Kampmann Tandem, KaControl version Installation Plan

  • Hello! I've reviewed the instructions for the KAMPMANN KaControl system, which includes details on wiring the Tandem air curtain system, along with components such as the Type 30510 speed controller, Type 3250110 room temp sensor, and Type 3210002 KaController. I'm familiar with the cabling diagrams, BUS communication, and the use of potential-free contacts. I'm ready to answer your questions about the document.
  • What is the maximum length of the BUS cable from the KaController to unit 1?
    What is the maximum number of parallel units?
    What type of cable should be used for BUS communication?
Tandem
01/21 EN
Cabling of Tandem with KaControl (*C1)
Fuse
by others
Mains
230 V/50 Hz
Smartboard PCB
PCB
PUR-T-EC01
Unit no. 1
Door air curtain EC
KaControl (C1)
Shut-off valve 230 V
AC
type 100913
Speed controller
Type 30510
Type 3250110
(optional)
Room
temperature
sensor
Door air curtain EC (*00)
Unit no. 2
Shut-off valve 230 V
AC
type 100913
To further door air
curtains
(Refer to information
for maximum number)
Potential-free
changeover contact
parametrisable
function
(factory-fitted unit
alarm)
Potential-free contact
wired to digital input D12
(Optional)
Refer to instructions for
possible functions!
Factory setting speed
increase via door contact
Contact closed = door closed
Potential-free contact
wired to digital input D11
KaController
Type 3210002
(Optional)
Refer to instructions for
possible functions!
Default setting
Remote ON/OFF
Contact closed = OFF
Cabling information:
• Comply with the details on type of cable and cabling taking into consideration VDE 0100.
* Without * NYM-J. The requisite number of wires including fuse is stated on the cable. No cross-section is specified, cable length is involved in calculation of the cross-section.
• With * IY(ST)Y 0.8 mm. Lay separately from power lines.
• With ** UNITRONIC BUS LD 0.22 mm2. Lay separately from power lines.
If you are using different cable types they must be at least equivalent to these.
• Length of BUS cable from the KaController room control unit to unit 1: max. 30 m.
• Maximum number of parallel units: 6 units. The number can be increased to a maximum of 30 using CANBUS cards type 3260701 needed for each unit (see accessories).
• Cable length of BUS line from unit 1 to the last unit, maximum 30 m. CANBUS cards type 3260701 needed for each unit (see accessories) maximum 300 m.
/