Wolf CGB-50 is a gas-fired condensing boiler, designed for efficient and reliable heating of residential and commercial buildings. It features innovative maintenance technology, enabling easy access to internal components for regular servicing and maintenance. The boiler's compact design allows for flexible installation in various spaces, making it suitable for both new construction and renovation projects. With its high efficiency rating, the CGB-50 minimizes energy consumption and reduces operating costs.

Wolf CGB-50 is a gas-fired condensing boiler, designed for efficient and reliable heating of residential and commercial buildings. It features innovative maintenance technology, enabling easy access to internal components for regular servicing and maintenance. The boiler's compact design allows for flexible installation in various spaces, making it suitable for both new construction and renovation projects. With its high efficiency rating, the CGB-50 minimizes energy consumption and reduces operating costs.

Maintenance instructions
Gas red condensing boiler
CGB-35 Boiler
CGB-50 Boiler
Document no.: 3061491_0805 Subjecttotechnicalmodications.
GB
Wolf GmbH · PO Box 1380 · 84048 Mainburg · Tel. +49 8751/74-0 · Fax +49 8751/741600 · Internet: www.wolf-heiztechnik.de
2
3061491_0805
Index ................................................................................................................ Page
Safetyinstructions ...................................................................................................3
Maintenancesteps ............................................................................................ 4-13
Listofrequiredcomponents ..................................................................................14
Overviewofthestepstobetakenandthemaintenancereport ...................... 15-16
Index
With innovative maintenance technology
Maintenance position 2
Maintenance position 1
3
3061491_0805
The following symbols are used in this
document to highlight special information
and warnings. These important instructions
relate to personal safety and general ope-
rational safety of the equipment.
"Safety Instructions" must be strictly
followed to prevent the risk of endan-
gering or injuring persons or causing
material damage to the equipment.
Danger from 'live' electrical compon-
ents.
NB: Switch off the main ON/OFF switch
before removing any panels.
Never reach into electrical compon-
ents or touch any electrical contacts
when the main ON/OFF switch is tur-
ned on! Otherwise you risk a harmful
or potentially fatal electric shock.
A voltage will still be present at the
mains terminals when the main ON/
OFF switch is turned off.
"NB" indicates technical instructions
which you must observe to prevent
material losses and boiler malfunc-
tions.
NB
Safety instructions
General notes
Maintenanceworkmustonlybecarried
outbyaqualiedheatingcontractor.
Regular maintenance and the exclusi-
veuseoforiginalWolfsparepartsare
necessarypreconditionsfortrouble-free
operationandalongservicelife.
Wethereforerecommendyouarrangea
maintenancecontractwithalocalheating
contractor.
Fig.:Gascombinationvalve
Dangerfromelectriccurrent
Escapinggasmaycausepoisoningortheriskofexplosion
Fig.:Ignitiontransformer,highvoltageignitionelectrode,heat
exchanger.Riskfrom'live'electricalcomponents,riskofburning
fromhotcomponents
Fig.:Gasconnection:Escapinggasmaycausepoisoningor
theriskofexplosion
Fig.:Terminalbox:Dangerfromelectriccurrent
4
3061491_0805
Maintenance steps
Closethegastap.
The mains terminals are 'live' even
when the ON/OFF switch has been
switchedOFF.
•Disconnectthesystemfromthepowersupply.
•Pivotthecontrolunitliddown.
SwitchOFFthecondensingboileratthe
ON/OFFswitch.
•Unlockthecasinglidwiththel.h.andr.h.
rotatingbolts.Releasethebottomofthe
casinglidandunhookatthetop.
L.h.rotatingbolt
R.h.rotatingbolt
5
3061491_0805
Maintenance steps
•Releasetheelectricalcable(6x).
•Pivot the heat exchanger into the mainte-
nanceposition1.
Danger of burning
Severalcomponentsmaybehot.Letthesecool
downforapprox.halfanhourorweargloves.
•Crackopenthegassupplyconnection
andremovethegasket.
•Releasetheheatexchangerlockingspring.
6
3061491_0805
Maintenance steps
•Pullthemulti-purposebagovertheheatex-
changer.
•Visualburnerunitinspection.
Replacethemonitoringelectrode.
Checkandreplacetheignitionelectrode,if
necessary.
Monitoring
electrode
Ignitionelectrode
•Removetheburnerunitupwards.
•Opentheretainingtab.
7
3061491_0805
Maintenance steps
•Removethedisplacersegmentsoneafter
theother.
Clamp
Lowerdisplacer
section
Sealring
Upperdisplacer
section
•Removetheclamp.
•Hook the multi-purpose bag into the heat
exchanger.
•Releasetheretainerandpivottheheat
exchangerintothemaintenanceposition2.
8
3061491_0805
Maintenance steps
•Cleanthecondensatepan.
•Cleantheheatexchangerwithabrush.
•Visualuepipeinspection.
•Removethemulti-purposebag.
9
3061491_0805
Maintenance steps
•Lubricatetheheatexchangergasketsatthe
topandbottomwithsiliconegrease.
•Lubricatetheheatexchangerseat.
Never stretch gaskets.
NB
•Replacetheheatexchangergasketatthe
topandbottom.
10
3061491_0805
Maintenance steps
•Insertthedisplacerclamp.
•Replacethesealringandthelowerdis-
placersection.
•Tiptheheatexchanger(forward)toreturnit
tomaintenanceposition2.
Inserttheupperdisplacersectionasfarasit
willgointotheburner.
•Pivot the heat exchanger into the mainte-
nanceposition1,inserttheburnerunitand
threadintherearretainingspring.
Positionthefrontretainingspringwithakey
intoitsposition.
Assembly
11
3061491_0805
Maintenance steps
•Pivottheheatexchangerbackintothemain-
tenance position 1 and plug in the cables
(6x).
•Clicktheheatexchangerlockingspringback
intoplace.
•Releasetheretainerandpivottheheatex-
changerfullybackintotheboiler.
Check the lower heat exchanger
gasket.
NB
•Installthegasrestrictorandgasket.
CGB-35
Gas type Colour Diameter
H yellow 660
P red 510
CGB-50
Gas type Colour Diameter
H lightgrey 850
P lilac 620
12
3061491_0805
Maintenance steps
Checking the siphon
Ifrequired,cleanandre-ll.
Checkfortightt,
preventuegasfromescaping.
•Checkthebalanceduesystem.
•Ifyounoticealossofwater,checktheex-
pansionvesselinletpressureandincrease
it,ifrequired,to0.75bar.Theheatingcircuit
mustbeatzeropressure.
Thenllthesystem.
13
3061491_0805
Maintenance steps
Carrying out a ventilation test
CheckLAFforsoundness,iftheCO
2
>
0.2%.
"Fluegas“
testport
"Airsupply"
testport
Check gas train for soundness and
waterconnectionsforleaks.
• Fitthecasing.
Completion
Test run
•ResettheMCBs.
•Openthegastap.
•SwitchtheboilerON.
•Set the program selector to emissions test
mode.
Emissionstestmodeposition
Carrying out a ue gas test
Inemissionstestmode,enterthecaptured
valuesinthemaintenancereport.
Re-adjusttheCO
2
value,ifrequired.
(seeinstallationinstructions).
14
3061491_0805
List of required components
Checking control accessories
Fig.:DWT
Fig.:AWT
•ThedisplaymustshowBUSconnection .
BUSconnection
Maintenance requires the following:
1 MaintenancesetCGB-35/50 Partno.8611173
1 Cleaningset-supplementaryset Partno.2482875
1 Cleaningbrush Partno.2440053
1 TestequipmentforBImSchtest[Germany]
We recommend you have the following as part of your service kit:
1 Gasketset,uepipeDN80 Partno.8611184
1 Siliconegrease 10gtube partno.8602264
or400gtube partno.3500103
1 Burnergasket Partno.8611177
1 Returntemperaturesensor partno.8603036
1 Flowtemperaturesensor partno.8603038
1 Fluegastemperaturelimiter partno.8603058
1 Ignitionelectrode partno.8603061
1 Safetyvalvewithclip Partno.2070315
1 Gasketsettiltedbushow/return Partno.8611186
1 Protectiveanodeforenamelledcylinder
15
3061491_0805
Overview of the steps to be taken and the
maintenance report
No. Step Report item
1 SwitchOFFtheboiler,switchOFFtheemergencystopswitch
2 Closethegassupplyvalve,
3 Removethecasingandthecombustionchamberhousing
4 Undothegastting
5 Pulltheelectricalcablesoffthefan,sensorsandelectrodes
6 Removetheheatexchangerlid
7 Visualinspectionoftheburnerunit O
8 Checktheignitionelectrodesandreplaceifrequired O
9 Cleantheheatingwaterheatexchanger O
10 Cleanthecondensatepan O
11 Checkandreplacegaskets,ifrequiredandlubricatethereplace-
mentswithsiliconegrease
O
12 Rellgranulate,ifaneutralisingsystemisinstalled O
13 Checktheprotectiveanodeevery2yearsonenamelledcylinders
andreplace,ifnecessary
O
14 Assembletheboiler
15 Cleanandllthesiphon,installandcheckfortightt O
16 Checktheexpansionvesselincaseofwaterloss O
17 Openthegassupplyvalveandstarttheboiler
18 Gassoundnesstest O
19 Fluegassystemsoundnesstest O
20 Checktheignition O
21 Checktheinteractionwithcontrolaccessories O
22 Fluegastestinemissionstestmode O
23 Grossuegastemperature °C
24 Airsupplytemperature °C
25 Netuegastemperature °C
26 Carbondioxidecontent(CO2) %
27 oroxygencontent(O2) %
28 Carbonmonoxidecontent(CO) %
29 Fluegasloss %
Conrmmaintenance(companystamp,signature)
Date:
16
3061491_0805
Overview of the steps to be taken and the
maintenance report
No. Step Report item
1 SwitchOFFtheboiler,switchOFFtheemergencystopswitch
2 Closethegassupplyvalve,
3 Removethecasingandthecombustionchamberhousing
4 Undothegastting
5 Pulltheelectricalcablesoffthefan,sensorsandelectrodes
6 Removetheheatexchangerlid
7 Visualinspectionoftheburnerunit O
8 Checktheignitionelectrodesandreplaceifrequired O
9 Cleantheheatingwaterheatexchanger O
10 Cleanthecondensatepan O
11 Checkandreplacegaskets,ifrequiredandlubricatethereplace-
mentswithsiliconegrease
O
12 Rellgranulate,ifaneutralisingsystemisinstalled O
13 Checktheprotectiveanodeevery2yearsonenamelledcylinders
andreplace,ifnecessary
O
14 Assembletheboiler
15 Cleanandllthesiphon,installandcheckfortightt O
16 Checktheexpansionvesselincaseofwaterloss O
17 Openthegassupplyvalveandstarttheboiler
18 Gassoundnesstest O
19 Fluegassystemsoundnesstest O
20 Checktheignition O
21 Checktheinteractionwithcontrolaccessories O
22 Fluegastestinemissionstestmode O
23 Grossuegastemperature °C
24 Airsupplytemperature °C
25 Netuegastemperature °C
26 Carbondioxidecontent(CO2) %
27 oroxygencontent(O2) %
28 Carbonmonoxidecontent(CO) %
29 Fluegasloss %
Conrmmaintenance(companystamp,signature)
Date:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Wolf CGB-50 Maintenance Instructions Manual

Type
Maintenance Instructions Manual
This manual is also suitable for

Wolf CGB-50 is a gas-fired condensing boiler, designed for efficient and reliable heating of residential and commercial buildings. It features innovative maintenance technology, enabling easy access to internal components for regular servicing and maintenance. The boiler's compact design allows for flexible installation in various spaces, making it suitable for both new construction and renovation projects. With its high efficiency rating, the CGB-50 minimizes energy consumption and reduces operating costs.