2
VI.UL.B1.02 Produced by Danfoss Floor Heating Hydronics · 08.2005
Instruction Shunt FHM-DK1/-K2
Design: The shunt is delivered assembled and can be
mounted directly on the manifold. As standard,
the shunt is delivered for left-side mounting.
However, it can be reversed.
Connection for ow and return ow is marked
with arrows on the shunt. Connection from below
(standard), from the side or from the top.
We recommend that, especially in connection
with district heating substations for direct heat-
ing, a dirt collector be mounted before the shunt
together with a possible dierential pressure
controller, (e.g. Danfoss AVPL).
Wiring diagram: All electric connections must be performed by
authorised personnel according to current rules
and regulations.
The Danfoss AT thermostat is a safety thermostat
for the protection of e.g. wooden oors against
NB: Cut o the power supply before opening/
setting the AT thermostat!
To set the AT thermostat, loosen the two screws
and lift o the housing.
In the top haIf, you will nd a temperature selec-
tor (see arrow), and the temperature scale is
marked on the base plate. Change the tempera-
ture by turning the selector.
The shut-down temperature should be 5-10 °C
over the operational temperature for the shunt.
This, however, depends on the ooring and pip-
ing. The recommended maximum temperature
of the supplier must be observed.
Screw the house back on when you have com-
pleted the setting.
Setting the AT
safety thermostat
(only FHM-DK1):
To check the temperature setting, e.g. on service
visits, remove the dark grey cover.
Example of system:
high temperatures. In the event of over tempera-
ture, the AT thermostat cuts o the oor-heating
control so as to close the thermal actuators.
If no controls are connected, the AT thermostat
will shut down e.g. the boiler or pump.
FHM-DK1
FHM-DK2