WIKA Safety manual pressure transmitter, model S-20
14082128.02 06/2014 GB/D/F/E
2.8.3 Values for the operating voltage at connection U
B+
■
The values for the maximum and minimum permissible load as a function of the operating voltage must also be
observed. See table 2-1: Parameters
■
The power supply for the pressure transmitter must be made via an energy-limited electrical circuit in accordance
with section 9.3 of UL/EN/IEC 61010-1, or an LPS to UL/EN/IEC 60950-1, or (for North America) class 2 in
accordance with UL1310/UL1585 (NEC or CEC). The power supply must be suitable for operation above 2,000 m
should the pressure transmitter be used at this altitude.
WARNING!
The operator must ensure that the operating voltage is within the permissible range. The power supply
should never drop below the minimum nor exceed the maximum. Otherwise this could lead to an impair-
ment of the safety function.
2.9 EMC
The EN 61326-3-1:2008 standard is applied.
WARNING!
In accordance with EN 61326-3-1:2008, for testing in accordance with IEC 61000-4-5, a test level of 2
kV is required. The interference immunity of the S-20 is 1 kV. To achieve a higher interference immunity,
external protective measures must be provided.
2.10 Commissioning of the pressure transmitter
The correct operation must be checked with commissioning.
WARNING!
After commissioning the pressure transmitter, a functional test of the entire safety function (safety loop)
should be initiated, in order to test whether the safety function of the system is ensured. Function tests
are intended to demonstrate the correct function of the whole safety-related system, including all instru-
ments (sensor, logic unit, actuator).
Any mechanical damage of the pressure transmitter at the installation point must be prevented.