Sanyo CL1271 Technical & Service Manual

Category
Split-system air conditioners
Type
Technical & Service Manual

This manual is also suitable for

TECHNICAL & SERVICE MANUAL
XS1271 & PNR-XS1872 + C1271
XS1271 & PNR-XS1872 + CL1271
XS1872 & PNR-XS1872 + CH1872
XS1872 & PNR-XS1872 + CL1872
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
Indoor Unit
Destination: North America
Outdoor Model No.
C1271
C1872
CL1271
CL1872
Product Code No.
1 852 330 24
1 852 330 36
1 852 330 26
1 852 330 40
XS1271 (Body) & PNR-XS1872 (Panel)
XS1872 (Body) & PNR-XS1872 (Panel)
C1271
CL1271
C1872
CL1872
REFERENCE NO. SM700767
Outdoor Unit
Indoor Model No.
Body (Panel)
XS1271 (PNR-XS1872)
XS1872 (PNR-XS1872)
Product Code No.
Body (Panel)
1 852 352 10 (1 852 352 11)
1 852 352 09 (1 852 352 11)
FILE NO.
Body
Panel
Wireless Remote Controller
Wired Remote Controller
(Option)
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
SPECIAL PRECAUTIONS
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
CAUTION
CAUTION
WARNING
WARNING
Important!
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an
important part of your job to install or service the system so it
operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given
in this manual.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
Install a protective leakage breaker depending on the
installation location (especially a damp or humid
location). If a leakage breaker is not installed, electric
shock can occur.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or thin
aluminum fins on the air conditioner can cut your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s
weight. It may be necessary to construct a strong wood or
metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent
"sweating" that can cause dripping and water damage to walls
and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
When Servicing
Turn the power off at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing the
refrigeration system. Escaped refrigerant gas, on contact
with fire or heat, can produce dangerously toxic gas.
Confirm upon completing installation that no refrigerant gas
is leaking. If escaped gas comes in contact with a stove,
gas water heater, electric room heater or other heat source,
it can produce dangerously toxic gas.
2
Table of Contents
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications
2-2. Major Component Specifications
2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Temperature Charts
5-2. Cooling Capactiy
5-3. Cooling Capactiy (Low Ambient)
6. ELECTRICAL DATA
6-1. Electrical Characteristics
6-2. Electric Wiring Diagrams
7. MAINTENANCE
7-1. Address Setting of the Remote Control Unit
7-2. Disconnecting and Connecting Positive Connector for Outdoor Unit
7-3. Disassembly Procedure
8. FUNCTIONS
8-1. Operation Functions
8-2. Protective Functions
9. TROUBLESHOOTING
9-1. Precautions before Performing Inspection or Repair
9-2. Method of Self-Diagnostics
9-3. Checking the Indoor and Outdoor Units
9-4. Trouble Diagnosis of Fan Motor
9-5. Noise Malfunction and Electromagnetic Interference
5
6
18
24
25
28
30
32
34
36
38
42
43
44
51
53
54
54
56
60
62
...................................................................................................................
.............................................................................................................
.......................................................................................
.......................................................................................
.....................................................................................................................
...................................................................................................
............................................................................................................
................................................................................................................
.........................................................................................
....................................................................................................
....................................................................................................
.......................................................................
.................................
......................................................................................................
...........................................................................................................
...........................................................................................................
...........................................................
.................................................................................................
..............................................................................
...........................................................................................
..........................................................
Page
3
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance
10-2. Checking Continuity of Fuse on PCB Ass'y
11. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
11-1. Characteristics of New Refrigerant R410A
11-2. Checklist before Servicing
11-3. Tools Specifically for R410A
11-4. Tubing Installation Procedures
11-5. In Case of Compressor Malfunction
11-6. In Case Refrigerant is Leaking
11-7. Charging Additional Refrigerant
11-8. Retro-Fitting Existing Systems
APPENDIX A INSTRUCTION MANUAL
XS1271 & PNR-XS1872 + C1271 XS1271 & PNR-XS1872 + CL1271
XS1872 & PNR-XS1872 + C1872 XS1872 & PNR-XS1872 + CL1872
APPENDIX B INSTALLATION INSTRUCTIONS
XS1271 & PNR-XS1872 + C1271 XS1271 & PNR-XS1872 + CL1271
XS1872 & PNR-XS1872 + C1872 XS1872 & PNR-XS1872 + CL1872
APPENDIX C INSTRUCTION MANUAL
(STK-RCS-7TWSU)
APPENDIX D INSTALLATION INSTRUCTIONS
(STK-RCS-7TWSU)
63
64
65
66
67
67
68
70
71
71
A-1
A-2
A-3
A-4
...............................................................................
.........................................................................
.........................................................................
...................................................................................................
................................................................................................
............................................................................................
....................................................................................
............................................................................................
..........................................................................................
............................................................................................
..........................................................................................
.............................................................................
.........................................................................................
.............................................................................
Page
()
()
4
95 °F D.B. / 71 °F W.B.
67 °F D.B. / 57 °F W.B.
1. OPERATING RANGE
Maximum
Minimum
115 °F D.B.
67 °F D.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
95 °F D.B. / 71 °F W.B.
67 °F D.B. / 57 °F W.B.
Maximum
Minimum
115 °F D.B.
0 °F D.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Models :XS1271 & PNR-XS1872 + C1271
 XS1872 & PNR-XS1872 + C1872
Models :XS1271 & PNR-XS1872 + CL1271
 XS1872 & PNR-XS1872 + CL1872
5
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit XS1271 & PNR-XS1872
Outdoor Unit C1271
2-1-1.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment Ibs (g)
Refrigerant Control
12.6
1,260
( 2.5 to 12.6 )
( 250 to 1,260 )
11,900
3.5
( 3,000 to 11,900 )
( 0.9 to 3.5 )
Cooling
7,200
4,700
115V Single-Phase 60Hz
104 to 126
Refrigerant Tubing Connections
Operation Sound
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Accessories
Narrow tube
Wide tube
Refrigerant inch (mm)
Tube Diameter inch (mm)
1/4 (6.35)
3/8 (9.52)
ft (m)Max. allowable tubing length at shipment
Flare Type
25 (7.5)
34 / 32 / 31
47
R410A / 2.43 (1,100)
Electric Expansion Valve
Washable, Anti-Mold
DC Rotary (Inverter)
-
Auto
Timer
Indoor / OutdoorFan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Compressor Locked Rotor Amperes
Air Clean Filter
BTU/h
Performance
%Power Factor 87
A20
Voltage Rating
BTU/h
kW
Total Capacity
BTU/h
SEER BTU/Wh 16
235 (400)
Air Circulation (High) ft
3
/min (m
3
/h)
4.26
Moisture Removal (High) Pints/h
EER BTU/h/W 9.44
Fuse or Circuit Breaker Capacity A20
Wired Remote Controller (Option) STK-RCS-7TWSU
6
Indoor Unit XS1271 & PNR-XS1872
Outdoor Unit C1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width
Depth
-
-
22-5/8 (575)
35.3 (16)
Individual Unit
Body
(XS1271)
Panel
(PNR-XS1872)
Indoor Unit
(XS1271 & PNR-XS1872)
inch (mm) (313)12-5/16
(625)24-19/32
(625)24-19/32
(18.7)41.3
11-5/32 (283)
inch (mm) 22-5/8 (575)
inch (mm)
Package Dimensions Height
Width
Depth 28-1/8 (714)
inch (mm) -
-
-
11-13/32 (290)
inch (mm) 24-13/16 (630)
41.9 (19)
4.59 (0.13)
24-19/32 (625)
6.0 (2.7)
1-9/16 (40)
24-19/32 (625)
26-11/16 (678)
4-1/8 (105)
26-3/16 (665)
7.7 (3.5)
1.65 (0.04)
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width
Depth
Outdoor Unit
(C1271)
inch (mm) (548)21-9/16
(720)28-11/32
(265)10-7/16
(600)23-5/8
(856)33-11/16
(362)14-1/4
(34.0)75.0
(37.0)81.6
(0.18)6.35
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
7
< 230V >
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit C1872
2-1-2.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment Ibs (g)
Refrigerant Control
8.3
1,860
( 1.2 to 8.3 )
( 250 to 1,860 )
17,500
5.15
( 4,000 to 17,500 )
( 1.2 to 5.15 )
Cooling
10,600
6,900
230V Single-Phase 60Hz
187 to 253
Refrigerant Tubing Connections
Operation Sound
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Accessories
Narrow tube
Wide tube
Refrigerant inch (mm)
Tube Diameter inch (mm)
1/4 (6.35)
1/2 (12.7)
ft (m)Max. allowable tubing length at shipment
Flare Type
25 (7.5)
44 / 40 / 36
51
R410A / 2.87 (1,300)
Electric Expansion Valve
Washable, Anti-Mold
DC Twin Rotary (Inverter)
-
Auto
Timer
Indoor / OutdoorFan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Compressor Locked Rotor Amperes
Air Clean Filter
BTU/h
Performance
%Power Factor 97
A 17.5
Voltage Rating
BTU/h
kW
Total Capacity
BTU/h
SEER BTU/Wh 16
341 (580)
Air Circulation (High) ft
3
/min (m
3
/h)
4.89
Moisture Removal (High) Pints/h
EER BTU/h/W 9.41
Fuse or Circuit Breaker Capacity A20
Wired Remote Controller (Option) STK-RCS-7TWSU
8
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit C1872
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width
Depth
Individual Unit
Body
(XS1872)
Panel
(PNR-XS1872)
Indoor Unit
(XS1872 & PNR-XS1872)
inch (mm)
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width
Depth
Outdoor Unit
(C1872)
inch (mm) (670)26-3/8
(880)34-21/32
(285)11-7/32
(740)29-1/8
(1,012)39-27/32
(380)14-31/32
(41.0)90.4
(45.0)99.2
(0.28)9.88
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
< 230V >
-
-
(313)12-5/16
(625)24-19/32
(625)24-19/32
(18.7)41.3
-
-
-
22-5/8 (575)
35.3 (16)
11-5/32 (283)
22-5/8 (575)
28-1/8 (714)
11-13/32 (290)
24-13/16 (630)
41.9 (19)
4.59 (0.13)
24-19/32 (625)
6.0 (2.7)
1-9/16 (40)
24-19/32 (625)
26-11/16 (678)
4-1/8 (105)
26-3/16 (665)
7.7 (3.5)
1.65 (0.04)
9
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit C1872
< 208V >
2-1-3.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment Ibs (g)
Refrigerant Control
9.1
1,860
( 1.2 to 9.1 )
( 250 to 1,860 )
17,500
5.15
( 4,000 to 17,500 )
( 1.2 to 5.15 )
Cooling
10,600
6,900
208V Single-Phase 60Hz
187 to 253
Refrigerant Tubing Connections
Operation Sound
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Accessories
Narrow tube
Wide tube
Refrigerant inch (mm)
Tube Diameter inch (mm)
1/4 (6.35)
1/2 (12.7)
ft (m)Max. allowable tubing length at shipment
Flare Type
25 (7.5)
44 / 40 / 36
51
R410A / 2.87 (1,300)
Electric Expansion Valve
Washable, Anti-Mold
DC Twin Rotary (Inverter)
-
Auto
Timer
Indoor / OutdoorFan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi, Me, Lo)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Compressor Locked Rotor Amperes
Air Clean Filter
BTU/h
Performance
%Power Factor 98
A 17.5
Voltage Rating
BTU/h
kW
Total Capacity
BTU/h
SEER BTU/Wh 16
341 (580)
Air Circulation (High) ft
3
/min (m
3
/h)
4.89
Moisture Removal (High) Pints/h
EER BTU/h/W 9.41
Fuse or Circuit Breaker Capacity A20
Wired Remote Controller (Option) STK-RCS-7TWSU
10
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit C1872
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width
Depth
Individual Unit
Body
(XS1872)
Panel
(PNR-XS1872)
Indoor Unit
(XS1872 & PNR-XS1872)
inch (mm)
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width
Depth
Outdoor Unit
(C1872)
inch (mm) (670)26-3/8
(880)34-21/32
(285)11-7/32
(740)29-1/8
(1,012)39-27/32
(380)14-31/32
(41.0)90.4
(45.0)99.2
(0.28)9.88
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
< 208V >
-
-
(313)12-5/16
(625)24-19/32
(625)24-19/32
(18.7)41.3
-
-
-
22-5/8 (575)
35.3 (16)
11-5/32 (283)
22-5/8 (575)
28-1/8 (714)
11-13/32 (290)
24-13/16 (630)
41.9 (19)
4.59 (0.13)
24-19/32 (625)
6.0 (2.7)
1-9/16 (40)
24-19/32 (625)
26-11/16 (678)
4-1/8 (105)
26-3/16 (665)
7.7 (3.5)
1.65 (0.04)
11
Indoor Unit XS1271 & PNR-XS1872
Outdoor Unit CL1271
2-1-4.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment Ibs (g)
Refrigerant Control
12.6
1,260
( 2.5 to 12.6 )
( 250 to 1,260 )
11,900
3.5
( 3,000 to 11,900 )
( 0.9 to 3.5 )
Cooling
7,200
4,700
115V Single-Phase 60Hz
104 to 126
Refrigerant Tubing Connections
Operation Sound
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Accessories
Narrow tube
Wide tube
Refrigerant inch (mm)
Tube Diameter inch (mm)
1/4 (6.35)
3/8 (9.52)
ft (m)Max. allowable tubing length at shipment
Flare Type
25 (7.5)
34 / 32 / 31
47
R410A / 2.43 (1,100)
Electric Expansion Valve
Washable, Anti-Mold
DC Rotary (Inverter)
-
Auto
Timer
Indoor / OutdoorFan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi and multi steps)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Compressor Locked Rotor Amperes
Air Clean Filter
BTU/h
Performance
%Power Factor 87
A20
Voltage Rating
BTU/h
kW
Total Capacity
BTU/h
SEER BTU/Wh 16
235 (400)
Air Circulation (High) ft
3
/min (m
3
/h)
4.26
Moisture Removal (High) Pints/h
EER BTU/h/W 9.44
Fuse or Circuit Breaker Capacity A20
Wired Remote Controller (Option) STK-RCS-7TWSU
12
Indoor Unit XS1271 & PNR-XS1872
Outdoor Unit CL1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width
Depth
-
-
22-5/8 (575)
35.3 (16)
Individual Unit
Body
(XS1271)
Panel
(PNR-XS1872)
Indoor Unit
(XS1271 & PNR-XS1872)
inch (mm) (313)12-5/16
(625)24-19/32
(625)24-19/32
(18.7)41.3
11-5/32 (283)
inch (mm) 22-5/8 (575)
inch (mm)
Package Dimensions Height
Width
Depth 28-1/8 (714)
inch (mm) -
-
-
11-13/32 (290)
inch (mm) 24-13/16 (630)
41.9 (19)
4.59 (0.13)
24-19/32 (625)
6.0 (2.7)
1-9/16 (40)
24-19/32 (625)
26-11/16 (678)
4-1/8 (105)
26-3/16 (665)
7.7 (3.5)
1.65 (0.04)
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width
Depth
Outdoor Unit
(CL1271)
inch (mm) (548)21-9/16
(720)28-11/32
(265)10-7/16
(600)23-5/8
(856)33-11/16
(362)14-1/4
(34.0)75.0
(37.0)81.6
(0.18)6.35
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
13
< 230V >
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit CL1872
2-1-5.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment Ibs (g)
Refrigerant Control
8.3
1,860
( 1.2 to 8.3 )
( 250 to 1,860 )
17,500
5.15
( 4,000 to 17,500 )
( 1.2 to 5.15 )
Cooling
10,600
6,900
230V Single-Phase 60Hz
187 to 253
Refrigerant Tubing Connections
Operation Sound
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Accessories
Narrow tube
Wide tube
Refrigerant inch (mm)
Tube Diameter inch (mm)
1/4 (6.35)
1/2 (12.7)
ft (m)Max. allowable tubing length at shipment
Flare Type
25 (7.5)
44 / 40 / 36
51
R410A / 2.87 (1,300)
Electric Expansion Valve
Washable, Anti-Mold
DC Twin Rotary (Inverter)
-
Auto
Timer
Indoor / OutdoorFan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi and multi steps)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Compressor Locked Rotor Amperes
Air Clean Filter
BTU/h
Performance
%Power Factor 97
A 17.5
Voltage Rating
BTU/h
kW
Total Capacity
BTU/h
SEER BTU/Wh 16
341 (580)
Air Circulation (High) ft
3
/min (m
3
/h)
4.89
Moisture Removal (High) Pints/h
EER BTU/h/W 9.41
Fuse or Circuit Breaker Capacity A20
Wired Remote Controller (Option) STK-RCS-7TWSU
14
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit CL1872
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width
Depth
Individual Unit
Body
(XS1872)
Panel
(PNR-XS1872)
Indoor Unit
(XS1872 & PNR-XS1872)
inch (mm)
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width
Depth
Outdoor Unit
(CL1872)
inch (mm) (670)26-3/8
(880)34-21/32
(285)11-7/32
(740)29-1/8
(1,012)39-27/32
(380)14-31/32
(41.0)90.4
(45.0)99.2
(0.28)9.88
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
< 230V >
-
-
(313)12-5/16
(625)24-19/32
(625)24-19/32
(18.7)41.3
-
-
-
22-5/8 (575)
35.3 (16)
11-5/32 (283)
22-5/8 (575)
28-1/8 (714)
11-13/32 (290)
24-13/16 (630)
41.9 (19)
4.59 (0.13)
24-19/32 (625)
6.0 (2.7)
1-9/16 (40)
24-19/32 (625)
26-11/16 (678)
4-1/8 (105)
26-3/16 (665)
7.7 (3.5)
1.65 (0.04)
15
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit CL1872
< 208V >
2-1-6.
Vertical
dB-A
dB-A
Indoor : Hi/Me/Lo
Outdoor : Hi
Air Filter
Compressor
Refrigerant / Amount charged at shipment Ibs (g)
Refrigerant Control
9.1
1,860
( 1.2 to 9.1 )
( 250 to 1,860 )
17,500
5.15
( 4,000 to 17,500 )
( 1.2 to 5.15 )
Cooling
10,600
6,900
208V Single-Phase 60Hz
187 to 253
Refrigerant Tubing Connections
Operation Sound
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Accessories
Narrow tube
Wide tube
Refrigerant inch (mm)
Tube Diameter inch (mm)
1/4 (6.35)
1/2 (12.7)
ft (m)Max. allowable tubing length at shipment
Flare Type
25 (7.5)
44 / 40 / 36
51
R410A / 2.87 (1,300)
Electric Expansion Valve
Washable, Anti-Mold
DC Twin Rotary (Inverter)
-
Auto
Timer
Indoor / OutdoorFan Speeds
24-Hour ON or OFF Timer, 1-Hour OFF Timer
Auto and 3 steps / Auto (Hi and multi steps)
Airflow Direction (Indoor) Horizontal
Controls / Temperature Control
Control Unit
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Features
Compressor Locked Rotor Amperes
Air Clean Filter
BTU/h
Performance
%Power Factor 98
A 17.5
Voltage Rating
BTU/h
kW
Total Capacity
BTU/h
SEER BTU/Wh 16
341 (580)
Air Circulation (High) ft
3
/min (m
3
/h)
4.89
Moisture Removal (High) Pints/h
EER BTU/h/W 9.41
Fuse or Circuit Breaker Capacity A20
Wired Remote Controller (Option) STK-RCS-7TWSU
16
Indoor Unit XS1872 & PNR-XS1872
Outdoor Unit CL1872
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.
Outdoor air temperature 95°F D.B. / 75°F W.B.
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width
Depth
Individual Unit
Body
(XS1872)
Panel
(PNR-XS1872)
Indoor Unit
(XS1872 & PNR-XS1872)
inch (mm)
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
Shipping Volume
Net
Shipping
Weight Ib. (kg)
Ib. (kg)
cu.ft (m
3
)
inch (mm)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width
Depth
Outdoor Unit
(CL1872)
inch (mm) (670)26-3/8
(880)34-21/32
(285)11-7/32
(740)29-1/8
(1,012)39-27/32
(380)14-31/32
(41.0)90.4
(45.0)99.2
(0.28)9.88
inch (mm)
inch (mm)
Package Dimensions Height
Width
Depth
inch (mm)
inch (mm)
< 208V >
-
-
(313)12-5/16
(625)24-19/32
(625)24-19/32
(18.7)41.3
-
-
-
22-5/8 (575)
35.3 (16)
11-5/32 (283)
22-5/8 (575)
28-1/8 (714)
11-13/32 (290)
24-13/16 (630)
41.9 (19)
4.59 (0.13)
24-19/32 (625)
6.0 (2.7)
1-9/16 (40)
24-19/32 (625)
26-11/16 (678)
4-1/8 (105)
26-3/16 (665)
7.7 (3.5)
1.65 (0.04)
17
Indoor Unit (Body) XS1271
Indoor Unit (Panel) PNR-XS1872
2-2. Major Component Specifications
2-2-1. Indoor Unit
MP24ZN-12V ... 2
Flap Motor
Type Stepping Motor
Rating
Model ... Q'ty
Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DC 12V
PLD-12115ST-1 ... 1
AC115V, 60Hz
10.8
Model ... Q'ty
Rating Voltage, Hz
Input
Drain Pump
W
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Thermal Fuse
293 (145)
Safty Device
Open
Type
°F (°C)
Aluminum Plate Fin / Copper Tube
2
18.1
2.94 (0.273) Face Area
Coil
Rows
Fins per inch
Heat Exchanger Coil
ft
2
(m
2
)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3A
CB-XS1271
1 ... D12-5/8 / L5-3/4 (D322/L147)
RCS-7MVPS4U
Turbo
DC Motor
SIC-72FV-B623-1 ... 1
8
-
470
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
inch (mm)
Fan Motor
Coil Resistance
Rough Measure RPM (Cool)
Type
Model ... Q'ty
No. of Poles
(Ambient Temp. 68 °F (20 °C))
Run Capacitor Micro F
VAC
Ohm
101 +/- 10%Coil Resistance
Ohm
(Ambient Temp. 68 °F (20 °C))
Yes
DC160V / 23W
Internal Controller
Yes
Rating Voltage / Nominal Output
Safety Device
Type
Over- Current Protection
Over- Heat Protection
18
Indoor Unit (Body) XS1872
Indoor Unit (Panel) PNR-XS1872
MP24ZN-12V ... 2
Flap Motor
Type Stepping Motor
Rating
Model ... Q'ty
Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DC 12V
Aluminum Plate Fin / Copper Tube
2
18.1
2.94 (0.273) Face Area
Coil
Rows
Fins per inch
Heat Exchanger Coil
ft
2
(m
2
)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 3A
CB-XS1872
1 ... D12-5/8 / L5-3/4 (D322/L147)
RCS-7MVPS4U
Turbo
DC Motor
SIC-72FV-D866-1B ... 1
8
-
650
-
-
Fan
Remote Control Unit
Q'ty ... Dia. and Length
Type
inch (mm)
Fan Motor
Coil Resistance
Rough Measure RPM (Cool)
Type
Model ... Q'ty
No. of Poles
(Ambient Temp. 68 °F (20 °C))
Run Capacitor Micro F
VAC
Ohm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Internal Controller
Safety Device
Type
PLD-12230ST-1 ... 1
AC208 to 240V, 60Hz
10.8
333 +/- 10%Coil Resistance
Model ... Q'ty
Rating Voltage, Hz
Input
Drain Pump
Ohm
W
Thermal Fuse
293 (145)
(Ambient Temp. 68 °F (20 °C))
Safty Device
Open
Type
°F (°C)
Yes
Yes
Over- Current Protection
Over- Heat Protection
DC340V / 20WRating Voltage / Nominal Output
19
2-2-2. Outdoor Unit
Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
125V 25A
CB-C1271
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Pints (cc)
WHT - BLU :
BLU - RED :
RED - WHT :
77.5
77.5
77.5
Micro F
VAC
External Finish Acrylic baked-on enamel finish
FV50S ... 0.68 (320)
-
-
Internal Controller
Yes
Aluminum Plate Fin / Copper Tube
2
18.1
Face Area
ft
2
(m
2
)
3.95 (0.367)
Coil
Rows
Fins per inch
Heat Exchanger Coil
DAJ12-55J71-CU ... 1
Compressor Oil ... Amount
8
50
750
Ohm
DC Motor
Type
Compressor Model / Nominal Output
Compressor
Coil Resistance (Ambient Temp. 68 °F (20 °C))
Ohm
DC Rotary (Hermetic)
G4C090LU1ER / 900W
U - V :
V - W :
W - U :
0.81
0.81
0.81
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Safety Device
Micro F
VAC
Run Capacitor
Crankcase Heater
Yes
Yes
Yes
Overload Relay
CS-7L115
Model
Operation Temp.
Open : 239 °F (115 °C), Close : 203 °F (95 °C)
-
-
-
1 ... D15-3/4 (D400)
Fan
Propeller
Q'ty ... Dia. inch (mm)
Type
Type
Over- Current Protection
(Ambient Temp. 68 °F (20 °C))
Fan Motor
Nominal Output
Coil Resistance
Safety Device
Rough Measure RPM (Cool)
Run Capacitor
Type
Model ... Q'ty
No. of Poles
W
Outdoor Unit C1271
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131