Vertiv Liebert® XDU060 Liquid to Air Heat Exchange for Chip Cooling User manual

Category
Split-system air conditioners
Type
User manual
LiebertĀ® XDU Liquid to Air Heat
Exchanger for Chip Cooling
Installer/User Guide
600 mm Wide
Vertivā„¢ | LiebertĀ® XDUīƒ„Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change without notice and may not
be suitable for all applications. While every precaution has been taken to ensure the accuracy
and completeness of this document, Vertiv assumes no responsibility and disclaims all liability
for damages resulting from use of this information or for any errors or omissions.
Vertiv recommends installing a monitored fluid detection system that is wired to activate the
automatic closure of field-installed coolant fluid supply and return shut off valves, where
applicable, to reduce the amount of coolant fluid leakage and consequential equipment and
building damage. Refer to local regulations and building codes relating to the application,
installation, and operation of this product. The consulting engineer, installer, and/or end user
is responsible for compliance with all applicable laws and regulations relating to the
application, installation, and operation of this product.
The products covered by this instruction manual are manufactured and/or sold by Vertiv.
This document is the property of Vertiv and contains confidential and proprietary information
owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv
is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective
companies. Any questions regarding usage of trademark names should be directed to the
original manufacturer.
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
TABLE OF CONTENTS
1 Important Safety Instructions 1
2 Nomenclature and Components 7
2.1 Model Number Nomenclature 7
2.2 Component Location 8
2.3 Cooling Configuration 9
3 Pre-installation Preparationīƒ„andīƒ„Guidelines 11
3.1 Planning Dimensions 11
3.2 Unit Weights 11
3.3 Implementing a Hot Aisle/Cold Aisle Equipment Layout 12
4 Equipment Inspection and Handling 13
4.1 Storing Before Installation 14
4.2 Packaging Material 14
4.3 Handling the Unit While Packaged 14
4.4 Unpacking the Export Shipped Unit 14
4.5 Unpacking the Domestic Shipped Unit 15
4.6 Removing Units from the Pallet 17
5 Installing in Enclosure Row 21
5.1 Adjusting Base Supports/Leveling Feet 21
6 Piping Requirements 23
6.1 Fluid Volume for Unit and Connection Piping 23
6.2 Water Quality Requirements 24
6.3 Connecting the Closed Loop System 26
6.4 Leak Check before Commission and Operation 27
6.5 Filling the System 28
6.5.1 Fluid Fill Source 29
6.5.2 Flushing the Cooling System 30
6.5.3 Filling the Complete System 30
6.5.4 Draining the System 31
7 Electrical Connections 33
7.1 Power Supply Cable Connection Guidelines 33
7.2 Wiring Connection Guidelines 33
7.3 Electrical Field Connections 34
7.4 Protective Features of the Electronically Commutated (EC) Fansā€”All Models 34
8 Vertivā„¢ LiebertĀ® XDU Start Up 35
8.1 Checks to Perform after Startup 35
9 Troubleshooting 37
10 Maintenance 39
10.1 Safety Instructions 39
i
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
10.2 Fluid and Piping Maintenance 40
10.3 Spare Parts 40
10.4 Maintenance Schedule 40
10.5 Fan Replacement 41
10.5.1 Replacing a Fan in 600-mm (24-Inch) Models 41
10.6 Checking and Cleaning the Strainer 43
10.7 Flow Sensor 44
10.7.1 Setting the Flow Sensor for the Vertivā„¢ LiebertĀ® XDU 46
11 Preventive Maintenance Worksheet 49
Appendices 53
Appendix A: Technical Support and Contacts 53
Appendix B: Performance Curves 55
Appendix C: Technical Specifications 59
Appendix D: Submittal Drawings 61
ii
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
1 Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the
Vertivā„¢ LiebertĀ®īƒ„XDU. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should operate, move, install or service this equipment.
This equipment is not to be installed in an area accessible to the general public.
Adhere to all warnings, cautions, notices, and installation, operating, and safety instructions on the unit and in this manual.
Follow all installation, operation, and maintenance instructions and all applicable national and local building, electrical, and
plumbing codes.
Any operation that requires opening doors or equipment panels must be carried out only by properly trained and qualified
personnel.
To identify the unit model and serial number for assistance or spare parts, locate the identification label on the unit. The label
is inside of the display of the door.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power supply disconnect
switches, verify with a voltmeter that power is Off, and wear appropriate, OSHA approved personal
protective equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to
comply can cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC, and
local codes, as applicable. Before proceeding with installation, read all instructions, verify that all the parts
are included, and check the nameplate to be sure the voltage matches available utility power. The Liebert
controller does not isolate power from the unit, even in the Unit Off mode. Some internal components require
and receive power even during the Unit Off mode of the controller. The factory supplied, optional disconnect
switch is inside the unit. The line side of this switch contains live high voltage. The only way to ensure that
there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical
schematic. Follow all local codes.
WARNING! Risk of electric shock. Can cause equipment damage, injury, or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before working within
any electric connection enclosures. Service and maintenance work must be performed only by properly
trained and qualified personnel and in accordance with applicable regulations and manufacturersā€™
specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
WARNING! Risk of electric shock. Can cause serious injury or death. The Vertivā„¢ LiebertĀ® iCOMā„¢
microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components
require and receive power even during the Unit Off mode of the LiebertĀ®iCOMā„¢ control. Open all local and
remote electric power disconnect switches and verify with a voltmeter that power is Off before working on
any component of the system.
1 Important Safety Instructions 1
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
WARNING! Risk of improper moving, lifting, or handling of the unit. Can cause equipment damage, injury, or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from, or prepare the unit for installation.
See Table 3.2 on pageīƒ„11 , for weights.
WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,
serious injury, or death. Installation and service of this equipment should be done only by qualified personnel
who have been specially trained in the installation of air conditioning equipment and who are wearing
appropriate, OSHA approved PPE.
WARNING! Risk of improper wire sizing/rating and loose electrical connections. Can cause overheated wire
and electrical connection terminals resulting in smoke, fire, equipment and building damage, injury, or death.
Use correctly sized copper wire only and verify that all electrical connections are tight before turning power
On. Check all electrical connections periodically and tighten as necessary.
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury, or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from, or prepare the unit for installation.
WARNING! Risk of unsecured unit rolling off of pallet. Can cause equipment damage, injury, or death. The unit
is on casters. Ensure that the unit and pallet are located on a flat surface before loosening the hardware
securing the unit to its shipping pallet.
WARNING! Risk of hair, clothing, and jewelry entanglement with high speed rotating fan blades. Can cause
equipment damage, serious injury, or death. Keep hair, jewelry, and loose clothing secured and away from
rotating fan blades during unit operation.
WARNING! Risk of contact with high speed rotating fan blades. Can cause serious injury or death. Open all
local and remote electric power supply disconnect switches, verify with a voltmeter that power is off, and
verify that all fan blades have stopped rotating before working in the unit cabinet or on the fan assembly. If
control voltage is applied, the fan motor can restart without warning after a power failure. Do not operate the
unit with any or all cabinet panels removed.
CAUTION: Risk of contact with extremely hot and/or cold surfaces. Can cause injury. Verify that all
components have reached a temperature that is safe for human contact or wear appropriate, OSHA approved
PPE before working within the electric connection enclosures or unit cabinet. Perform maintenance only when
the system is de-energized and component temperatures have become safe for human contact.
1 Important Safety Instructions
2
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only properly
trained and qualified personnel wearing appropriate, OSHA approved PPE should attempt to move, lift,
remove packaging from, or prepare the unit for installation.
NOTICE
Risk of improper power supply connection. Can cause equipment damage and loss of warranty coverage.
Prior to connecting any equipment to a main or alternate power source (for example: backup generator systems)
for start-up, commissioning, testing, or normal operation, ensure that these sources are correctly adjusted to the
nameplate voltage and frequency of all equipment to be connected. In general, power source voltages should be
stabilized and regulated to within Ā±10% of the load nameplate nominal voltage. Also, ensure that no three-phase
sources are single-phased at any time.
NOTICE
Risk of piping system corrosion and freezing fluids. Can cause leaks resulting in equipment and very expensive
building damage. Cooling coils and piping systems are at high risk of freezing and premature corrosion. Fluids in
these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil and
piping corrosion. The water or water/glycol solution must be analyzed by a competent local water treatment
specialist before start up to establish the inhibitor and antifreeze solution requirement and at regularly scheduled
intervals throughout the life of the system to determine the pattern of inhibitor depletion.
The complexity of water/glycol solution condition problems and the variations of required treatment programs
make it extremely important to obtain the advice of a competent and experienced water treatment specialist and
follow a regularly scheduled coolant fluid system maintenance program.
Water chemistry varies greatly by location, as do the required additives, called inhibitors, that reduce the
corrosive effect of the fluids on the piping systems and components. The chemistry of the water used must be
considered, because water from some sources may contain corrosive elements that reduce the effectiveness of
the inhibited formulation. Sediment deposits prevent the formation of a protective oxide layer on the inside of the
coolant system components and piping. The water/coolant fluid must be treated and circulating through the
system continuously to prevent the buildup of sediment deposits and or growth of sulfate reducing bacteria.
Proper inhibitor maintenance must be performed in order to prevent corrosion of the system. Consult glycol
manufacturer for testing and maintenance of inhibitors.
Commercial ethylene glycol, when pure, is generally less corrosive to the common metals of construction than
water itself. It will, however, assume the corrosivity of the water from which it is prepared and may become
increasingly corrosive with use if not properly inhibited.
We recommend installing a monitored fluid detection system that is wired to activate the automatic closure of
field installed coolant fluid supply and return shut-off valves to reduce the amount of coolant fluid leakage and
consequential equipment and building damage. The shut-off valves must be sized to close off against the
maximum coolant fluid system pressure in case of a catastrophic fluid leak.
1 Important Safety Instructions 3
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
NOTICE
Risk of frozen pipes and corrosion from improper coolant mixture. Can cause water leaks resulting in equipment
and building damage.
When the cooling unit or piping may be exposed to freezing temperatures, charge the system with the proper
percentage of glycol and water for the coldest design ambient temperature. Automotive antifreeze is
unacceptable and must NOT be used in any glycol fluid system. Use only HVAC glycol solution that meets the
requirements of recommended industry practices. Do not use galvanized pipe.
NOTICE
Risk of no-flow condition. Can cause equipment damage.
Do not leave the water/coolant fluid supply circuit in a no-flow condition. Idle fluid allows the collection of
sediment that prevents the formation of a protective oxide layer on the inside of tubes. Keep unit switched On
and water/coolant fluid supply circuit system operating continuously.
NOTICE
Risk of clogged or leaking fluid lines. Can cause equipment and building damage.
Improper installation, application and service practices can result in water leakage from the unit. Water leakage
can result in catastrophic and expensive building and equipment damage and loss of critical data center
equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid detection system to immediately discover and report coolant fluid
system and condensate drain line leaks.
NOTICE
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to fit
below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the unit upright, indoors, and protected from dampness, freezing temperatures, and contact damage.
1 Important Safety Instructions
4
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
Agency Listed
The XDU Thermal Management System complying with North American requirements shall be Certified/Listed to one of the
following harmonized US and Canadian product safety standards. Units are marked with the CSA logo with ā€œcā€ and ā€œusā€
country identifiers.
ā€¢CSA C22.2 No. 236/UL 1995 Heating and Cooling Equipment; or
ā€¢CSA/UL 60335-2-40 Household and similar electrical appliances - Safety - Particular requirements for electrical
heat pumps, air-conditioners and dehumidifiers, in conjunction with CSA/UL 60335-1 Household and similar
electrical appliances - Safety - Part 1: General requirements
The XDU Thermal Management System complying with CE requirements shall conform to the
following Directives, Standards and Regulations. Units are marked with the CE Mark and come with
Declarations of Conformity.
ā€¢Machinery Directive 2006/42 / EC and Low Voltage Directive 2014/35 / EU:
ā€¢EN 60335-2-40 Household and similar electrical appliances - Safety - Particular requirements for electric
heat pumps, air conditioners and dehumidifiers, in combination with
ā€¢EN 60335-1 Household and similar electrical appliances - Safety - Part 1: General requirements
ā€¢EMC Directive 2014/30 / EU:
ā€¢EN 61000-6-2 Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity standard for
industrial environments
ā€¢EN 61000-6-3 Electromagnetic compatibility (EMC) Part 6-3: Generic standards - Emission standard for
residential, commercial and light industrial environments
ā€¢Directive 2011/65/EU - Restriction of Hazardous Substances in Electrical and Electronic Equipment and Directive
(EU) 2015/863 amending Annex II to Directive 2011/65/EU
ā€¢REACH Regulation EC No. 1907/2006 - Registration, Evaluation, Authorization and Restriction of Chemicals
1 Important Safety Instructions 5
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
1 Important Safety Instructions
6
This page intentionally left blank
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
2 Nomenclature and Components
This section describes the model number for Vertivā„¢ LiebertĀ® XDU units and components.
2.1 Model Number Nomenclature
Table 2.2 below describes each digit of the 25-digitīƒ„configurationīƒ„number. The 14-digit model number consists of the first 10
digits and last four digits of the configuration number.
Model # Part 1 Model Details Model # Part 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
X D U 0 6 0 A C W - - 1 D - - - - - - - - A - - -
Table 2.1 Vertivā„¢ LiebertĀ® XDU Model Number Example
Digit Description
Digits 1, 2 = The base unit
XD = Extreme Heat Density System
Digit 3 = System Type
U = Coolant distribution unit
Digit 4, 5, 6 = Nominal Capacity
060 = 60īƒ„kW
Digit 7 = Heat Rejection
A = Air (fin-type heat exchanger)
Digit 8 = Supply Power
C = 208īƒ„V/2 = 380V/3 ~/ 60 Hz
2 = 380 V/ 3 ~/60 Hz
M = 380-415 V/3 ~/50 Hz
Digit 9 = Coolant Fluid Type
W = Water
Digit 10 = Pump Configuration
- = Placeholder
Digit 11 = Pump Hp
- = Placeholder
Digit 12 = Fan Redundancy
1 = N
Digit 13 = Packaging
D = Domestic
E = Seaworthy (Export)
Table 2.2 Model Number Digit Definitions for Liebert XDU
2 Nomenclature and Components 7
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
Digit Description
Digit 14 = Agency
- = Placeholder
Digit 15 = Coil
- = Placeholder
Digit 16 = Placeholder
- = Placeholder
Digit 17 = Placeholder
- = Placeholder
Digit 18 = Placeholder
- = Placeholder
Digit 19 = Placeholder
- = Placeholder
Digit 20 = Placeholder
- = Placeholder
Digit 21 = Placeholder
- = Placeholder
Digit 22 = Special Feature Application Configuration
A = Standard configuration
S = SFA
Digit 23, 24, 25 = Factory Configuration
- = Placeholder
Table 2.2 Model Number Digit Definitions for Liebert XDU (continued)
2.2 Component Location
The unit component locations are described in the submittal documents included in the Submittal Drawings on pageīƒ„61 .
The following table lists the relevant documents by number and title.
Document Number Title
DPN004931 Component Location Diagram Liquid to Air 60 kW, 600 mm (24 in.) Model
Table 2.3 Component Location Drawings
2 Nomenclature and Components
8
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
2.3 Cooling Configuration
Figure 2.1 Liquid to Air Cooling System Overview
Item Description
1 XDU
2 Heat load
3 Pump
4 Heat exchanger
2 Nomenclature and Components 9
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
2 Nomenclature and Components
10
This page intentionally left blank
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
3 Pre-installation Preparationīƒ„andīƒ„Guidelines
NOTE: Before installing unit, determine whether any building alterations are required to run piping, wiring, and duct
work. Follow all unit dimensional drawings and refer to the submittal engineering dimensional drawings of individual
units for proper clearances.
Refer to Model Number Nomenclature on pageīƒ„7 and the appropriate submittal drawings to determine the type of system
being installed and anticipate building alterations, piping, and duct work needed.
The unit dimensions, pipe connection locations, and piping schematics are described in the submittal documents included in
the .
ā€¢Verify that the floor is level, solid, and sufficient to support the unit. See Table 3.2 below , for unit weights.
ā€¢Confirm that the room is properly insulated and has a sealed vapor barrier.
ā€¢For proper humidity control, keep outside or fresh air to an absolute minimum (less than 5% of total air circulated
in the room).
ā€¢Install the units as close as possible to the largest heat load.
ā€¢Allow at least the minimum recommended clearances for maintenance and service. See the appropriate
submittal drawings for dimensions.
ā€¢We recommend installing an under floor leak detection system. Contact your Vertiv representative for
information.
3.1 Planning Dimensions
The unit and floor stand dimensions are described in the submittal documents included in Submittal Drawings on pageīƒ„61 .
The following table lists the relevant documents by number and title.
Document Number Title
XDU
DPN004930 Cabinet Dimensional Data Liquid to Air 60kW, 600 mm (24 in.) Model
Floor Stand
DPN004933 Floorstand Dimensional Data 600 mm (24 in.) Model
Table 3.1 Dimension Planning Drawings
3.2 Unit Weights
Domestic Packaging Export Packaging
Dry Weight, lbīƒ„(kg)
Ship Weight, lbīƒ„(kg) Shipping Dimensions, in.īƒ„(mm) Ship Weight, lbīƒ„(kg) Shipping Dimensions, in.īƒ„(mm)
825 (374) 90īƒ„xīƒ„128īƒ„x 97 (2286īƒ„xīƒ„3251īƒ„x 2464) 915 (415) 90.5īƒ„x 128.5īƒ„xīƒ„99 (2299īƒ„xīƒ„3264īƒ„xīƒ„2515) 700 (318)
Table 3.2 Vertivā„¢ LiebertĀ® XDU Shipping Dimensions and Unit Weights
3 Pre-installation Preparationīƒ„andīƒ„Guidelines 11
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
3.3 Implementing a Hot Aisle/Cold Aisle Equipment Layout
Best practice is to place equipment racks in alternating rows of cold aisles and hot aisles. This is best accomplished when
planning the layout of the file server farm area. It is more difficult to accomplish when the computer room is already populated
with operating hardware.
In the cold aisle, the equipment racks are arranged face-to-face so the cooling air discharged from the cooling unit is
discharged up through perforated floor tiles, drawn into the face of the computer hardware and exhausted out the back of the
equipment rack into the adjacent hot aisles. Hot aisles are literally hot because the alternating cold and hot-aisle design
separates the source of cooling air from hot air discharge, which returns to the computer room cooling unit. No perforated
tiles should be placed in the hot aisles, which mixes hot and cold air, lowering the temperature of the air returning to the
cooling units and reducing usable capacity.
Figure 3.1 Vertivā„¢ LiebertĀ® XDU Layout in Hot/Cold Aisle Application
Item Description
1 Aisle pitch, 7īƒ„tiles, 14īƒ„ft. (4.3īƒ„m)
2 Cold aisle
3 Hot aisle
4 Front aisle, 4īƒ„ft. (1.2īƒ„m)
5 Rack, 42īƒ„in. (1067īƒ„mm)
6 Back aisle, 3īƒ„ft. (0.91 m)
7 XDU
8 Heat load
3 Pre-installation Preparationīƒ„andīƒ„Guidelines
12
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
4 Equipment Inspection and Handling
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury, or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from, or prepare the unit for installation.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only properly
trained and qualified personnel wearing appropriate, OSHA approved PPE should attempt to move, lift,
remove packaging from, or prepare the unit for installation.
NOTICE
Risk of passageway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a passageway while on or off the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to fit
below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors, and protected from dampness, freezing temperatures,
and contact damage.
Upon arrival of the unit and before unpacking:
ā€¢Verify that the labeled equipment matches the bill of lading.
ā€¢Carefully inspect all items for visible or concealed damage.
ā€¢Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or to your sales
representative
Equipment Recommended for Handling the Unit:
ā€¢Forklift
ā€¢Pallet jack
ā€¢Piano jacks
4 Equipment Inspection and Handling 13
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
4.1 Storing Before Installation
If storing the unit for long periods before installation:
ā€¢Keep the packaging on the unit and allow proper clearance around the unit to perform periodic inspections and
maintenance.
ā€¢Inspect the unit periodically for condensation inside the unit or other signs of other effects of the storage
environment.
ā€¢Rotate the fans and motor shaft by hand periodically for several revolutions. Look for signs of lubrication problem
or obstructions. Failure to regularly rotate fans on a stored unit will result in premature fan failure. This type of
failure is not covered by warranty.
ā€¢If storing at low temperatures, trapped moisture can collect on walls and electrical components.
ā€¢We recommend routine inspections and, if needed, install electric heaters near the unit to prevent condensation.
4.2 Packaging Material
All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
4.3 Handling the Unit While Packaged
Transport the unit with a forklift or pallet jack.
When using a forklift or pallet jack:
ā€¢Make sure that the forks (if adjustable) are spread to the widest allowable distance that will fit under the skid.
ā€¢Make sure the fork length is suitable for the skid length. Skid length is 60īƒ„inches (1524īƒ„mm).
ā€¢When moving the packaged unit, do not lift the unit any higher than 2īƒ„toīƒ„4īƒ„inches (51īƒ„toīƒ„102 mm). All personnel
except those moving the unit must be kept 12īƒ„feet (3.7īƒ„m) or more from the unit while it is being moved.
ā€¢If the unit must be lifted higher than 4īƒ„inches (102 mm), all personnel not directly involved in moving the unit
must be 20īƒ„feet (5īƒ„m) or farther from the unit.
4.4 Unpacking the Export Shipped Unit
1. Remove the metal clips (12 places typical) that secure the top panel of the crate to the side panels, see Figure 4.1
on the facing page .
2. Use a Phillips head screwdriver to remove all the wood screws (34 places typical) that secure the side panels
together and to the pallet, see Figure 4.1 on the facing page .
3. To remove the remaining packaging, start with Step 1 , of Unpacking the Domestic Shipped Unit on the facing
page .
4 Equipment Inspection and Handling
14
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
Figure 4.1 Metal Clips and Wood Screws on Crate
Item Description
1 Metal clips, typical 12 places
2 Wood screws, minimum 34 places
4.5 Unpacking the Domestic Shipped Unit
1. Use a 9/16-inch (14 mm) socket drive or wrench to remove the lag screws (four places typical) that secure the
ramp to the pallet, see Figure 4.2 on the next page . Set the ramps aside for use later when preparing to move
the unit from the pallet.
2. Remove the exterior packaging from around the unit.
NOTE: The bag may remain in place to protect from dust and to protect the unit panels, or it may be removed for
immediate installation.
3. Remove the bag from the unit when ready to move off the pallet and install the unit. See Removing Units from the
Pallet on pageīƒ„17 .
4 Equipment Inspection and Handling 15
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
Figure 4.2 Lag Screws that Secure Ramps
4 Equipment Inspection and Handling
16
Vertivā„¢ LiebertĀ® XDUīƒ„Installer/User Guide
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77

Vertiv Liebert® XDU060 Liquid to Air Heat Exchange for Chip Cooling User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI