OEM pressure transmitters, model OT-1
OEM pressure transmitter, model OT-1
OEM-Druckmessumformer, Typ OT-1
Transmetteur de pression OEM, type OT-1
Transmisor de presión OEM, modelo OT-1
2 WIKA operating instructions OEM pressure transmitter, model OT-1
EN
DE
2127027.03 10/2019 EN/DE/FR/ES
FR
ES
© 2006 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA
®
is a registered trademark in various countries.
WIKA
®
ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Lire le mode d'emploi avant de commencer toute opération !
A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo!
¡Guardar el manual para una eventual consulta!
Operating instructions model OT-1 Page 3 - 16
Betriebsanleitung Typ OT-1 Seite 17 - 30
Mode d’emploi type OT-1 Page 31 - 44
Manual de instrucciones modelo OT-1 Página 45 - 57
3WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
Contents
1. General information 4
2. Safety 5
3. Specications 7
4. Design and function 8
5. Transport, packaging and storage 9
6. Commissioning, operation 9
7. Maintenance and cleaning 12
8. Faults 13
9. Dismounting, return and disposal 14
Declarations of conformity can be found online at www.wika.com
Contents
4 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
1. General information
1. General information
The pressure transmitter described in the operating instructions has been designed and manufactured using state-
of-the-art technology. All components are subject to stringent quality and environmental criteria during production.
Our management systems are certied to ISO 9001 and ISO 14001.
These operating instructions contain important information on handling the instrument. Working safely requires that
all safety instructions and work instructions are observed.
Observe the relevant local accident prevention regulations and general safety regulations for the instrument's range
of use.
The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and
readily accessible to skilled personnel at any time.
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.
The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended
use, non-compliance with these operating instructions, assignment of insuciently qualied skilled personnel or
unauthorised modications to the instrument.
The general terms and conditions contained in the sales documentation shall apply.
Subject to technical modications.
Further information:
- Internet address: www.wika.com / www.wika.de
- Relevant data sheet: PE 81.42
- Application consultant: Tel.: +49 9372 132-0
Fax: +49 9372 132-406
5WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
1. General information/2. Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light injuries or damage to equipment or the
environment, if not avoided.
Information
... points out useful tips, recommendations and information for ecient and trouble-free operation.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure that the appropriate pressure transmitter has been
selected in terms of measuring range, design and specic measuring conditions.
Non-observance can result in serious injury and/or damage to the equipment.
WARNING!
Open the connections only after the system has been depressurised.
Observe the working conditions in accordance with chapter 3 “Specications”.
Always operate the pressure transmitter within the overpressure safety range.
Further important safety instructions can be found in the individual chapters of these operating instructions.
2.1 Intended use
The pressure transmitter is used to convert pressure into an electrical signal.
The instrument has been designed and built solely for the intended use described here, and may only be used
accordingly.
6 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
2. Safety
The technical specications contained in these operating instructions must be observed. Improper handling or opera-
tion of the instrument outside of its technical specications requires the instrument to be taken out of service immedi-
ately and inspected by an authorised WIKA service engineer.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
2.2 Personnelqualication
WARNING!
Riskofinjuryshouldqualicationbeinsucient!
Improper handling can result in considerable injury and damage to equipment.
The activities described in these operating instructions may only be carried out by skilled personnel who
have the qualications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training, knowledge of measurement
and control technology and on their experience and knowledge of country-specic regulations, current standards and
directives, are capable of carrying out the work described and independently recognising potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive media.
2.3 Special hazards
WARNING!
For hazardous media such as oxygen, acetylene, ammable or toxic gases or liquids, and refrigeration
plants, compressors, etc., in addition to all standard regulations, the appropriate existing codes or
regulations must also be followed.
WARNING!
Residual media in dismounted pressure transmitters can result in a risk to persons, the environment and
equipment.
Take sucient precautionary measures.
7WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
2.Safety/3.Specications
2.4 Labelling, safety marking
Product label
If the serial number becomes illegible due to mechanical damage or overpainting, traceability will no longer be possible.
3. Specications
Specications
Measuring range [bar] 6 10 16 25 40 60 100 160 250 400 600
Overpressure limit [bar] 20 20 32 50 80 120 200 320 500 800 1,200
Burst pressure [bar] 100 100 160 250 400 550 800 1,000 1,200 1,700 2,400
Output signals and power supply Output signal Power supply U
+
4 ... 20 mA, 2-wire DC 8 ... 36 V
DC 1 ... 6 V, 3-wire DC 9 ... 36 V
DC 1 ... 5 V, 3-wire DC 8 ... 36 V
DC 0 ... 10 V, 3-wire DC 14 ... 36 V
DC 0.5 ... 4.5 V, ratiometric DC 5 ±0.5 V
Insulation voltage DC 500 V
Ingress protection IP67, using mating connectors with the corresponding ingress protection
Product no.
Customer-specic text
ID (production batch)
8 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
3.Specications/4.Designandfunction
Specications
Permissible temperature ranges
Medium -40 ... +125 °C
Ambient -40 ... +100 °C, for cable outlet a limited temperature range of -40 ... +90 °C applies
Storage -40 ... +120 °C, for cable outlet a limited temperature range of -40 ... +90 °C applies
Rated temperature range 0 ... +80 °C
Weight approx. 70 g
CE conformity
EMC directive, EN 61326 emission (group 1, class B) and interference immunity (industrial application)
Pressure equipment directive
RoHS directive
For special model numbers, e.g. OT-10000, please note the specications stated on the delivery note.
For further specications see WIKA data sheet PE 81.42 and the order documentation.
In accordance with EN 61326-1, in case of outdoor installations, faults caused by surge voltages must be considered.
To protect the instrument, it must be connected using a shielded cable. The shield of the cable must be connected on
at least one side to ground or a suitable reference potential.
Alternatively, a suitable external measure to protect against surge voltages has to be provided.
4. Design and function
4.1 Description
The prevailing pressure is measured at the sensor element through the deformation of a diaphragm. By supplying
power, this deformation of the diaphragm is converted into an electrical signal. The output signal from the pressure
transmitter is amplied and standardised.
4.2 Scope of delivery
Cross-check scope of delivery with delivery note.
9WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
5. Transport, packaging and storage/6. Commissioning, operation
5. Transport, packaging and storage
5.1 Transport
Check the pressure transmitter for any damage that may have been caused during transportation.
Obvious damage must be reported immediately.
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for
repair).
5.3 Storage
Permissible conditions at the place of storage:
Storage temperature: -40 ... +120 °C, for cable outlet a limited temperature range of -40 ... +90 °C applies
WARNING!
Before storing the instrument (following operation), remove any residual media. This is of particular
importance if the medium is hazardous to health, e.g. caustic, toxic, carcinogenic, radioactive, etc.
6. Commissioning, operation
CAUTION!
Prior to commissioning, the pressure transmitter must be subjected to a visual inspection.
Leaking uid is indicative of damage.
Only use the pressure transmitter if it is in perfect condition with respect to safety.
CAUTION!
The pressure transmitter must not be exposed to any condensation.
10 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
6. Commissioning, operation
Correct sealing of the process connections with parallel
threads at the sealing face
must be made using suita-
ble at gaskets, sealing rings or WIKA prole sealings.
For sealing process connections with tapered threads,
the sealing must be made in the threads using additional
sealing material, e.g. PTFE tape (EN 837-2).
6.1 Mechanical mounting
The sealing faces at the instrument have to be undamaged and clean.
When screwing the instrument in, the force required to do this must not be
applied through the case, but only through the spanner ats provided for this
purpose, and using a suitable tool.
When screwing in, do not cross the threads.
For information on tapped holes and welding sockets, see Technical
information IN 00.14 at www.wika.com.
Sealing the process connection
For further information on seals see WIKA data sheet AC 09.08 or at www.wika.com.
Spanner ats
per EN 837
per DIN EN ISO 1179-2
(formerly DIN 3852-E)
NPT, R and PT
Parallel threads
Tapered threads
11WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
6. Commissioning, operation
6.2 Electrical mounting
6.2.1 Connection assembly
Use the pressure transmitter with shielded cable. The cable shield must be grounded, if the cable is longer than
30 m or leaves the building.
Use a cable with suitable characteristics for the particular operating conditions.
For cable variants, strain relief must be employed.
Cable with ventilation tubes must be vented to atmosphere.
The instrument must be grounded via the process connection.
Select a cable diameter that matches the cable gland of the plug. Make sure that the cable gland of the mounted
plug has a tight t and that the seals are present and undamaged. Tighten the threaded connection and check that
the seal is correctly seated, in order to ensure the ingress protection.
For cable outlets, make sure that no moisture enters at the cable end.
This equipment is intended for operation with low voltages, which are separated from the power supply or voltages
of greater than AC 50 V or DC 120 V. Preferably, a connection to an SELV circuit is recommended, or alternatively to
circuits with a dierent protective measure in accordance with IEC 60364-4-41.
6.2.2 Connection diagrams
Circular connector M12 x 1 (4-pin)
2-wire 3-wire
4
3
1
2
U
+
1 1
U
-
3 3
S
+
- 4
U+ Positive power supply
U- Negative power supply, reference potential
S+ Positive output terminal
2-wire The two connection lines are used for the voltage supply.
The measurement signal also provides the supply current.
3-wire Two connection lines are used for the voltage supply.
One connection line is used for the measurement signal.
Cable outlet
2-wire 3-wire
U
+
brown brown
U
-
green blue
S
+
- white
Metri-Pack series 150 (3-pin)
2-wire 3-wire
U
+
B B
U
-
A A
S
+
- C
12 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
6. Commissioning, operation/7. Maintenance and cleaning
6.2.3 Setting up a voltage supply
The permissible power supply depends on the corresponding output signal.
Output signal Power supply U
+
Maximum load R
A
inΩ
4 ... 20 mA, 2-wire DC 8 ... 36 V R
A
≤ (power supply – 8 V)/0.02 A
DC 1 ... 6 V, 3-wire DC 9 ... 36 V R
A
> 2.5 kΩ
DC 1 ... 5 V, 3-wire DC 8 ... 36 V R
A
> 2.5 kΩ
DC 0 ... 10 V, 3-wire DC 14 ... 36 V R
A
> 5 kΩ
DC 0.5 ... 4.5 V, ratiometric DC 5 ±0.5 V R
A
> 4.5 kΩ
7. Maintenance and cleaning
7.1 Maintenance
This pressure transmitter is maintenance-free.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
Before cleaning, correctly disconnect the pressure transmitter from the pressure supply, switch it o and
disconnect it from the power supply.
Electrical connections must not come into contact with moisture.
Wash or clean the dismounted instrument before returning it, in order to protect persons and the
environment from exposure to residual media.
Residual media in dismounted pressure transmitters can result in a risk to persons, the environment and
equipment. Take sucient precautionary measures.
Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm of the process
connection.
For information on returning the instrument see chapter 9.2 “Return”.
13WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
8. Faults
8. Faults
In the event of any faults, rst check whether the pressure transmitter is mounted correctly, mechanically and electrically.
Faults Causes Measures
No output signal Cable break Check the continuity
Deviating zero point signal Overpressure limit exceeded Observe the permissible overpressure safety (see
chapter 3 “Specications”)
Deviating zero point signal Operating temperature too high/low Observe the permissible temperatures (see chapter 3
“Specications”)
Constant output signal upon
change in pressure
Mechanical overload caused by
overpressure
Replace pressure transmitter; if it fails repeatedly, contact
the manufacturer
Signal span too small Mechanical overload caused by
overpressure
Replace pressure transmitter; if it fails repeatedly, contact
the manufacturer
Signal span varies EMC interference sources in
the environment; for example,
frequency converter
Shield the pressure transmitter; cable shield; remove
source of interference
Signal span varies/inaccurate Operating temperature too high/low Observe the permissible temperatures (see chapter 3
“Specications”)
Signal span drops/too small Signal span drops/too small Contact manufacturer and replace pressure transmitter
If complaint is unjustied, we will charge you the complaint processing fees.
CAUTION!
If faults cannot be eliminated by means of the measures listed above, shut down the instrument
immediately, and ensure that pressure and/or signal are no longer present, and secure the instrument from
being put back into operation inadvertently. In this case, contact the manufacturer. If a return is needed,
please follow the instructions given in chapter 9.2 "Return".
14 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
EN
9. Dismounting, return and disposal
9. Dismounting, return and disposal
WARNING!
Residual media in dismounted pressure transmitters can result in a risk to persons, the environment and
equipment. Take sucient precautionary measures.
9.1 Dismounting
Only disconnect the pressure transmitter once the system has been depressurised!
9.2 Return
WARNING!
Strictly observe the following when shipping the instrument:
All instruments delivered to WIKA must be free from any kind of hazardous substances (acids, bases,
solutions, etc.).
When returning the instrument, use the original packaging or a suitable transport package.
Information on returns can be found under the heading “Service” on our local website.
9.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance
with the country-specic waste disposal regulations.
Do not dispose of with household waste. Ensure a proper disposal in accordance with national
regulations.
51WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
52 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.03 10/2019 EN/DE/FR/ES
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
63911 Klingenberg • Germany
Tel. +49 9372 132-0
Fax +49 9372 132-406
www.wika.de
WIKA subsidiaries worldwide can be found online at www.wika.com
WIKA Niederlassungen weltweit nden Sie online unter www.wika.de
La liste des liales WIKA dans le monde se trouve sur www.wika.fr
sucursales WIKA en todo el mundo puede encontrar en www.wika.es
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

WIKA OT-1 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI