Sanyo SAP-CRV123EH User manual

Category
Split-system air conditioners
Type
User manual
TECHNICAL & SERVICE MANUAL
SAP-KRV93EH + SAP-CRV93EH
SAP-KRV123EH + SAP-CRV123EH
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
SAP-CRV93EH
SAP-CRV123EH
AIR CO
N
DITIONER
IMPORTANT
These air conditioners employ new
refrigerant R410A.
Pay special attention when
servicing the unit.
SAP-KRV93EH
SAP-KRV123EH
FILE NO.
REFERENCE NO. SM700590
W
Indoor Unit Outdoor Unit
Indoor Model No. Product Code No.
SAP-KRV93EH 1 852 089 81
SAP-KRV123EH 1 852 089 80
Outdoor Model No. Product Code No.
SAP-CRV93EH 1 852 089 85
SAP-CRV123EH 1 852 089 84
Destination: Europe
2
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and oper-
ating standards. As the installer or service person, it is an
important part of your job to install or service the system
so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as
shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a haz-
ard or unsafe practice which
can result in severe personal
injury or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tub-
ing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause accidental
injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your
knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can
cut your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the outdoor unit. This pre-
vents water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-
free connection.
Check carefully for leaks before starting the test run.
When Servicing
Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have been
left inside the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously
toxic gas.
Confirm upon completing installation that no refriger-
ant gas is leaking. If escaped gas comes in contact
with a stove, gas water heater, electric room heater or
other heat source, it can produce dangerously toxic
gas.
WARNING
WARNING
CAUTION
CAUTION
3
Table of Contents
Page
1. OPERATING RANGE................................................................................................................ 4
2. SPECIFICATIONS
2-1. Unit Specifications ............................................................................................................ 5
2-2. Major Component Specifications...................................................................................... 7
2-3. Other Component Specifications...................................................................................... 11
3. DIMENSIONAL DATA................................................................................................................ 12
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram................................................................................................. 14
5. PERFORMANCE DATA
5-1. Temperature Charts..........................................................................................................15
5-2. Air Throw Distance Charts................................................................................................ 17
5-3. Operating Frequency Charts ............................................................................................ 19
6. ELECTRICAL DATA
6-1. Electrical Characteristics ..................................................................................................23
6-2. Electric Wiring Diagrams .................................................................................................. 24
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection .................................................................................................26
7-2. Recommended Wire Length and Diameter ...................................................................... 28
7-3. Remote Control Unit Installation Position ......................................................................... 29
7-4. How to Test Run the Air Conditioner ................................................................................ 30
7-5. Remove the Grille to Install the Indoor Unit...................................................................... 31
8. MAINTENANCE
8-1. Address Setting of the Remote Control Unit .................................................................... 32
8-2. Disconnecting and Connecting Positive Connector for Outdoor Unit ............................... 33
9. FUNCTIONS
9-1. Operation Functions .........................................................................................................34
9-2. Protective Functions ......................................................................................................... 36
10. TROUBLESHOOTING............................................................................................................... 38
11. CHECKING ELECTRICAL COMPONENTS
11-1. Measurement of Insulation Resistance ............................................................................ 43
11-2. Checking Continuity of Fuse on PCB Ass’y ..................................................................... 44
12. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT .............................................................. 45
INSTRUCTION MANUAL ...................................................................................... 52
APPENDIX
4
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. –20°C D.B. / –20°C W.B.
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit SAP-KRV93EH
Outdoor Unit SAP-CRV93EH
Power Source 220 – 240V Single-phase 50Hz
Performance Cooling Heating
Capacity kW 2.65 (0.9 – 3.2) 3.60 (0.9 – 5.0)
BTU/h 9,000 (3,100 – 10,900) 12,300 (3,100 – 17,100)
Air circulation (High) m
3
/h 480 530
Moisture removal (High) Liters/h 1.6
Electrical Rating Cooling Heating
Available voltage range V 198 – 264
Running amperes A 3.86 (1.28 – 5.88) 4.81 (1.21 – 6.47)
Power input W 755 (250 – 1,150) 995 (250 – 1,340)
Power factor % 85 90
C.O.P. W/W 3.51 3.62
Compressor locked rotor amperes A 15
Features
Controls / Temperature control Microprocessor / I.C. thermister
Control unit Wireless remote control unit
Timer ON / OFF 24 hours & Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (DC inverter)
Refrigerant / Amount charged at shipment g R410A / 950
Refrigerant control Electric expansion valve
Operation sound Indoor: Hi / Me / Lo dB-A 34 / 31 / 28 34 / 31 / 28
Outdoor: Hi dB-A 46 47
Refrigerant tubing connections Flare type
Max allowable tubing length at shipment m 7.5
Refrigerant Narrow tube mm (in.) 6.35 (1/4)
tube diameter Wide tube mm (in.) 9.52 (3/8)
Refrigerant tube kit / Accessories Optional / Air clean filter
Voltage Rating 230V
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 548
Width mm 825 720
Depth mm 189 265
Package dimensions Height mm 350 600
Width mm 900 856
Depth mm 255 362
Weight Net kg 9.0 34.0
Shipping kg 11.0 36.0
Shipping volume m
3
0.080 0.186
6
Indoor Unit SAP-KRV123EH
Outdoor Unit SAP-CRV123EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Power Source 220 – 240V Single-phase 50Hz
Performance Cooling Heating
Capacity kW 3.50 (0.9 – 3.8) 4.20 (0.9 – 5.8)
BTU/h 11,900 (3,100 – 13,000) 14,300 (3,100 – 19,800)
Air circulation (High) m
3
/h 500 530
Moisture removal (High) Liters/h 2.0
Electrical Rating Cooling Heating
Available voltage range V 198 – 264
Running amperes A 5.21 (1.19 – 6.21) 5.48 (1.18 – 7.09)
Power input W 1,090 (250 – 1,300) 1,165 (250 – 1,500)
Power factor % 91 92
C.O.P. W/W 3.21 3.61
Compressor locked rotor amperes A 15
Features
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON / OFF 24 hours & Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, Anti-Mold
Compressor Rotary (DC inverter)
Refrigerant / Amount charged at shipment g R410A / 1,100
Refrigerant control Electric expansion valve
Operation sound Indoor: Hi / Me / Lo dB-A 36 / 33 / 29 34 / 31 / 29
Outdoor: Hi dB-A 47 49
Refrigerant tubing connections Flare type
Max allowable tubing length at shipment m 7.5
Refrigerant Narrow tube mm (in.) 6.35 (1/4)
tube diameter Wide tube mm (in.) 9.52 (3/8)
Refrigerant tube kit / Accessories Optional / Air clean filter
Voltage Rating 230V
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 548
Width mm 825 720
Depth mm 189 265
Package dimensions Height mm 350 600
Width mm 900 856
Depth mm 255 362
Weight Net kg 9.0 35.0
Shipping kg 11.0 37.0
Shipping volume m
3
0.080 0.186
7
2-2. Major Component Specifications
2-2-1. Indoor Unit
Indoor Unit SAP–KRV93EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. CB-KRV93EH (POW-KRV93GJH)
Controls Microprocessor
Control circuit fuse 250V 3.15A
Flap Motor and Louver Motor
Type Stepping motor
Model MP24Z3-12V
Rating DC 12V
Coil resistance (Ambient temp. 25°C) Each pair of terminals: 400 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area m
2
0.188
Fan & Fan Motor
Type Fan / Fan motor Cross-flow / AC motor
Q’ty … Dia. and lengthmm1 … D92 / L634
Fan motor model … Q’ty IBH-884-066 … 1
No. of poles … Rough measure rpm (Cool / Heat) 4 … 1,200 / 1,250
Nominal output W 30
Coil resistance (Ambient temp. 20°C) BRN WHT: 234
PNK (RED) WHT: 209
— :
Safety devices Type Thermal fuse
Operating temp. Open °C 130
Close
Run capacitor µF 1.2
VAC 440
Remote Control Unit RCS-3HVPSS4E
8
Indoor Unit SAP–KRV123EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. CB-KRV123EH (POW-KRV93GJH)
Controls Microprocessor
Control circuit fuse 250V 3.15A
Flap Motor and Louver Motor
Type Stepping motor
Model MP24Z3-12V
Rating DC 12V
Coil resistance (Ambient temp. 25°C) Each pair of terminals: 400 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area m
2
0.188
Fan & Fan Motor
Type Fan / Fan motor Cross-flow / AC motor
Q’ty … Dia. and lengthmm1 … D92 / L634
Fan motor model … Q’ty IBH-884-066 … 1
No. of poles … Rough measure rpm (Cool / Heat) 4 … 1,250 / 1,250
Nominal output W 30
Coil resistance (Ambient temp. 20°C) BRN WHT: 234
PNK (RED) WHT: 209
— :
Safety devices Type Thermal fuse
Operating temp. Open °C 130
Close
Run capacitor µF 1.2
VAC 440
Remote Control Unit RCS-3HVPSS4E
9
2-2-2. Outdoor Unit
Outdoor Unit SAP–CRV93EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Compressor
Type DC Rotary (Hermetic)
Compressor model / Nominal output G4C090LU1ER / 600W
Compressor oil … Amount cc FV50S … 320
Coil resistance (Ambient temp. 20°C) U – V: 0.81
V – W: 0.81
W – U: 0.81
Safety devices
CT (Peak current cut-off control) YES
Compressor discharge temp. control YES
Operation cut-off control in abnormal ambient temp.
Run capacitor µF
VAC
Crankcase heater
Fan & Fan Motor
Type … Fan / Fan motor Propeller / AC motor
Q’ty … Dia. mm 1 … 370
Fan motor model … Q’ty IB-976-501 … 1
No. of poles … Rough measure rpm (Cool / Heat) 6 … 700 / 700
Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT BRN: 213
RED (PNK) WHT: 168
— :
Safety devices Type Thermal fuse
Operating temp. Open °C 150
Close °C
Run capacitor on control PCB (A) µF 2.0
VAC 440
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.4
Face area m
2
0.288
External Finish Acrylic baked-on enamel finish
Control PCB (A) / Control PCB (B)
Part No. CB-CRV93EH (POW-CRV93GJH)
Controls Microprocessor
Control circuit fuse 250V, 20A
10
Outdoor Unit SAP–CRV123EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Fan & Fan Motor
Type … Fan / Fan Motor Propeller / DC Motor
Q’ty … Dia. mm 1 … 370
Fan motor model … Q’ty DAJ12-55J71-C … 1
No. of poles … Rough measure rpm (Cool / Heat) 8 … 750 / 750
Nominal output W 50
Coil resistance (Ambient temp. 20°C)
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor on control PCB (A) µF
VAC
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.4
Face area m
2
0.367
External Finish Acrylic baked-on enamel finish
Control PCB (A) / Control PCB (B)
Part No. CB-CRV123EH (POW-CRV123GJH)
Controls Microprocessor
Control circuit fuse 250V, 20A
Compressor
Type DC Rotary (Hermetic)
Compressor model / Nominal output G4C090LU1ER / 600W
Compressor oil … Amount cc FV50S … 320
Coil resistance (Ambient temp. 20°C) U – V: 0.81
V – W: 0.81
W – U: 0.81
Safety devices
CT (Peak current cut-off control) YES
Compressor discharge temp. control YES
Operation cut-off control in abnormal ambient temp.
Run capacitor µF
VAC
Crankcase heater
11
2-3. Other Component Specifications
Indoor Unit SAP–KRV93EH
SAP–KRV123EH
Outdoor Unit SAP–CRV93EH
SAP–CRV123EH
0
0 102030405060708090
40
60
80
100
120
140
160
180
200
20
10
1
2
3
4
5
6
7
8
9
10
15 20 25 30 35 40
• Indoor air temp sensor
• Indoor heat exchanger sensor
• Compressor temp sensor
Resistance (k)
Resistance (k)
Temperature (°C)
Temperature (°C)
• Outdoor air temp sensor
• Outdoor heat exchanger sensor
40
35
30
25
20
15
10
5
0
–20 –15 –10 –5 0 5 10 15 20
Temperature (°C)
Resistance (k)
12
5 5815
825
285
567
189 3
45
24.5 56
815
56 79.5
40
40
450187.5
178.9
Wide tube ø9.52(3/8")
Drain hose ø18
Narrow tube ø6.35(1/4")
187.5
178.9
86.5
86.5 45
360
(ø65)
308
187.5187.5
92.5122.5
70
825
450
45
285
40
(ø65)
24.5
40
196
46.5 27.4
70
32
133.8
52 23
3. DIMENSIONAL DATA
Indoor Unit SAP-KRV93EH
SAP-KRV123EH
Unit: mm
13
Outdoor Unit SAP-CRV93EH
SAP-CRV123EH
720 72
Wide tube service valve
ø9.52 (3/8")
2-ø12 holes
Narrow tube service valve
ø6.35 (1/4")
548
16
109 55
155
2
91
265
91
290
316
538
275
AIR DISCHARGE
(12 class only)
AIR INTAKE
AIR INTAKE
12
ID:2-ø23.6
ID:ø18
Unit: mm
14
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Indoor Unit SAP-KRV93EH Outdoor Unit SAP-CRV93EH
SAP-CRV123EH SAP-CRV123EH
Compressor
4-way
valve
Accumulator
Wide tube
service
valve
Wide tube
O.D.
ø9.52 mm
(3/8 ")
Narrow
tube
service
valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Heat exchanger
Heat exchanger
Muffler
Capillary
tube for
split flow
Cooling cycle
(Defrosting cycle)
Heating cycle
Indoor unit Outdoor unit
Electric
expansion
valve
M
Modulator
(12 class only)
Strainer
Muffler
(12 class only)
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
IMPORTANT
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
IMPORTANT
CAUTION
15
5. PERFORMANCE DATA
5-1. Temperature Charts
Indoor Unit SAP-KRV93EH
Outdoor Unit SAP-CRV93EH
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes
extremely high in heating mode. (Refer to “9-2. Overload prevention during heating.”)
Points of rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B. / 24°C W.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
NOTE
Cooling Characteristics Heating Characteristics
25 30 35 40
25 30 35 40
17
16
15
14
13
12
11
10
–5 0 5 10 15 20 25
3
2
8
9
6
7
4
5
–5 0 5 10 15 20 25
60
55
50
45
40
35
30
25
Outdoor inlet air D.B. temp.( C)
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
Operating current (A)
Operating current (A)
Indoor discharge air temperature ( C)
Indoor discharge air temperature ( C)
–5 0 5 10 15 20 25
Outdoor inlet air D.B. temp.( C)
25 30 35 40
4
5
3
2
1.2
(11.2)
1.3
(12.2)
1.1
(10.2)
1.0
(9.2)
3.5
(34.7)
3.0
(29.6)
2.5
(24.5)
2.0
(19.4)
Low pressure at wide tube service valve
MPa (kgf/cm
2
G)
High pressure at wide tube service valve
MPa (kgf/cm
2
G)
27
°C
24
°C
Indoor Air Temp.30°C
24
°C
27
°C
Indoor Air Temp.30°C
27
°C
24
°C
Indoor Air Temp.30°C
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23°C
20
°C
17
°C
Indoor Air Temp.23°C
16
Indoor Unit SAP-KRV123EH
Outdoor Unit SAP-CRV123EH
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes
extremely high in heating mode. (Refer to “9-2. Overload prevention during heating.”)
Points of rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B. / 24°C W.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
NOTE
Cooling Characteristics Heating Characteristics
Low pressure at wide tube service valve
MPa (kgf/cm
2
G)
High pressure at wide tube service valve
MPa (kgf/cm
2
G)
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
Operating current (A)
Operating current (A)
Indoor discharge air temperature ( C)
Indoor discharge air temperature ( C)
25
1.3
(12.2)
1.0
(9.2)
1.1
(10.2)
30 35 40
1.2
(11.2)
Outdoor fan speed
HighLow
25
4
6
8
9
3
2
5
7
30 35 40
Outdoor fan speed
HighLow
25
8
10
12
14
16
18
30 35 40
Outdoor fan speed
HighLow
50 5 10152025
2.0
(19.4)
2.5
(24.5)
3.0
(29.6)
3.5
(34.7)
50 5
4
6
8
9
3
2
5
7
10 15 20 25
50 5 10
30
6
25
35
40
45
50
55
20
60
15 20 25
27
°C
24
°C
Indoor Air Temp.30°C
20
°C
17
°C
Indoor Air Temp.23°C
Indoor Air Temp.23°C
17
°C
20
°C
Indoor Air Temp.30
°C
24
°C
27
°C
17
°C
23°C
20
°C
27
°C
24
°C
30°C
17
5-2. Air Throw Distance Charts
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C
Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C
Fan speed : High
Cooling
1
2
3
4
123456789
: Flap angle 0° , : Axis air velocity 0°
: Flap angle 30°, : Axis air velocity 30°
1
2
3
4
123456789
: Flap angle 45° , : Axis air velocity 45°
: Flap angle 60° , : Axis air velocity 60°
Indoor Unit SAP–KRV93EH
18
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 20°C
Fan speed : High
Heating
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Room air temp. : 27°C
Fan speed : High
Cooling
1
2
3
4
123456789
: Flap angle 0° , : Axis air velocity 0°
: Flap angle 30°, : Axis air velocity 30°
1
2
3
4
123456789
: Flap angle 45° , : Axis air velocity 45°
: Flap angle 60° , : Axis air velocity 60°
Indoor Unit SAPKRV123EH
19
5-3. Operating Frequency Charts
0
1
2
3
4
5
0 1020304050607080
Operating Freqency (Hz)
Cooling Capacity (kW)
54
Min.
Center
Max.
0
200
400
600
800
1000
1200
0 1020304050607080
Operating Freqency (Hz)
Power Input (W)
54
Min.
Center
Max.
755
2.65
Indoor Unit SAP–KRV93EH
Outdoor Unit SAP–CRV93EH
230V Single-phase 50Hz
NOTE
1) Rating conditions in cooling are:
Indoor: 27°C D.B. / 19°C W.B.
Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
Cooling
20
0
1
2
3
4
5
0 20 40 60 80 100 120
Operating Freqency (Hz)
Heating Capacity (kW)
3.6
Min.
Center
Max.
75
0
200
400
600
800
1000
1200
1400
0 20 40 60 80 100 120
Operating Freqency (Hz)
Power Input (W)
995
Min.
Center
Max.
75
230V Single-phase 50Hz
NOTE
1) Rating conditions in heating are:
Indoor: 20°C D.B.
Outdoor: 7°C D.B. / 6°C W.B.
2) Fan speed: High
Heating
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77