground ................................................................................... 12
2.5.3 Isolated Ground on 3MIX12 Module ....................................................................... 12
2.5.4 24V Loop Ground on 3MIX12 Module ..................................................................... 12
2.6 Mounting the Chassis ......................................................................................................... 14
2.6.1 Panel or Wall Mounting the Aluminum Enclosure ................................................... 15
2.7 Removing Battery Saver Tabs ............................................................................................. 17
2.8 Connecting Power .............................................................................................................. 17
2.8.1 Connecting External Power .................................................................................... 18
2.9 Removing the I/O Cover ..................................................................................................... 20
2.10 Connecting Communication Ports ........................................................................... 21
2.10.1 Connecting to COM1 ............................................................................................ 22
2.10.2 Connecting to COM2 ............................................................................................ 25
2.10.3 Connecting to COM3 ............................................................................................ 28
2.10.4 Connecting to COM4 ............................................................................................ 30
2.10.5 Ethernet and Micro USB Ports ............................................................................... 32
Section 3: I/O Configuration and Wiring 33
3.1 Analog Inputs ..................................................................................................................... 34
3.1.1 AI Wiring ................................................................................................................ 34
3.2 Analog Outputs .................................................................................................................. 36
3.2.1 AO Wiring .............................................................................................................. 37
3.3 Digital Inputs ...................................................................................................................... 38
3.3.1 DI Wiring ................................................................................................................ 39
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
iv Contents
3.4 Digital Outputs ................................................................................................................... 39
3.4.1 DO Wiring .............................................................................................................. 41
3.5 Pulse Inputs ........................................................................................................................ 45
3.5.1 PI Wiring ................................................................................................................ 46
Section 4: Operation 47
4.1 Powering Up/Powering Down the Device ........................................................................... 47
4.2 Establishing Communications ............................................................................................ 47
4.2.1 Communicating with the SCADA Host .................................................................... 47
4.2.2 Communicating with a Laptop Using a Serial Port ................................................... 48
4.2.3 Communicating with a Laptop Using Ethernet ........................................................ 49
Section 5: Service and Troubleshooting 51
5.1 Returning the Unit for Repairs ............................................................................................ 52
5.2 Interpreting the Status LEDs ............................................................................................... 53
5.3 Removing/Replacing the Power Module ............................................................................. 57
5.4 Removing/Replacing the SRAM Batteries ............................................................................ 59
5.5 Removing/Replacing the CPU Module (3CPU16)................................................................. 61
5.6 Removing/Replacing an I/O Module (3MIX12) .................................................................... 62
5.7 Removing/Replacing a Personality Module ......................................................................... 64
5.8 Upgrading System Firmware .............................................................................................. 65
5.9 Backing Up Historical Data and Your Configuration ............................................................ 66
5.10 Backing Up Your Solution ................................................................................................... 67
Index 69
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Introduction 1
Section 1: Introduction
This section covers the following topics:
Safety Labels
Features
FB3000 Chassis
Central Processing Unit (CPU)
I/O
Power Options
Communications
Software Tools
The Emerson FB3000 Remote Terminal Unit (RTU) runs measurement and control applications
suitable for the oil and gas, water, wastewater, and other process industries. You can also purchase
the FB3000 as an I/O-only device (FBxRemote I/O™) where control runs in a separate host FB3000
RTU. This manual describes how to install and configure the FB3000 hardware.
For information on using the FBxConnect configuration software, see the online help that
accompanies FBxConnect.
Figure 1-1: FB3000 RTU
1
2
3
4
5
6
7
8
9
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
2 Introduction
1.1 Safety Labels
This product may display safety label(s) to identify potential hazards. The same types of notices
appear within the documentation. Whenever you see an exclamation point (!) enclosed within a
triangle (shown to the left), consult the documentation for additional safety information about the
hazard and how to avoid it. The labels used are:
DANGER
MAY CAUSE DEATH
Observe all precautionary signs posted on the equipment.
Failure to do so may result in death or serious injury to personnel.
WARNING
DANGER TO PERSONNEL AND EQUIPMENT
Observed all precautionary signs posted on the equipment.
Failure to do so may result in injury to personnel or cause damage to the equipment.
CAUTION
MAY CAUSE INJURY TO PERSONNEL OR DAMAGE EQUIPMENT
Observed all precautionary signs posted on the equipment.
Failure to do so may result in injury to personnel or cause damage to the equipment.
SAFETY FIRST
General instructions and safety reminders.
1.2 Features
The FB3000 RTU includes the following key features:
Operates in Class I Division 2 non-incendive and Ex ec Zone 2 non-sparking environments
when installed within a suitable enclosure
Eight slot chassis may be extended with one, two, or three extension chassis.
Supports I/O modules (holding I/O electronics/logic) and associated “personalitymodules
(handling wiring and termination)
Supports one or two power supply modules
Obtains power from a DC power supply (10.5-30Vdc)
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Introduction 3
Supports serial communication options for RS-232 and RS-485
Provides two Ethernet (10/100/1000Base-T) ports
Provides Micro A-B USB connector to support DNP3 communications
1.3 FB3000 RTU Chassis
The FB3000 RTU has an eight-slot chassis. The CPU is always in slot one of the base chassis.
Figure 1-2: FB3000 RTU - 8 Slot Version (with/without slot covers)
Each slot includes an upper section and a lower section. The upper section holds the internal logic
for the module and the lower section holds the personality module used for wiring.
If your RTU is not fully populated with modules, you can fill the empty slots with slot covers to
protect the connectors from dust. These are installed/removed using the same screws used for
personality modules.
If you require more than seven I/O slots, you can optionally purchase one, two, or three extension
chassis to attach to the base chassis, allowing an additional 8, 16, or 24 I/O slots.
1.4 Central Processing Unit (CPU)
The RTU’s CPU is a Freescale (NXP) SoloX dual-core architecture processor with an Arm® Cortex®-
A9 core, and an Arm Cortex-M4 core. If your RTU includes multiple chassis, there is still only one
CPU module in the 1st slot of the first chassis; all other chassis hold only I/O modules.
There are two CPU versions available:
3CPU16 – FB3000 RTU with full control and I/O capabilities.
3IOCPU FBxRemote I/O for I/O only with no control, no calculation support, and no
application support.
1.4.1 Memory
The RTU includes both static and flash memory.
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
4 Introduction
Table 1-1: Memory
Memory
Usage
256 MB Flash
Firmware image and report files; with 104 MB reserved for file system
and 128 MB available for database and history
16 MB SRAM
Historical data logs and configuration
1 GB DDR3 SDRAM
Firmware execution and execution memory
1.5 I/O
Other than slot 1 in the base chassis (which is reserved for the CPU), any slot can contain an I/O
module. Each 12-channel Mixed I/O module (labelled 3MIX12) supports the following
inputs/outputs
Eight (8) input channels that you can individually configure using FBxConnect as analog inputs
(AI), digital inputs (DI), or pulse inputs (PI).
AIs are software-selectable as either 1VDC to-5VDC or 4 mA to 20 mA
Two (2) analog output channels.
Two (2) digital output channels.
As noted, the eight-slot RTU supports seven (7) I/O slots. Table 1-2 shows the maximum number of
I/O channels if all I/O slots are fully populated.
Table 1-2: Maximum I/O Count in Single Chassis
# of Slots
AI/DI/PI
AO
DO
7
56
14
14
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Introduction 5
You can purchase one, two, or three extension chassis to connect to the base chassis, to add 8, 16,
or 24 additional I/O slots.
1.6 Power
You can power the RTU using an external DC input. The RTU includes two power supply modules.
Table 1-3: Power
Power Source
Usage
External DC Power Supply
10.5 Vdc to 30 Vdc external supply
1.7 Communications
The RTU includes four serial communication ports, two Ethernet ports, and one Micro A-B USB port.
The Ethernet ports reside on the top of the CPU module and use RJ-45-style 8P8C sockets. Each
port supports a maximum of six concurrent TCP connections (sockets). The Micro A-B USB port
resides on the front of the CPU module and supports DNP3 communication. The serial ports allow
communication using DNP3, Modbus slave and Modbus master protocols.
Table 1-4: Serial Ports
Port
Type
Use
COM1
Serial communications
Software-selectable for RS-232 or
RS-485 operation*
4-wire
RS-232, or RS-485 communication to host or
other devices. 4-wire used with external radio.
COM2
Serial communications
Software-selectable for RS-232 or
RS-485 operation*
4-wire
RS-232 or RS-485 communication to host or
other devices. 4-wire used with external radio.
COM3
Serial communications
Isolated RS-485 operation
2-wire
RS-485 communication to host or other devices
such as 4088B.
COM4
Serial communications
Isolated RS-485 operation
2-wire
RS-485 communication to host or other devices
such as 4088B.
*Under older standards RS-485 (4-wire) referred to as RS-422.
Note:
For an I/O
only CPU (3IOCPU) FBxConnect pass-through communication from a host requires
Ethernet communication; serial ports are only supported through a local connection.
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
6 Introduction
1.8 Software Tools
The FBxConnect configuration software provides a series of wizards that enables you to perform
configuration activities for the RTU. You connect a PC running the FBxConnect configuration
software to the RTU using one of the serial, Ethernet or USB ports. You can then:
Set parameters within your application
Configure I/O channels
Specify the serial communication method for a port (RS-232 to RS-485) as needed
Update system firmware
Optional FBxDesigner programming software lets you create custom applications for the RTU
using any of the five IEC61131 languages.
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Installation 7
Section 2: Installation
This section covers the following topics:
Hazardous Locations
Required Tools
Site Considerations
General Wiring Guidelines
Grounding
Mounting the Chassis
Removing the Battery Saver Tab
Connecting Power
Removing the I/O Cover
Connecting Communications Ports
The RTU ships from the factory fully assembled.
2.1 Hazardous Locations
For North America the FB3000 has certifications for Class I Division 2 (Groups A, B, C & D) non-
incendive and non-hazardous locations only. For other world areas the FB3000-has ATEX and IEC Ex
certifications for Ex ec Zone 2 non-sparking installations and non-hazardous locations only.
All certifications are listed on the data plate located on the top of the device. Refer to the CSA
Approval Information document (CD9411A) for special information for Class I Division 2 and Ex ec
Zone 2 installations.
2.2 Required Tools
Certain tools and equipment are required for installing and servicing the RTU.
Table 2-1: Required Tools
Tool
Use
#2 Phillips screwdriver
Chassis ground lug, panel installation, removal of rear
panel.
¼slotted blade screwdriver
Personality module removal
Magnets
Battery removal
Non-metallic tool
Battery removal
Laptop PC running Field Tools with
FBxConnect configuration software Software configuration
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
8 Installation
2.3 Site Considerations
The RTU must reside in an accessible location for configuration and service. Refer to the
dimensional drawings for information on the space required.
Figure 2-1: FB3000 Dimensions8 Slot (with/without DIN Rail mounting plate assembly)
1
No DIN mounting plate in this view.
Connecting Extension Chassis
The FB3000 supports up to 3 additional chassis. When connecting an extension chassis to the
“base” chassis (the chassis containing the CPU module), use only the connector on the right hand
side of the base chassis. The FB3000 base chassis cannot support an extension chassis using the
left-hand connector.
DANGER
When installing in a hazardous location, the installer must ensure the side connectors between
the chassis are fully engaged.
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
Installation 9
CAUTION
MAY CAUSE INJURY TO PERSONNEL OR DAMAGE EQUIPMENT
When mounting an FB3000 with one or more extension chassis in an enclosure, ensure that you
mount the racks in a left to right
horizontal direction (wall mount on DIN-rails)
inside the end user
system enclosure to allow for adequate heat dissipation.
Never
mount the racks in a
vertical
stacked direction.
Notes: If using multiple chassis, the length dimension increases by approximately 220 mm (8.7 in)
for each additional chassis, so:
if using two chassis, overall length is approximately 465 mm (18.30 in)
If using three chassis, overall length is approximately 685 mm (26.96 in)
If using four chassis, overall length is approximately 905 mm (35.62 in)
1. Squeeze hard to remove connector covers on the two mating chassis. You may need to
use both hands.
Figure 2-2: Removing Chassis Connector Cover
Emerson FB3000 RTU Instruction Manual
D301851X012
April 2021
10 Installation
2. Press the two chassis together. If mounting on a DIN rail, slide both chassis onto the DIN
rail first to ensure proper alignment and place clamps/brackets at both ends of assembly
on DIN rail to ensure side connectors between chassis remain fully engaged. (See Section
2.6).
Figure 2-3: Pressing Chassis Together
2.4 General Wiring Guidelines
The RTU’s pluggable terminal blocks use compression-type terminals that accommodate wire
between 24 and 12 AWG depending on the connector or terminal block and the usage. Use 28 to
16 AWG wires on the 20 pin I/O connectors; use 20 to 12 AWG wires on the power connection.
CAUTION
All wires must be rated for a temperature of 90oC or higher.
CAUTION
Wires used for power
must
have a wire gauge between 20 and 12 AWG.
When making a connection, insert the bare end of the wire (approx. 1/4" max) into the clamp
adjacent to the screw and secure the screw.
To prevent shorts, ensure that no bare wire is exposed. You can also use crimp bootlace
ferrules (18 to 24 AWG for I/O; 18 to 20 AWG for power).
Allow some slack in the wire while making terminal connections. Slack makes the wires more
manageable and helps minimize mechanical strain on the terminal blocks.
Use twisted pair, shielded and insulated cable for communication and I/O wiring to minimize
signal errors caused by electromagnetic interference (EMI), radio frequency interference (RFI)
and transients. When using shielded cable, ground all shields at a suitable Instrument Earth
connection point. This prevents circulating ground current loops that can cause signal errors.
See the FB3000 product data sheet for information about applicable standards for EMI and RFI
emissions and susceptibility.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84

Remote Automation Solutions FB3000 Remote Terminal Unit (RTU) User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI