PRE-OPERATION INSTRUCTIONS
INSTALLATION
WIRING
INVERTER SETTING
FL REMOTE COMMUNICATION
FUNCTION
CYCLIC TRANSMISSION
DESCRIPTION AND CORRECTIVE
ACTION OF FAULT INDICATION
MESSAGE TRANSMISSON
TROUBLESHOOTING
A-1
Thank you for choosing this Mitsubishi Electric Inverter plug-in
option.
This Instruction Manual gives handling information and
precautions for use of this equipment. Incorrect handling might
cause an unexpected fault. Before using the equipment, please
read this manual carefully to use the equipment to its optimum.
Please forward this manual to the end user.
1. Electric Shock Prevention
This section is specifically about
safety matters
Do not attempt to install, operate, maintain or inspect this
product until you have read through this Instruction Manual and
appended documents carefully and can use the equipment
correctly. Do not use this product until you have a full
knowledge of the equipment, safety information and
instructions.
In this Instruction Manual, the safety instruction levels are
classified into "WARNING" and "CAUTION".
Incorrect handling may cause
hazardous conditions, resulting in
death or severe injury.
Incorrect handling may cause
hazardous conditions, resulting in
medium or slight injury, or may cause
only material damage.
The level may even lead to a serious
consequence according to conditions. Both instruction levels
must be followed because these are important to personal
safety.
WARNING
CAUTION
CAUTION
SAFETY INSTRUCTIONS
WARNING
While the inverter power is ON, do not remove the front cover
or the wiring cover. Do not run the inverter with the front
cover or the wiring cover removed. Otherwise you may
access the exposed high voltage terminals or the charging
part of the circuitry and get an electric shock.
Even if power is OFF, do not remove the front cover except for
wiring or periodic inspection. You may accidentally touch the
charged inverter circuits and get an electric shock.
Before wiring or inspection, power must be switched OFF. To
confirm that, LED indication of the operation panel must be
checked. (It must be OFF.) Any person who is involved in
wiring or inspection shall wait for at least 10 minutes after the
power supply has been switched OFF and check that there
are no residual voltage using a tester or the like. The
capacitor is charged with high voltage for some time after
power OFF, and it is dangerous.
Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work.
The plug-in option must be installed before wiring. Otherwise,
you may get an electric shock or be injured.
Do not touch the plug-in option or handle the cables with wet
hands. Otherwise you may get an electric shock.
Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Otherwise you may get an electric
shock.
A-2
2. Injury Prevention
3. Additional Instructions
Also the following points must be noted to prevent an accidental
failure, injury, electric shock, etc.
1) Transportation and mounting
2) Trial run
3) Usage
4) Maintenance, inspection and parts replacement
5) Disposal
6) General instruction
CAUTION
The voltage applied to each terminal must be the ones
specified in the Instruction Manual. Otherwise burst, damage,
etc. may occur.
The cables must be connected to the correct terminals.
Otherwise burst, damage, etc. may occur.
Polarity must be correct. Otherwise burst, damage, etc. may
occur.
While power is ON or for some time after power-OFF, do not
touch the inverter as they will be extremely hot. Doing so can
cause burns.
CAUTION
Do not install or operate the plug-in option if it is damaged or
has parts missing.
Do not stand or rest heavy objects on the product.
The mounting orientation must be correct.
Foreign conductive objects must be prevented from entering
the inverter. That includes screws and metal fragments or
other flammable substances such as oil.
CAUTION
Before starting operation, each parameter must be confirmed
and adjusted. A failure to do so may cause some machines to
make unexpected motions.
WARNING
Do not modify the equipment.
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the inverter.
CAUTION
Static electricity in your body must be discharged before you
touch the product. Otherwise the product may be damaged.
CAUTION
Do not test the equipment with a megger (measure insulation
resistance).
CAUTION
This inverter plug-in option must be treated as industrial
waste.
Many of the diagrams and drawings in this Instruction Manual
show the inverter without a cover or partially open for
explanation. Never operate the inverter in this manner. The
cover must be reinstalled and the instructions in the inverter
manual must be followed when operating the inverter.
I
— CONTENTS —
1 PRE-OPERATION INSTRUCTIONS 1
1.1 Inverter model ....................................................................................................................................1
1.2 Unpacking and product confirmation ..............................................................................................2
1.2.1 Product confirmation.......................................................................................................................................2
1.2.2 SERIAL check ................................................................................................................................................3
1.3 Parts....................................................................................................................................................8
1.4 LED status ..........................................................................................................................................9
1.4.1 Device status LED (DEV), remote status LED (RMT) ..................................................................................10
1.4.2 Transmitting (TX)/receiving (RX) LED ..........................................................................................................11
1.4.3 Communication set status LED (CHG)......................................................................................................... 11
1.5 Specifications...................................................................................................................................12
1.5.1 Inverter option specifications ........................................................................................................................12
1.5.2 Communication specifications ...................................................................................................................... 12
2INSTALLATION 13
2.1 Pre-installation instructions ...........................................................................................................13
2.2 Installation of the communication option LED display cover .....................................................14
2.3 Installation procedure .....................................................................................................................15
2.4 Node address setting ......................................................................................................................17
3WIRING 18
3.1 Connection to network ....................................................................................................................18
3.2 Cable specifications ........................................................................................................................19
3.3 Precautions for system configuration ...........................................................................................19
3.4 Wiring................................................................................................................................................20
II
4 INVERTER SETTING 22
4.1 Parameter list ...................................................................................................................................22
4.2 Operation mode setting...................................................................................................................26
4.2.1 Operation mode indication............................................................................................................................26
4.2.2 Operation mode switchover method.............................................................................................................27
4.3 Selection of control source for the Network operation mode .....................................................32
4.4 Operation at communication error occurrence ............................................................................34
4.4.1 Operation selection at communication error occurrence (Pr. 501, Pr. 502) .................................................34
4.4.2 Fault and measures......................................................................................................................................36
4.5 Inverter reset ....................................................................................................................................38
4.6 Frequency and speed conversion specifications.........................................................................39
5 FL REMOTE COMMUNICATION FUNCTION 40
5.1 Functions..........................................................................................................................................40
5.1.1 Output from the inverter to the network ........................................................................................................ 40
5.1.2 Input to the inverter from the network........................................................................................................... 41
5.2 Types of data communication ........................................................................................................42
6 CYCLIC TRANSMISSION 43
6.1 Common memory ............................................................................................................................44
6.1.1 Common memory area 1..............................................................................................................................46
6.1.2 Common memory area 2..............................................................................................................................47
6.2 Output data (master to inverter) .....................................................................................................50
6.2.1 Control input command ................................................................................................................................51
6.2.2 Set frequency ...............................................................................................................................................53
6.3 Input data (inverter to master) ........................................................................................................54
6.3.1 Inverter status monitor..................................................................................................................................55
III
6.3.2 Fault code.....................................................................................................................................................57
6.3.3 Life/warning ..................................................................................................................................................57
6.3.4 Output frequency monitor ............................................................................................................................. 59
6.3.5 Output current monitor.................................................................................................................................. 59
7 MESSAGE TRANSMISSON 60
7.1 Error response at word block read/write .......................................................................................63
7.2 Word block read/write .....................................................................................................................64
7.2.1 Virtual address space of word block read/write ............................................................................................65
7.2.2 Product information ......................................................................................................................................66
7.2.3 Operation mode............................................................................................................................................68
7.2.4 Inverter status...............................................................................................................................................69
7.2.5 Set frequency ...............................................................................................................................................70
7.2.6 Inverter monitor ............................................................................................................................................ 71
7.2.7 Parameter.....................................................................................................................................................74
7.2.8 Calibration parameters .................................................................................................................................76
7.2.9 Fault record ..................................................................................................................................................78
7.3 Network parameter read..................................................................................................................84
7.4 Log data read ...................................................................................................................................87
7.5 Log data clear...................................................................................................................................90
7.6 Profile read .......................................................................................................................................91
7.7 Message loopback ...........................................................................................................................95
8 DESCRIPTION AND CORRECTIVE ACTION OF FAULT INDICATION 96
9 TROUBLESHOOTING 97
APPENDIX 99
MEMO
1
1
1 PRE-OPERATION INSTRUCTIONS
1.1 Inverter model
The inverter model, 55K and 75K stated in this Instruction Manual differs according to each -NA, -EC, -
CH(T) versions. Refer to the following correspondence table for each inverter model. (Refer to the Instruction
Manual of each inverter for the inverter model.)
For example, "for the 75K or higher" indicates "for the FR-A740-01440-NA or higher" in the case of FR-
A740 of NA version.
NA EC CH
F700
FR-F720(P)-55K FR-F720-02330-NA 
FR-F720(P)-75K FR-F720-03160-NA 
FR-F740(P)-55K FR-F740-01160-NA FR-F740-01160-EC FR-F740-55K-CH(T)
FR-F740(P)-75K FR-F740-01800-NA FR-F740-01800-EC FR-F740-S75K-CH(T)
A700
FR-A720-55K FR-A720-02150-NA 
FR-A720-75K FR-A720-02880-NA 
FR-A740-55K FR-A740-01100-NA FR-A740-01800-EC FR-A740-55K-CHT
FR-A740-75K FR-A740-01440-NA FR-A740-02160-EC FR-A740-75K-CHT
2
PRE-OPERATION INSTRUCTIONS
1.2 Unpacking and product confirmation
Take the plug-in option out of the package, check the product name, and confirm that the product is as you
ordered and intact.
This product is a plug-in option for the FR-A700/F700(P) series inverter.
1.2.1 Product confirmation
Check the enclosed items.
Plug-in option
......................................... 1
Mounting screw (M3 6mm)
............ 2 (Refer to page 15.)
Hex-head screw for option
mounting (5.5mm)
............. 1 (Refer to page 15.)
Communication option LED
display cover
............ 1 (Refer to page 14.)
5.5mm
3
PRE-OPERATION INSTRUCTIONS
1
1.2.2 SERIAL check
The plug-in option is compatible with the inverter having the following SERIAL or later.
Check the SERIAL indicated on the inverter rating plate or package.
SERIAL check
Refer to the inverter manual for the location of the rating plate.
(1) PU/NET operation switchover (X65 signal) specification
The inverters with the following SERIAL are operated in the PU/NET operation switchover (X65 signal)
specification when connected with FR-A7NF.
FR-A700 series
FR-F700 series Japanese specification
Regardless of their SERIAL, all FR-F700P series inverters are operated with the PU operation interlock (X12
signal) specification.
Rating plate example

SERIAL
Symbol Year Month Control number
TCAG TC number
The SERIAL consists of one symbol, two characters indicating production year and month, and six characters indicating control number.
The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (November), or Z (December.)
Model SERIAL
FR-A720-(-NA),
FR-A740-
(-NA)(-EC)(-CHT),
FR-CA70-EC, FR-CA70-ECT
7X to
03
Model SERIAL
FR-F720-0.75K to 110K,
FR-F740-0.75K to 560K
91 or later
4
PRE-OPERATION INSTRUCTIONS
FR-F700 series NA specification
FR-F700 series EC specification
FR-F700 series CHT specification
Model SERIAL
FR-F720-00046 to 04750-NA,
FR-F740-00023 to 12120-NA
91 or later
Model SERIAL
FR-F740-00023 to 00620-EC,
FR-CF70-EC, FR-CF70-ECT
95 or later
Model SERIAL
FR-F740-0.75K to 55K-CHT,
FR-F740-S75K to S630K-CHT
93 or later
5
PRE-OPERATION INSTRUCTIONS
1
(2) PU operation interlock (X12 signal) specification
The FR-F700P series and the inverters with the following TC and SERIAL are operated in the PU operation
interlock (X12 signal) specification when connected with FR-A7NF.
FR-A700 series Japanese and NA specification
Model SERIAL
FR-A720- (-NA)
FR-A740-
 (-NA)
04
REMARKS
The following table shows the operation mode switching specifications of the FR-A700 series inverters
with the FR-A7NF. The specification depends on a combination of both SERIALs. Check the board of the
FR-A7NF for its version and the SERIAL.
Refer to chapter 4 or later for the differences between the PU/NET operation switchover (X65 signal)
specification and the PU operation interlock (X12 signal) specification.
FR-A7NF SERIAL of the FR-A700 series inverter
Version
SERIAL
7X to 03
04 or later
A
03 or earlier
PU/NET operation switchover (X65 signal)
specification
PU/NET operation switchover (X65 signal)
specification
B
04 or later
PU/NET operation switchover (X65 signal)
specification
PU operation interlock (X12 signal)
specification

Symbol Year Month Control number
The SERIAL consists of one symbol, two characters indicating production year and month, and three characters indicating control number.
The last digit of the production year is indicated as the Year, and the Month is indicated by 1 to 9, X (October), Y (November), or Z (December.)
6
PRE-OPERATION INSTRUCTIONS
FR-A700 series EC specification
Model TC number SERIAL
FR-A740-00023 to 00052-EC
TCAG7 C0 or later
TCAG8 A0 or later
FR-A740-00083/00126-EC
TCAG7 C0 or later
TCAG8 B0 or later
FR-A740-00170/00250-EC
TCAG7 Y0 or later
TCAG8 Z0 or later
FR-A740-00310/00380-EC
TCAG7 Z0 or later
TCAG8 B0 or later
FR-A740-00470/00620-EC
TCAG7 Y0 or later
TCAG8 Z0 or later
FR-CA70-EC
(Control unit)
TCAG7 V0
 or later
TCAG8 E0 or later
FR-CA70-ECT
(Control unit)
TCAG7 S0 or later
TCAG8 E0 or later
7
PRE-OPERATION INSTRUCTIONS
1
FR-A700 series CHT specification
Model TC number SERIAL
FR-A740-0.4K to 1.5K-CHT
TCAG7 A0 or later
TCAG8 Y0 or later
FR-A740-2.2K/3.7K-CHT
TCAG7 A0 or later
TCAG8 Z0 or later
FR-A740-5.5K/7.5K-CHT
TCAG7 W0 or later
TCAG8 X0 or later
FR-A740-11K/15K-CHT
TCAG7 X0 or later
TCAG8 Z0 or later
FR-A740-18.5/22K-CHT
TCAG7 W0 or later
TCAG8 X0 or later
FR-A740-30K to 45K-CHT
TCAG7 X0
 or later
TCAG8 V0 or later
FR-A740-55K-CHT
TCAG7 W0 or later
TCAG8 V0 or later
FR-A740-75K/90K-CHT
TCAG7 V0 or later
TCAG8 F0 or later
FR-A740-110K-CHT
TCAG7 X0 or later
TCAG8 G0 or later
FR-A740-132K-CHT
TCAG7 W0 or later
TCAG8 G0 or later
FR-A740-160K/185K-CHT TCAG7 W0 or later
FR-A740-220K to 280K-CHT TCAG7 V0
 or later
FR-A740-315K/355K-CHT TCAG7 U0 or later
FR-A740-400K to 500K-CHT TCAG7 R0 or later
8
PRE-OPERATION INSTRUCTIONS
1.3 Parts
Front view Rear view
0
9
8
7
6
5
4
3
2
1
X10
SW1
0
9
8
7
6
5
4
3
2
1
X1
SW2
SW3
D1 D2
D3 D4
FR-A7NF
SERIAL
B
Ver.
LED (operation status indication)
Lit/flicker/OFF of the LED indicate inverter
operation status.
Mounting
hole
Connector
Connect to the inverter option connector.
Node address switch
Set the node address.
Mounting
hole
Mounting
hole
Connector for communication
Connect to the network by
connecting a FL-net dedicated
cable.
Switch for manufacturer
setting
Do not change from
initially-set status (OFF).
SW3
O
N
2
L
Version information
Check the version of
the FR-A7NF.
SERIAL
Check the SERIAL
of the FR-A7NF.
9
PRE-OPERATION INSTRUCTIONS
1
1.4 LED status
Each LED indicates the operating status of the option unit and network according to the indication status.
0
9
8
7
6
5
4
3
2
1
X10
SW1
0
9
8
7
6
5
4
3
2
1
X1
SW2
D1 D2
D3 D4
FR-A7NF
D1 D2
S
D3 D4
D1: Communication set status LED (CHG)
D2: Device status LED (DEV)
D3: Reception/transmission LED (TX/RX)
D4: Remote status LED (RMT)
10
PRE-OPERATION INSTRUCTIONS
1.4.1 Device status LED (DEV), remote status LED (RMT)
LED Status
Node Status Description
DEV RMT
Power is OFF The inverter power is OFF.
Hardware fault
· Node address is out of range (other than 1 to 64).
· Optional board fault
· When mounted to the inverter which is not compatible with
the FR-A7NF (Refer to page 3 for the inverter which is
compatible with the FR-A7NF)
· When a contact fault occurs in an option connector between
the inverter and communication option.
FL remote network is not connected
Although hardware is normal, it is not connected to the FL
remote network.
FL remote network at a remote stop
It is correctly set to connect to the FL remote network and
waiting for remote I/O control.
FL remote network
during remote connection
processing
Although remote I/O control started, initial processing is in
progress.
Master is not present When the master is disconnected from FL remote network.
FL remote network
during remote operation
During remote I/O control
Own node is disconnected When the own node is disconnected from FL remote network.
11
PRE-OPERATION INSTRUCTIONS
1
:OFF, : red is lit, : green is lit, :red is flickering, : green is flickering,
: red and green are alternately flickering
1.4.2 Transmitting (TX)/receiving (RX) LED
:OFF, : green is lit
1.4.3 Communication set status LED (CHG)
:OFF, : red is flickering
Setting error
Although it is connected to the FL remote, setting error is found.
(When the slave is not the one the master is expected.)
Duplicate node When node address is duplicate with other node address
LED Status Node Status Description
Not transmitting (TX)/not receiving
(RX)
———
Transmitting (TX)/receiving (RX) Flickers at high speed during continuous transmitting/receiving
LED Status Node Status Description
Communication setting is not changed
———
Communication setting is changed
The red LED flickers when the applied setting and the node
address switch setting differ. The setting value of the node
address switch is applied by re-powering ON the inverter in this
status, then communication setting status LED turns OFF.
LED Status
Node Status Description
DEV RMT
12
PRE-OPERATION INSTRUCTIONS
1.5 Specifications
1.5.1 Inverter option specifications
1.5.2 Communication specifications
Power supply Supplied from the inverter
Type Inverter plug-in option (can be mounted/dismounted to/from the inverter front face)
FL-net dedicated cable Refer to page 19
Maximum number of
connectable inverters
64 units maximum
Communication speed Auto negotiation (auto detection) (10Mbps/100Mbps)
Topology
· Star (connection with a hub in the center)
· Star bus (connection with multiple hubs)
Communication
distance
· Between node hub: 100m maximum (Node indicate master and inverters.)
· Between hubs: 100m maximum
· Overall length: 2000m maximum
Electrical interface Conforms to IEEE802.3u (conforms to CSMA/CD)
Transmission protocol FL remote
Node address setting
Can be set with node address switch (Refer to page 17).
The setting is applied to IP address as well.
(192.168.250.node address)
I/O points Input 64 points, output 64 points
13
2 INSTALLATION
2.1 Pre-installation instructions
Make sure that the input power of the inverter is OFF.
CAUTION
With input power ON, do not install or remove the plug-in option. Otherwise, the inverter and
plug-in option may be damaged.
Static electricity in your body must be discharged before you touch the product. Otherwise the
product may be damaged.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108