APC 66124 User manual

Category
Networking
Type
User manual
3402231500/AC
990-3402231500AC
Installation manual
Network
Management
Teleservice Card
(66124)
66124
SENSOR/RS 485
ETHERNET
( Settings)
100M
UPS Data CD
PHONE
RESET
ACT
3402231500/AC
The Network Management Teleservice Card (66124) is
recommended for central UPSs protecting entire networks or for UPS
units backing up critical loads.
With the card installed, the UPS has its own IP address and uses the
local computer capabilities to:
supply web pages (http or https (SSL)) with information on status
conditions and measurements/settings/alarms,
integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli
Netview and Computer Associates Unicenter,
communicate with shutdown modules installed on the protected
servers (Network Shutdown Module),
send e-mail and SMS messages,
control the ON/OFF function of the UPS and the outlets,
monitor the Environment Sensor,
Access the Teleservice solution for remote monitoring and
maintenance services of your UPS.
One Network Management Teleservice Card (66124),
One serial cable for configuration (3402226700),
One phone cable for teleservice (3402226800),
One installation manual (34022315EN),
One Teleservice information form (3402228500),
PHONE port
ETHERNET port
Service port (Sensor/RS485)
Default settings, sensor configuration :
INTRODUCTION
The Network Management Teleservice Card must be
installed and used in accordance with manufacturer
instructions.
UNPACKING AND CHECKS
Installation manual
Network
Management
Teleservice Card
(66124)
66108
Settings/Sensor
ETHERNET
UPS data RS232
100M
10M
Settings/Sensor
Settings/Sensor
Settings/Sensor
Settings/Sensor
66124
S
ettin
g
s/S
en
so
r
E
TH
E
R
N
E
T
U
P
S
d
ata
R
S
23
2
10
0
M
1
0
M
S
e
ttin
g
s
/S
en
so
r
S
ettin
g
s/S
e
n
so
r
S
e
t
t
i
n
g
s
/
S
e
n
s
o
r
S
e
t
t
in
g
s
/S
e
n
s
o
r
OVERVIEW
INDICATIONS
LED Colour Status Description
UPS Data Green OFF
ON
Flashing
Card not connected to phone
network
Card connected to phone
network, but no activity
Port is sending/receiving
CD Orange
OFF
ON
Flashing
Modem is not connected
Modem is connected
Modem is connecting
LED Colour Status Description
ACT Green OFF
ON
Flashing
Card not connected to network
Card connected to network, but
no activity
Port is sending/receiving
100M Orange
OFF
ON
Port operating at 10 Mbits/s
Port operating at 100 Mbits/s
LED Colour Status Description
Sensor Green OFF
ON
Flashing
Card starting
Card ready
Communication with environment
Sensor is operational
RS485 Orange
OFF
Flashing
Flashing
every seconds
Settings mode activated
Port is sending/receiving
Communication fault or
configuration errors
SWITCHES SETTING
MAC adress
PHONE port:
Green LED : Phone communication
with the UPS
Orange LED : Modem connection
ETHERNET port:
Green LED : Connection + activity
Orange LED : 10/100 M
Service port (Sensor/RS485):
Green LED : Communication with
the UPS
Orange LED :RS232 activity
Catalogue number
66124
SENSOR/RS 485
ETHERNET
( Settings)
100M
UPS Data CD
PHONE
RESET
AC
T
000623001C07
000623001C07
SA2
1
8
3
SA1
1
8
3
OFF
ON
OFF
ON
3402231500/AC
The Network Management Teleservice Card (66124) can be hot-
plugged on MGE
TM
Galaxy
TM
7000 UPSs. It is not necessary to
shutdown the UPS, disconnect the load or restart the UPS.
A. Remove the plastic cover of the Minislot.
B. Note the MAC address of the card before inserting it.
C. Connect the PHONE cable.
D. Connect the ETHERNET cable (network already connected).
E. Insert and secure the card with the screws.
Check the ETHERNET port indications.
Wait until the UPS Data LED flashes regularly (approx. two minutes),
indicating that card start-up has terminated correctly.
Once the card has started, proceed as indicated below.
Connect one end of the serial cable to the Service port.
Connect the other end of the cable to the COM (IOIOI) port of a PC.
Run a terminal emulator such as HyperTerminal
TM
with these settings
"Echo typed characters locally" option: disabled
Press the
key.
press the 1 key (Network configuration menu)
Type MGEUPS (or mgeups), then press the
key.
The main configuration menu is displayed
:
The card is configured by default with this service enabled. No manual
configuration is required.The IP parameters are automatically collected
by the card.
To view the network configuration(from the main configuration
menu):
Press the 2 key (Network configuration), then press the
key.
Press the 1 key(Read Network settings)., then press the
key.
The settings supplied by the server are displayed:
Note the IP address.
Press the
key
Press the 0 key (Exit), then press the
key.
Press the 0 key (Exit), then press the
key.
Manual configuration is required.
To set the network configuration(from the main configuration menu):
Press the 2 key (Network configuration), then press the
key.
Press the 2 key (Modify Network settings), then press the
key.
Follow the instructions and enter the IP parameters:
Wait until "Done" is displayed, indicating that the IP parameters have
been saved.
Press the 0 key (Exit), then press the
key.
Press the 1 key (Reset), then press the
key.
The card restarts with the new IP settings (after approx. two minutes).
To check whether the
Network Management Teleservice Card
is
operational after installation and IP settings, proceed as follows.
Run a browser
Enter in the address bar:
http://IP address/ (e.g. http://172.16.1.82/)
The home page is displayed:
Set the time by clicking the Time command.
Continue configuration via the sections in the Settings menu.
Install the Network Management Teleservice Card kit using the
present manual.
Fill in the information form (3402228500).
Send the form to your Teleservice centre (by Fax or Internet).
Your centre will activate this service.
You receive an acknowledgement of receipt.
The information form must be sent back in order to trigger remote
monitoring of your equipment.
The manual (34003991EN) provides all the information required to use,
install and configure the
Network Management Teleservice Card
.
For more information on the supervision, control and configuration
functions offered by the
Network Management Teleservice Card
, see
the user manual on the
www.apc.com
web site.
INSTALLATION
IP SETTINGS
Bits per second Data bits Stop bits Flow control
38400 8 1 none
APC by Schneider Electric
NETWORK MANAGEMENT CARD
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
Your network is equipped with a BOOTP/DHCP server (default)
Network configuration :
MAC address : 00:06:23:00:1C:07
Mode : DHCP
IP address : 172.17.23.18
Subnet mask : 255.255.248.0
Gateway : 172.17.17
UPS
6
6
1
24
S
E
N
S
O
R
/R
S
4
8
5
E
T
H
E
R
N
E
T
(
S
e
t
t
in
g
s
)
1
0
0
M
U
P
S
D
a
ta
C
D
P
H
O
N
E
R
E
S
E
T
A
C
T
000623001C07
000623001C07
A
B
E
DC
Your network is not equipped with a BOOTP/DHCP server
1 : Read Network settings
2 : Modify Network settings
3 : Set ethernet speed
0 : Exit
For each of the following questions, you can press "Return" to select
the value shown in braces, or you can enter a new value
Should this target obtain IP settings from the network?[N] N
Static IP address [172.17.16.16]?172.16.1.82
Subnet mask IP address [255.255.0.0]? 255.255.255.0
Gateway address IP address [0.0.0.0]? 172.17.17.1
Done
ACCESS TO SUPERVISION
Teleservice procedure
USER MANUAL
3402231500/AC
The Environment sensor is a Network Management Teleservice
Card option.
The sensor remotely monitors the UPS environment by regularly
measuring the temperature and humidity, and checking the states of
two external contacts. It can also send alarms (e-mail, SNMP trap)
tripped by pre-set thresholds.
Connection is made via the Service port (Settings/Sensor) on the
Network Management Teleservice Card. The sensor is detected
automatically. Configuration and supervision use a menu that may be
accessed directly from the home page. For more information, see the
user manual of the Network Teleservice Management Card.
SENSOR CONNECTION (option)
66102
Settings/Sensor
ETHERNET
1
00
M
10
M
U
PS
d
at
a
R
S2
3
2
O
n =
L
i
nk
B
lin
k =
A
c
t
U
PS
dat
a
R
S2
3
2
Settings/Sensor
ETHERNET
PHONE
Settings/Sensor
ETHERNET
100
M
1
0M
Settings/Sensor
UPS
TECHNICAL CHARACTERISTICS
Physical characteristics
Dimensions (W x D x H) 132 x 66 x 42 mm
Weight 85 g
RoHS 100% compatible
Storage
Storage temperature
range
-10°C to 70°C
Ambient conditions
Operating temperature
range
0°C to 40°C
Relative humidity 90% RH max. without condensation
Card performance
Supply voltage 5V ±5%
Supply current (all LEDs
ON and Environment
Sensor connected)
500 mA max.
Functions
Web supervision 5 browsers max. (http),
3 browsers max. (https)
Languages English
Alarms E-mail, SNMP TRAP, Web page
Log 400 measurements or events
Server protection Up to 35 servers protected
Network Fast ETHERNET, 10/100 Mbits, auto-negotiation
HTTP 1.1, SNMP V1, NTP, TFTP, SMTP,
BOOTP/DHCP
Identification User name and password
Security SSL 3.0, TLS 1.0
Browsers Microsoft Internet Explorer 6.x or higher
NMS Enterprise Power Manager (EPM)
Management-Pac 2
MIB MIB II standard - MGE V1.7 MIB
Settings (default values)
IP network BOOTP/DHCP enabled
IP address: 172.17.16.16
Subnet mask: 255.255.0.0
Gateway: 0.0.0.0
NTP server: pool.ntp.org
Web-page access control User name: MGEUPS
Password: MGEUPS
Service-port menu access
control
Password: MGEUPS or mgeups
(not modifiable)
Date and time Synchronise with an NTP server (GMT)
Service port 38400 bits/s, 8 bits, 1 bit stop, no parity
Standards
ITE (Information
Technology Equipment)
safety
IEC/EN 60950-1 (2005)
R&TTE 99/05/EEC
EMC EN 61000-6-2 (2005), EN 61000-6-3 (2006)
2004/108/EEC
Low voltage 2006/95/EEC
FCC (Federal
Communication
Commission )
This equipment has been tested and found to
comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC rules. These limits
are designed to provide reasonable protection
against harmful interference when the equipment
is operated in a commercial environment.