Ingersoll-Rand Trane TR15REG-DB Installer's Manual

Type
Installer's Manual

This manual is also suitable for

Ingersoll-Rand Trane TR15REG-DB is an electrical device used to connect electrical loads to either utility (normal) power source or an emergency power source. It is typically used to automatically switch electrical loads to a standby generator in the event of a power outage. Some of its capabilities include:

  • Automatic transfer: The switch can automatically transfer loads between the main power source and the generator when the main power fails.
  • Voltage monitoring: The switch can monitor the voltage of the main power source and the generator to ensure that the loads are receiving a stable voltage.

Ingersoll-Rand Trane TR15REG-DB is an electrical device used to connect electrical loads to either utility (normal) power source or an emergency power source. It is typically used to automatically switch electrical loads to a standby generator in the event of a power outage. Some of its capabilities include:

  • Automatic transfer: The switch can automatically transfer loads between the main power source and the generator when the main power fails.
  • Voltage monitoring: The switch can monitor the voltage of the main power source and the generator to ensure that the loads are receiving a stable voltage.
o TR15REG-DB (15Kw single-phase)
o TR20REG-DB (20Kw single-phase)
o TR20REG-DB-3 (20Kw three-phase)
Note: “Graphics in this document are for representation only.
Actual model may differ in appearance.”
March 2017 18-SG01D1-1A-EN
Installer’s Guide
Home Standby Generator
Automatic Transfer Switch
Table Of Contents
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting & Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fault Inspection and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DKG-173 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DKG-173 Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Application Rang . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Typical Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Relevant Models and Implications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Product Appearance and Parts Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
MCQ3 Technical Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
MCQ2 Technical Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Box Matching Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2
18-SG01D1-1A-EN
Preface
The Automatic Transfer Switch (hereafter referred to as ATS) uses world-famous ATS or AC Contactors as
the main switches, and are manufactured from advanced and closely-controlled production processes. It is
combined with all our automatic generators to form a complete and thorough Automatic Transfer System.
The DKG-173 Transfer Controller is installed inside the ATS, which applies to three phase or single phase
systems with phase voltage of 220v AC. Pluggable connectors are connected with external connections, which
make the maintenance, inspection, or replacement easy and convenient.
We have 125A single phase ATS, 125A three phase ATS, and 200A single phase ATS for your different needs in
various conditions.
Functions
ATS has control functions (such as generator start-up delay, mains restore delay and voltage
detection, etc.). When the ATS is connected to automatic generators, the generator's control
box will send the transfer signal in order to transfer loads automatically. It can operate with our automatic
control systems or other brands that have remote-start self-control functions which are simple and economic.
Control Mode
Generation/Automatic/Mains
LED Display
Mains Available
Mains on Load
Generator Available
Generator on Load
Parameter Settings
M. VOLT. SET: Mains Voltage Normal Value Setting, 75%-100% settable
VOLT. 100% = 170-300V
MCT: Closing Delay Time afer Mains Voltage returns to normal, 0-40 MIN. settable
GCT: Closing Delay Time after Generator Voltage returns to normal, 0-40S settable
G. VOLT. SET: Generator Voltage Normal Value Setting, 75%-100% settable
VOLT. 100% = 170-300V
Protection Function: Mains/Generator low voltage protection
3
18-SG01D1-1A-EN
Important Safety Instructions
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate
or service this equipment. Also read the instructions and information on all tags, decals, and labels that may
be afxed to the transfer switch. Throughout this publication, and on tags and decals afxed to the generator,
DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a
particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their
denitions are as follows:
DANGER
After this heading, read instructions that, if not strictly complied
with, will result in personal injury or property damage.
WARNING
After this heading, read instructions that, if not strictly complied
with, may result in personal injury or property damage.
CAUTION
After this heading, read instructions that, if not strictly complied
with, could result in damage to equipment and/or property.
This symbol points out important safety information that, if not followed,
could endanger personal safety and/or property.
This symbol points out potential explosion hazard.
This symbol points out potential re hazard.
This symbol points out potential electrical shock hazard.
4
18-SG01D1-1A-EN
Important Safety Instructions
• Remove all jewelry (such as rings, watches, bracelets, etc.) before working on this equipment.
• If work must be done on this equipment while standing on metal or concrete, place insulative mats over a dry
wood platform. Work on this equipment only while standing on insulative mats.
• Never work on this equipment while physically or mentally fatigued.
• Keep the transfer switch enclosure door closed and bolted at all times. Only qualied personnel should be
permitted access to the switch interior.
Equipment Description
The automatic transfer switch is used for transferring electrical load from a UTILITY (NORMAL) power source
to an EMERGENCY (STANDBY) power source.
Mounting
This model automatic transfer switch is designed for use only with Trane home standby generator sets.
• Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the
switch vertically to a rigid supporting structure.
To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to
level the unit.
Connecting Power Source and Load Line
• Wiring diagrams and electrical schematics are provided in this manual.
• Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire
brush. All power cables should enter the switch next to transfer mechanism terminals. If ALUMINUM
conductors are used, apply corrosion inhibitor to conductors.
Tighten terminal lugs to the torque values as noted on the decal located on the inside of the door. After
tightening terminal lugs, carefully wipe away any excess corrosion inhibitor.
5
18-SG01D1-1A-EN
Operation Instructions
Automatic Mode
1. Move the control switch of the ATS Control Panel on the AUTO position, the control mode of the generator
is "AUTO".
2. When mains are on load, the indicators "Mains Available" and "Mains On Load" will light up.
3. When mains failure occurs or utility is abnormal, the generator will be controlled by the Control Box for
"Start-up Delay" automatic start.
4. When the generator has started and the voltage is normal, the "Generator Available" indicator lights up. If
the ATS automatically switches the generator on, and the "Generator On Load" indicator lights up.
5. When the utility is restored, the "Mains Available" indicator lights up. The ATS automatically transfers to the
mains side after the generator control box has sent the "Mains on Load" signal. The "Generator on Load" light
goes off and the "Mains on Load" indicator lights up.
6. When the ATS control box detects that generator voltage is normal, the "Generator Available" indicator
lights up. The ATS transfers to the generator side when the GCT time setting is set on conditions of "Generator
on Load".
6
18-SG01D1-1A-EN
Fault Inspection and Troubleshooting
All our products will be strictly inspected before delivery in order to guarantee the quality of products.
Unreliability caused by users' improper installation and misuse can be checked in accordance with the following
instructions. Please contact us or the nearest dealer for help if faults are still unresolved.
1. The Main Switch has no action
A. The start-up delay has not nished. Please wait.
B. Verify whether the lines are correctly connected, especially the mains power source, the generator power
source, and load lines.
C. Check if the control lines from the ATS to the Control Box are correctly connected.
2. Indicators do not work
A. Verify whether lines are correctly connected or not, especially the mains power source, the generator power
source, and load lines.
B. Check if the setting of each control panel delay potentiometer is correct.
3. Generator does not start in case of utility outage
A. Verify whether the ATS Control Panel control switch and generator are set in the "AUTO" position.
B. Check if the control lines from ATS to the generator's Control Box are correctly connected.
7
18-SG01D1-1A-EN
Specications
Outside Size : 495 x 375 x 180
Operation Temp -20°C to 70°C (-4°F to 158°F)
Storage Temp -40°C to 85°C (-40°F to 185°F)
Humidity 5 to 95% cannot freezing
Weight (Kg) 17.5
Controller DKG-173 Specications
Generating voltage 170-300V-AC (Ph-N phase line-null line)
Mains voltage 170-300V-AC (Ph-N phase line-null line)
Generator contactor delay 1s to 40s, adjustable
Mains regain delay 1s to 40s, adjustable
MCB relay output 10A@250V-AC
GCB relay output 10A@250V-AC
Remote start relay output 10A@250V-AC/28V-DC
Operation temp. range -30°C (-22°F) to 70°C (158°F)
Storage temp. range -30°C (-22°F) to 80°C (176°F)
Max Humidity 95% non-condensing (non-condensation)
Size 70 x 115 x 66mm (W x H x D)
Weight 180g
Installation method DIN-rail mounting
Enclosure material Heat Resistant ABS/PC (UL94-VO) plastic
Protection lever IP20
Automatic Transfer Switch Spec Data
Working Volt (Ue) AC400V
Rated Isolation Volt 690V
Frequency 60HZ
Rated Working Current (A) 200A
Rated Short-time Withstand Current 10KA
Rated Limited Short-circuit Current 25KA
Operating Torque (N.m) 12
Conversion Time (S) < 80
Mechanical Endurance (times) 10000
Poles 2P
_
8
18-SG01D1-1A-EN
DKG-173
DIN RAIL MOUNTED ATS CONTROLLER WITHOUT DC SUPPLY
DESCRIPTION
The DATAKOM model DKG -173 is a DIN Rail mounted ATS controller
not requiring DC supply.
The unit monitors monitors 3-phase phase mains voltages, sends
remote start command to the generating set and performs changeover
of both generator and mains contactors.
The Front Panel LED provides information about mains and generator
power availability as well as contactor positions.
Mains return delay and genset contactor delays are adjustable
between 1 and 40 seconds through front panel knobs.
FEATURES
• DIN Rail mounted
• No DC supply required
Adjustable MCB and GCB delays
• 10A/250V AC MCB and GCB outlets
• 10A/28V DC/250V AC remote start output
• Isolated mains and generator set inputs
OPERATION
When the mains exist while all its phase voltage are below the limit 1/
• If R, MC, RST LEDs are on.
The MCB terminal is supplied with voltage R.
The REMOTE START relay contact is open.
The REMOTE START relay contact opens.
If any phase voltage of mains is over the limit
• R, MC, RST LEDs turn off.
The MCB terminal is open.
The REMOTE START relay contact closes.
The REMOTE START output is expected to provide a generator set running condition.
When the generator set voltage G is over the limit
The G LED turns on
At the expiration of the generator set contactor delay, the GC LED turns on and the GCB
terminal is supplied with voltage G.
9
18-SG01D1-1A-EN
DKG-173 Specications
Inputs:
R-S-T: mains phase voltages
NEUT-MN: mains neutral terminal
G: generator phase voltage
NEUT-GN: generator neutral terminal
Outputs:
MCB-MAINS CONTACTOR: normally open relay output connecting the phase-R voltage to the terminal (10A @
250V AC)
GCB-GENERATOR CONTACTOR: normally open relay output connecting the phase-G voltage to the terminal
(10A @ 250V AC)
REMOTE START: normally open engine start request relay output (10A @ 28V DC / 250V AC)
LED Indicators:
G: generator set voltage present
GC: generator set contactor closed
R: power supplied from mains
RST: mains voltage present
MC: mains contactor closed
Technical Specications:
Alternator voltage:
170-300V AC (Ph-N)
Mains Voltage:
170-300V AC (Ph-N)
Generator contactor delay:
1 to 40 seconds (adjustable)
Mains return delay:
1 to 40 seconds (adjustable)
MCB relay output:
10A @ 250V AC
GCB relay output:
10A @ 250V AC
Remote start relay output:
10A @ 250V AC / 28V DC
Operating temperature:
-30 C (-22 F) to 70 C (158 F)
Storage temperature:
-30 C (-22 F) to 80 C (176 F)
Maximum humidity:
95% non-condensing
Dimensions:
70 x 115 x 66mm (W x H x D)
Weight:
180g (approx.)
Installation:
DIN Rail mounted
Case Material:
High Temp. ABS/PC (UL94-V0)
IP Protection:
IP20
Conformity (EU directives)
-2006/95/EC (low voltage)
-2004/108/EC (EMC)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
10
18-SG01D1-1A-EN
Application Range
MCTRANS Series Dual power transfer switches (ATSE MCTRANS Series Dual power transfer switches (ATSE)
are advanced products which adopted the early twentieth century technology. It can used for two-way power
source infrequently transferred switched with rated insulation voltage AC800V and DC250V, rated current 20 to
5000A, rated frequency 50 or 60 Hz.
It mainly applied in occasions where need uninterruptible power supply, such as malls & ofce buildings, post
communications, re-ghting, military, mines, ship & vessel, escalator & elevator and industrial assembly lines,
etc. in order to meet the assembly lines, etc. in order to meet the requirements of providing more reliable
power sources.
The products are characterized by its small size, easy operation, fast switching speed and high reliability.
MCQ2 Model is double segments (without Neutral Position, transfer sequence: Mains to Generator) dual
power transfer switch.
MCQ3 Model is three segments (with Neutral Position, transfer sequence: Mains to Neutral to Generator) dual
power transfer switch.
Standards
IEC60947-1/GBT.14048.1-2000 Low-voltage switch Equipment and control Equipment/General rules
IEC60947-3/GBT.14048.3 Low Voltage Switch Equipment and Control Low Voltage Switch, Isolator, Isolation
Switch, and Combined Electronic Equipment
IEC60947-6/GBT.14048.11 Automatic Change-over Switch Circuit
11
18-SG01D1-1A-EN
Typical Connection Diagram
12
18-SG01D1-1A-EN
Relevant Models and Implications
Model Rated Current Pole Rated Voltage Wiring Method Control Voltage
MCQ3 three
segments with open
position
20 40 80 100 2: 2 poles 690V F: Front 2: 230V AC
MCQ2 double
segments without open
position
125 160 200 225 3: 3 poles 400V B: Back 4: 400V AC
250 350 400 4: 4 poles
13
18-SG01D1-1A-EN
Product Appearance and Parts Description
14
18-SG01D1-1A-EN
MCQ3 Main Technical Specications
Model MCQ3
Rated Voltage
Rated Current 20A-63A 80A-125A 160A-250A 350A-500A 630A-800A
Coil Quantity Double Coils
Wiring Method Front Back
Pole 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P
Weight (Kg) 5.5 6 6.5 6 6.5 7 6 8 10 11 14 18 25 33 42
Operating
Current
DC100V (A) 3 3 4 3 3 4 3 4 5 5 5 7 6 6 6
AC100V/110V (A) 3 3 4 3 3 4 3 4 5 5 5 7 6 6 6
AC200V/220V (A) 1.5 1.5 2 1.5 1.5 2 2.5 2.5 2.5 2.5 2.5 3.5 3 3 3
Tripping
Current
DV100V 1A 1.5A 2A
AC100V/110V 1A 1.5A 2A
AC200V/220V 0.5A 0.7A 1A
Perfor-
mance
Short-time Withstand Current 5KA 10KA 12KA 15KA
Rated Conditional Short
Circuit Current
12.5KA 25KA 30KA 37.5KA
Connecting and Breaking
Capability
AC-33B (101e Connect • 81e Break) cos=0.35 DC-33B 1.1Ie Connect • 1.1Ie Break L/R = 1ms
Switching
Time
A power
side
Control 55ms 60ms 100ms
Break 20ms 25ms 30ms
B power
side
Control 80ms 80ms 135ms
Break 20ms 20ms 30ms
Life Electrical: 2500 operations, Mechanical: 10000 operations
Operating Recycles 120 operations / hour
Auxiliary Switch
A power side 1C, B power side 1C, Switch Capacity AC100V 5A
AC200V 2.5A DC100V 0.5A
Accessories Manual Operation Handle
15
18-SG01D1-1A-EN
Model MCQ3
Rated Voltage
Rated Current 1000A 1250A 1600A 2000A 3150A 4000A 5000A
Coil Quantity Double Coils
Wiring Method Back
Pole 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P 3P 3P
Weight (Kg) 30 39 49 31 40 51 36 47 59 95 115 135 110 150 190 207 265
Operating
Current
DC100V (A) 6 6 8 6 6 6 7 8 9 8 10 12 10 12 14 16 18
AC100V/110V (A) 6 6 8 6 6 6 7 8 9 8 10 12 10 12 14 16 18
AC200V/220V (A) 2 3 4 3 3 4 3.5 4 4.5 4 5 6 7 7 8 8 8
Tripping
Current
DC100V 2A 4A
AC100V/110V 2A 4A
AC200V/220V 1A 1A
Perfor-
mance
Short-time Withstand Current 22KA 25KA 35KA 50KA 50KA 50KA
Rated Conditional Short
Circuit Current
50KA 55KA 55KA 80KA 100KA 120KA
Connecting and Breaking Capa-
bility
AC-33B (10Ie Connect • 8Ie break) cos=0.35 DC-33B 1.1Ie Connect • 1.1Ie Break L/R = 1mst
Switch-
ing Time
A power
side
Control 115ms 115ms 180ms 140ms 200ms (190) 210ms (190)
Break 25ms 25ms 25ms 30ms 30ms (30) 35ms (35)
B power
side
Control 145ms 150ms 150ms 190ms 220ms (240) 150ms (270)
Break 25ms 25ms 25ms 30ms 30ms (30) 35ms (35)
Life Electrical: 2000 operations Mechanical: 8000 operations
Operating Recycles 120 operations / hour 30 operations / hour
Auxiliary Switch A power side 1C, B power side 1C, Switch Capacity AC100V 5A AC200V 2.5A DC100V 0.5A
Accessories Manual Operation Handle
MCQ3 Main Technical Specications
(continued)
16
Model MCQ2
Rated Voltage AC400V / 690V DC125V / 250V
Rated Current 20A-63A 80A 100A 125A 160A 200A 225A 250A
Coil Quantity Double Coils
Wiring Method Front
Pole 2P 3P 4P 2P 3P 4P 2P 3P 4P
Weight (Kg) 4.5 5 5.5 5 5.5 6 6 8 10
Operating
Current
DC100V (A) 3 3 4 3 3 4 3 4 5
AC100V/110V (A) 3 3 4 3 3 4 3 4 5
AC200V/220V (A) 1.5 1.5 2 1.5 1.5 2 1.5 2 2.5
Tripping
Current
DC100V 1A
AC100V/110V 1A
AC200V/220V 0.5A
Performance
Short-time Withstand Current 5KA 10KA
Rated Conditional Short Circuit Current 12.5KA 25KA
Connecting and Breaking Capability
AC-33B(10Ie connect • 8Ie break) cos=0.35
DC-33B 1.1Ie connect • 1.1Ie break L/R = 1ms
Switching
Time
A power side
Control 55ms
Break 20ms
B power side
Control 80ms
Break 20ms
Life Electrical: 2500 operations, Mechanical: 10000 operations
Operating Recycles 120 operations / hour
Auxiliary Switch
A power side 1C, B power side 1C, Switch Capacity AC100V 5A
AC200V 2.5A DC100V 0.5A
Accessories Manual Operation Handle
Note: the outside dimension of MCQ2 Models Rated Current from 450A to 500A are
the same as the 340A to 500A Models of the MCQ3.
MCQ2 Main Technical Specications
17
18-SG01D1-1A-EN
Installation Dimensions
20A-63A Panel Safe Distance (S1 Dimensions: 30mm (400V), 60mm (690V)
80A-125A Panel Safe Distance (S1 Dimensions: 30mm (400V), 60mm (690V)
160A-250A Panel Safe Distance (S1 Dimensions: 30mm (400V), 60mm (690V)
18
18-SG01D1-1A-EN
1 Operation Circuit Terminal 2 Manual Operation Handle Entrance
3 Auxiliary Switch 4 A Power Side Main Circuit Terminal
5 Loaded Side Main Circuit Terminal 6 B Power Side Main Circuit Terminal
7 ON / OFF Option Buttons 8 Manual Operation Handle (removable)
Installation Dimensions
19
18-SG01D1-1A-EN
Box Matching Dimensions
Figure I. Fixing Bolt Hole (front) Figure II. Fixing Bolt Hole and Panel Hole (back)
Model
MCQ3
100
MCQ3
250
MCQ3
400
MCQ3
630
MCQ3
800
MCQ3
1000
MCQ3
1250
MCQ3
1600
MCQ3
2000
MCQ3
2500
MCQ3
3150
MCQ3
4000
B
2P 103 113 164 310 310 340 340 380 460 500 685 685
3P 133 148 224 375 375 420 420 480 595 645 915 915
4P 163 183 284 440 440 500 500 580 790 790 1155 1155
I 152 152 200 360 360 360 360 360 420 420 420 420
J
2P - - - 145 145 180 180 225 285 310 460 460
3P - - - 210 210 260 260 325 420 455 690 690
4P - - - 275 275 340 340 425 600 600 920 920
K - - - 330 330 330 330 330 350 350 350 350
L - - - 25 25 23 23 20 20 20 65 65
M 5.8 5.8 9 14 14 14 14 14 14 14 14 14
Figure I II
Note:
1. Keep the wire bending pressure from placing directly on the terminal when connecting the main circuit
terminal.
2. For the arc extinction distance outside the arc chute, please see the Outside Dimensions Part Figure I and
Figure II.
3. Please connect the grounding wire to the terminal marked
20
18-SG01D1-1A-EN
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Ingersoll-Rand Trane TR15REG-DB Installer's Manual

Type
Installer's Manual
This manual is also suitable for

Ingersoll-Rand Trane TR15REG-DB is an electrical device used to connect electrical loads to either utility (normal) power source or an emergency power source. It is typically used to automatically switch electrical loads to a standby generator in the event of a power outage. Some of its capabilities include:

  • Automatic transfer: The switch can automatically transfer loads between the main power source and the generator when the main power fails.
  • Voltage monitoring: The switch can monitor the voltage of the main power source and the generator to ensure that the loads are receiving a stable voltage.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI