  • Hello, I am an AI assistant and I have reviewed the Installation Guide for the Ampac Mounting base 45681-206AMP. This document provides instructions for installing the base, which is designed for use with specific detectors and control panels. It is also equipped with a feature that detects removal of the detector head. I am ready to answer your questions regarding the information in this document.
  • What type of detectors is this base compatible with?
    What type of control panel is required for this base?
    What happens if a detector is removed from the base?
Sav-Wire 2 Base
Installation Guide
General
The Sav-Wire 2 base, part no 45681-206AMP, is a mounting base for Series 65 smoke and heat
detectors and may be used only in association with a Sav-Wire-compatible re control panel. The
use of any other control panel will render the re detection system inoperable.
Detectors, call points and sounders are connected to the control panel by one pair of wires. In the
event of an alarm, polarity is reversed in order to activate the sounders without affecting the status of
the detectors.
Sav-Wire 2 bases incorporate a circuit which detects the removal of a detector head. If a detector is
removed from the base the control panel will give a fault signal.
Installation and Wiring
The base is installed in exactly the same way as a standard base. Shielded cables should be used.
Install in accordance with BS5839 Part 1.
It is essential to observe polarity when wiring a Sav-Wire 2 base. See wiring diagram overleaf.
39214-700/Rev/ B
Locking the detector
The detector head should be locked into the base, particularly if it is installed at a height less than
3m above the oor level. The reason for locking is to deny unauthorised persons access to the base
terminals in order to prevent base malfunction.
Lock the detector with a hexagonal driver.
Commissioning and Maintenance
Fit all detector heads before switching on power. Commission in accordance with BS5839 Part 1.
Routine maintenance should be carried out to BS5839 Part 1.
+
EOL
Resistor
(8.2kΩ)
From
control
panel
Note: This Sav-Wire 2 base may be used
only with compatible control panels
REMOTE LED
+ R
+ ve
–R
EARTH
+ R
– ve
+ ve
–R
EARTH
+ R
– ve
+ ve
–R
EARTH
– ve
Sav-Wire base wiring diagram
Ampac
7 Ledgar Road, Balcatta, Western Australia 6021
Telephone: +618 9201 6100 Fax: +618 9201 6101
Email: [email protected] Website: www.Ampac.net
Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo- re.co.uk Website: www.apollo- re.co.uk
/