Rosemount 644 Temperature Transmitter Owner's manual

Type
Owner's manual
www.rosemount.com
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644 Temperature Transmitter
with Profibus PA
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
www.rosemount.com
Rosemount 644 Temperature
Transmitter with Profibus PA
Rosemount 644 Hardware Revision 9
NOTICE
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-(952) 906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact an Emerson Process
Management Sales Representative.
Reference Manual
00809-0300-4728, Rev AA
January 2011
TOC-1
Rosemount 644
SECTION 1
Introduction
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Transmitter Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Device Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
SECTION 2
Configuration
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Configuration Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Profile 3.02 Identification Number Adaptation Mode . . . . . . . . . . . 2-3
Block Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Configuration Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Basic Setup Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Device Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Assign Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Default Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Transmitter Setup Using Class 2 Master . . . . . . . . . . . . . . . . . . . . . . . 2-4
Basic Transmitter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Transmitter Online Setup with DD or DTM . . . . . . . . . . . . . . . . . . . . . 2-6
Basic Transmitter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
SECTION 3
Hardware Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Typical European Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Typical North American Installation . . . . . . . . . . . . . . . . . . . . . . . . 3-4
LCD Display Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
SECTION 4
Electrical Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Sensor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Ground the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Table of Contents
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
TOC-2
SECTION 5
Calibration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
SECTION 6
Troubleshooting
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Diagnostics Identification and Recommendation. . . . . . . . . . . . . . . . . 6-2
Extended Diagnostics Identification with class one master . . . . . . 6-4
PlantWeb and NE107 Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Alert Messages and Fail Safe Type Selection . . . . . . . . . . . . . . . . . . . 6-6
APPENDIX A
Specifications and
Reference Data
Profibus PA Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Functional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Tagging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
APPENDIX B
Product Certifications
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
European Union Directive Information. . . . . . . . . . . . . . . . . . . . . . . . . B-1
Hazardous Locations Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Rosemount 644 with Profibus PA. . . . . . . . . . . . . . . . . . . . . . . . . . B-2
IECEx Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Russian GOST Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Kazakhstan GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Ukraine GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
APPENDIX C
Profibus Block
Information
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Condensed Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-7
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
www.rosemount.com
Section 1 Introduction
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-2
Transmitter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-2
Device Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-3
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1-4
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
Before connecting Profibus devices in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-intrinsic field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
1-2
USING THIS MANUAL The sections in this manual provide information on installing, operating, and
maintaining the Rosemount 644 with Profibus PA protocol. The sections are
organized as follows:
Section 2: Configuration provides instruction on commissioning and operating
the Rosemount 644 PA transmitter. Information on software functions,
configuration parameters, and online variables is also included.
Section 3: Hardware Installation contains mechanical mounting and
installation instructions, and field upgrade options.
Section 4: Electrical Installation contains electrical installation instructions,
with wiring and power considerations.
Section 5: Calibration contains techniques for calibration and troubleshooting
Appendix A: Specifications and Reference Data supplies reference and
specification data, as well as ordering information.
Appendix B: Product Certifications contains intrinsic safety approval
information, European ATEX directive information, and approval drawings.
Appendix C: Profibus Block Information contains Profibus block and
parameter information.
TRANSMITTER
OVERVIEW
Features of the Rosemount 644 with Profibus PA include:
Accepts inputs from a wide variety of sensors (T/C, RTD, Ohm, mV)
Configuration using Siemens SIMATIC PDM
Electronics that are completely encapsulated in epoxy making the
transmitter extremely durable and ensuring long-term reliability
A compact size and a variety of housing options allowing mounting
flexibility for the control room or the field
Refer to the following literature for a full range of compatible connection
heads, sensors, and thermowells provided by Emerson Process
Management.
Temperature Sensors and Assemblies Product Data Sheet, Volume 1
(document number 00813-0100-2654)
Temperature Sensors and Assemblies Product Data Sheet, Volume 2
(document number 00813-0200-2654)
Rosemount 1067 compact sensor and 1097 Thermowell Product Data
Sheet (00813-0100-4951)
Rosemount 65Q and 65B Resistance Temperature Sensors for
Hygienic and Sanitary Applications Product Data Sheet
(00813-0100-4827)
NOTE
For Rosemount 644 with HART
®
or FOUNDATION
fieldbus, see Rosemount
Product Manual 00809-0100-4728.
Reference Manual
00809-0300-4728, Rev AA
January 2011
1-3
Rosemount 644
DEVICE REVISION
Table 1-1. Device Revisions
(NE53)
CONSIDERATIONS
General Electrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to their sensed temperature. The 644 converts
the low-level sensor signal to digital Profibus PA signal that is relatively
insensitive to lead length and electrical noise. This signal is then transmitted
to the control room via two wires.
Commissioning The transmitter can be commissioned before or after installation. It may be
useful to commission it on the bench, before installation, to ensure proper
operation and to become familiar with its functionality. Make sure the
instruments in the loop are installed in accordance with intrinsically safe,
FISCO, or non-incendive field wiring practices.
Mechanical Location
When choosing an installation location and position, take into account the
need for access to the transmitter.
Special Mounting
Special mounting hardware is available for mounting a 644 head mount
transmitter to a DIN rail, or assembling a new 644 head mount to an existing
threaded sensor connection head (former option code L1).
Electrical Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. For best results, shielded cable should be
used in electrically noisy environments.
Make wiring connections through the cable entry in the side of the connection
head. Be sure to provide adequate clearance for cover removal.
Environmental The transmitter electronics module is permanently sealed within the housing,
resisting moisture and corrosive damage. Verify that the operating
atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures
between –40 and 185 °F (–40 and 85 °C). Heat from the process is
transferred from the thermowell to the transmitter housing. If the expected
process temperature is near or beyond specification limits, consider the use of
additional thermowell lagging, and extension nipple, or a remote mounting
configuration to isolate the transmitter from the process.
Date
Software
Revision
Profibus
Profile
Changes to
Software
Compatible Files
Manual
Revision
11/10 1.01.016 3.02 New
Product
644 GSD: EPM1039.gsd
Profile:3.02 GSD: pa139700.gsd
DD: see Rosemount.com
DTM: see Rosemount.com
AA
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
1-4
Figure 1-1 provides an example of the relationship between transmitter
housing temperature rise and extension length.
Figure 1-1. 644 head mount
Transmitter Connection Head
Temperature Rise vs. Extension
Length
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C
and the process temperature to be measured is 800 °C, the maximum
permissible connection head temperature rise is the transmitter specification
limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 100 mm meets this requirement, but 125 mm
provides a margin of 8 °C, thereby reducing any temperature effects in the
transmitter.
RETURN OF MATERIALS To expedite the return process in North America, call the Emerson Process
Management National Response Center toll-free at 800-654-7768. This
center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for the following information:
Product model
Serial numbers
The last process material to which the product was exposed
The center will provide
A Return Material Authorization (RMA) number
Instructions and procedures that are necessary to return goods that
were exposed to hazardous substances
For other locations, please contact an Emerson Process Management sales
representative.
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS),
required by law to be available to people exposed to specific hazardous
substances, must be included with the returned materials.
Housing Temperature Rise, Above
Ambient °C (°F)
3 4 5 6 7 8 9
0
60 (108)
50 (90)
40 (72)
30 (54)
20 (36)
10 (18)
3.6
22
Extension Length (in.)
815 °C (1500 °F) Oven Temperature
540 °C (1000 °F)
Oven Temperature
250 °C (482 °F) Oven Temperature
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
www.rosemount.com
Section 2 Configuration
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-1
Configuration Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-3
Basic Setup Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-3
Transmitter Setup Using Class 2 Master . . . . . . . . . . . . .page 2-4
Transmitter Online Setup with DD or DTM . . . . . . . . . . . .page 2-6
SAFETY MESSAGES Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
Before connecting Profibus devices in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
2-2
Figure 2-1. Configuration
Flowchart
START
HERE
Bench
Calibration?
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
Refer to Section 2: Configuration
FIELD INSTALL
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED
Reference Manual
00809-0300-4728, Rev AA
January 2011
2-3
Rosemount 644
CONFIGURATION
GUIDELINES
To configure on the bench, required equipment includes a power supply, a
class 2 master with DP/PA coupler, proper cable, and terminators. Verify that
the Security hardware jumper is set to the OFF position in order to proceed
with configuration. See Figure 4-2 for jumper location.
Setup for the Rosemount 644 can be done via Siemens SIMATIC
®
PDM
software or any other DD or DTM based Class 2 master.
Profile 3.02 Identification
Number Adaptation
Mode
Rosemount 644 Profibus Profile 3.02 devices are set to Identification Number
Adaptation Mode when shipped from the factory. This mode allows the
transmitter to communicate with any Profibus class 1 master with either the
generic Profile GSD (9700) or Rosemount 644 specific GSD (1039).
Block Modes When configuring a device with a class 2 master, it is best practice to set
blocks to OOS when downloading parameters that affect the transmitter
output. However, the 644 will allow configuration changes made in AUTO to
be downloaded to the device. This prevents the class one master from seeing
a jump in output without a status change. Setting the blocks OOS and back
into Auto is done automatically when using the class two master configuration
wizards within the Rosemount 644 DD or DTM. This is done so no additional
action is required when configuring the device.
Configuration Tools The Rosemount 644 can be configured through the factory at order entry or
using a class 2 master. The C1 option code must be ordered to obtain
addressing and configuration of the device at the factory.
Class 2 masters require either DD or DTM files for configuration. These files
can be found at www.rosemount.com or by contacting your local Emerson
Process representative.
The remainder of this section will cover the configuration tasks using the
Class 2 master configuration tool.
NOTE
Instructions in this section use the terminology found in the class 2 master.
See Appendix C: Profibus Block Information to cross reference parameters
between the class2 master, and the Profibus specification.
BASIC SETUP TASKS
Device Description Before configuring the device, ensure the host has the appropriate Device
Description file revision for this device. The device descriptor can be found on
www.rosemount.com. The initial release of the Rosemount 644 with Profibus
PA protocol is device revision 1.
Assign Address The Rosemount 644 is shipped with a temporary address of 126. This must
be changed to a unique value between 1 and 125 in order to establish
communication with the class 1 master. Usually, addresses 1-2 are reserved
for masters, therefore transmitter addresses between 3 and 125 are
recommended for the device.
Address can be set using either:
Factory Configuration (C1 option code)
Class 2 master – see respective class 2 master manual for setting
instrument addresses
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
2-4
Default Configuration Unless otherwise specified, the Rosemount 644 will be shipped with the
following settings:
Table 2-1. Temperature
configuration defaults
TRANSMITTER SETUP
USING CLASS 2
MASTER
Basic Transmitter Setup
Table 2-2. Basic Transmitter
Configuration using Class 2
master
Process Alarms Process alarms activate an output alarm status when the configured alarm
point is exceeded. A process alarm will be transmitted continuously if the
output set points are exceeded. The alarms will reset once the value returns
within range.
Process Alarm parameters are defined as follows
HI-HI Alarm: Changes Output Status to Good – Critical Alarm – Hi Limit
HI Warning: Changes Output Status to Good – Advisory Alarm – Hi
Limit
LO Warning: Changes Output Status to Good – Advisory Alarm – Lo
Limit
LO-LO Alarm: Changes Output Status to Good – Critical Alarm – Lo
Limit
Alarm Hysteresis: Amount the output value must pass back into range
before alarm is cleared.
Example: Upper Alarm = 100 °C. Alarm Hysteresis = 0.5 °C. After
activation at 100 °C, the alarm will clear once the output goes below
99.5 °C = 100 - 0.5 °C.
Process Alerts can be set using,
Class 2 master – see Table 2-3 for configuration
Device Address: 126
Sensor Type: RTD, Pt 100 (= 0.00385, 4 wire)
Damping: 5 sec.
Units of Measurement: °C
Alarm Limits:
HI-HI: Infinity
HI: Infinity
LO: - Infinity
LO-LO: Infinity
Local Display (when installed): Engineering Units of Temperature
Measurement Range: 0 °C to 100 °C
Desired Action Menu >> Parameter >> Value
Set Sensor Type Primary Value>>Sensor>>Sensor Type
Set Connection Type (Number of Wires) Primary Value>>Sensor>>Sensor Connection
Set Units
*
Primary Value>>Sensor>>Primary Value Unit
Set Upper Range Value Primary Value>>Process Value Scale>>Upper Value
Set Lower Range Value Primary Value>>Process Value Scale>>Lower Value
Set Damping Value Primary Value>>Sensor>>Damping Value
* Please see “Basic Transmitter Configuration using DD or DTM” on page 2-6 for considerations
when changing units.
Reference Manual
00809-0300-4728, Rev AA
January 2011
2-5
Rosemount 644
Table 2-3. Process Alarm
Configuration using Class 2
master
Simulation Simulation is in the AI block and used to verify the output from the transducer
block. The Rosemount 644 has a simulation jumper located on the transmitter
puck top cover that must be set to the ON position in order to simulate.
NOTE
This jumper position is ignored when the transmitter is initially powered. The
jumper position must be changed while the transmitter is powered to activate
simulation. If power is removed and restored, the simulation mode will be OFF
regardless of jumper position.
With simulation enabled, the actual measurement value has no impact on the
OUT value or the status. The OUT value will equal the simulated value from
the transducer block plus any scaling or linearization effects performed in the
AI block.
Once the simulation jumper is set to on, simulation mode can be activated
Using a Class 2 master see Table 2-4.
Table 2-4. Simulation
configuration using Class 2
master
Desired Action Menu Path
Enter Process Alarm Levels Output>>Output Limits>>LO-LO Alarm
Output>>Output Limits>>LO Warning
Output>>Output Limits>>HI Warning
Output>>Output Limits>>HI- HI Alarm
Desired Action Menu >> Parameter >> Value
Enable Simulate Main Setup>>Human Interface>>
Simulation Status>>State>>
Select Enabled
Enter Simulation Value
Select Simulation Status>>Press “Download
to device” icon
Disable Simulate Main Setup>>Human Interface>>
Simulation Status>>State>>
Select Disabled
Press “Download to device” icon
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
2-6
TRANSMITTER ONLINE
SETUP WITH DD OR DTM
Basic Transmitter Setup
Table 2-5. Basic Transmitter
Configuration using DD or DTM
Using Guided Setup
Using Manual Setup
NOTE
Changes made to the PRIMARY_VALUE_UNIT parameter through Manual
Setup>>Classic View are only reflected in the Transducer Block parameters.
To change the AI OUT units the PV Scale and OUT Scale need to be updated
to mirror the upper and lower sensor limits in the desired units.
Example: (All values are arbitrary)
The default configuration of the device is:
If the user desires to change the units to °F, only the parameters in Bold will
change with the PRIMARY_VALUE_UNIT. The AI.OUT will stay in °C until the
PV_SCALE and OUT_SCALE are configured to match each other. (This can
be with the measurement range or the sensor limits.
So the following change is needed:
PV_SCALE = 1562,-328 (make the same as USL and LSL)
OUT_SCALE = 1562,-328, °F (make the same as PV_SCALE)
Desired Action Menu >> Category >> Method
Set Sensor Type Configure>>Guided Setup>>Configure Sensor Method
Set Connection Type Configure>>Guided Setup>>Configure Sensor Method
Set Units Configure>>Guided Setup>>Configure Sensor Method
Set Damping Configure>>Guided Setup>>Configure Sensor Method
Desired Action Menu >> Category >> Tab >> Value
Set Sensor Type Configure>>Manual Setup>>Sensor>>Sensor Type
Set Connection Type
(Number of Wires)
Configure>>Manual Setup>>Sensor>>Sensor
Connection
Set Units Configure>>Manual Setup>>Classic
View>>Transducer Block>>Primary Value Unit
Set Damping Configure>>Manual Setup>>Sensor>>Damping Value
Set Upper Range Value Configure>>Manual Setup>>Classic View>>Analog
Input Block>>Analog Input Block_1>>Lower Range
Set Lower Range Value Configure>>Manual Setup>>Classic View>>Analog
Input Block>>Analog Input Block_1>>Upper Range
4-wire PT100_A_385 AI.OUT = 23 °C
PRIMARY_VALUE_UNIT = °C PV_SCALE = 100, 0
PV.VALUE = 23 °C OUT_SCALE = 100,0, °C
SV.VALUE = 23 °C
USL = 850 °C
LSL = -200 °C
4-wire PT100_A_385 AI.OUT = 23 °C
PRIMARY_VALUE_UNIT = °C PV_SCALE = 212, 32
PV.VALUE = 73 °C OUT_SCALE = 100,0, °C
SV.VALUE = 73 ° C
USL = 1562 °C
LSL = -328 °C
Reference Manual
00809-0300-4728, Rev AA
January 2011
2-7
Rosemount 644
Process Alarms Process Alarms can be set using a DD or DTM – see Table 2-6 for
configuration.
Table 2-6. Process Alarm
Configuration using DD or DTM
LCD Display The LCD display connects directly to the top of the transmitter puck and uses
a 10-pin connector to directly connect to the electronics board. A display
cover is provided to accommodate the display.
The display always indicates the transmitter output temperature as well as
abbreviated diagnostic status when applicable. When turned on, the display
will alternate between the selected variables.
For LCD display configuration using a DD or DTM see Table 2-7.
Table 2-7. LCD Display
Configuration using DD or DTM
Simulation Once the simulation jumper is set to on, simulation mode can be activated
Using DD or DTM see Table 2-8.
Table 2-8. Simulation
Configuration using DD or DTM
Desired Action Menu Path
Enter Process Alert Levels Configure>>Alarm Setup>>LO-LO>>[Value]
Configure>>Alarm Setup>>LO>>[Value]
Configure>>Alarm Setup>>HI >>[Value]
Configure>>Alarm Setup>>HI-HI >>[Value]
Desired Action Menu >> Parameter >> Value
Select Display Parameters Configure>>Manual Setup>>Display Tab>>Select
Parameters to display
Desired Action Menu >> Parameter >> Value
Enable Simulate Service Tools>>Simulate>>Select Enabled State
Enter Simulation Value
Select Simulation Status>>Press Transfer button
Disable Simulate Service Tools>>Simulate>>Select Disabled State
>>Press Transfer button
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
2-8
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
www.rosemount.com
Section 3 Hardware Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-3
OVERVIEW The information in this section covers installation considerations for the
Rosemount 644. A Quick Installation Guide is shipped with every transmitter
to describe pipe-fitting, wiring procedures, and basic configuration for initial
installation.
SAFETY MESSAGES Procedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the following safety messages before performing an operation preceded by
this symbol.
Warnings
Individual transmitters are clearly marked with a tag indicating the approvals
they carry. Transmitters must be installed in accordance with all applicable
codes and standards to maintain these certified ratings. Refer to ““Hazardous
Locations Certificates” on page B-2 for information on these approvals.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the approvals section of this reference manual for any restrictions associated with a safe
installation.
In an Explosion-Proof/Flameproof installation, do not remove the transmitter
covers when power is applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
Reference Manual
00809-0300-4728, Rev AA
January 2011
Rosemount 644
3-2
MOUNTING Mount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
The 644 head mount installs
In a connection head or universal head mounted directly on a sensor
assembly
Apart from a sensor assembly using a universal head
To a DIN rail using an optional mounting clip.
The 644 rail mount attaches directly to a wall or to a DIN rail.
Mounting a 644H to a DIN Rail
To attach a head mount transmitter to a DIN rail, assemble the appropriate rail
mounting kit (part number 00644-5301-0010) to the transmitter as shown in
Figure 3-1.
Figure 3-1. Assembling Rail Clip
Hardware to a 644
Retrofitting a 644H for Use in an Existing Threaded Sensor Connection
Head
To mount a 644 in an existing threaded sensor connection head (former
option code L1), order the 644H retrofit kit (part number 00644-5321-0010).
The retrofit kit includes a new mounting bracket and all associated hardware
necessary to facilitate the installation of the 644H in the existing head. See
Figure 3-2.
G-Rail (asymmetric) Top Hat Rail (symmetric)
Note: Kit includes Mounting Hardware and both types of Rail Kits.
Transmitter
Mounting
Hardware
Rail Clip
Transmitter
Mounting
Hardware
Rail Clip
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88