Eaton Network Card-MS Quick Start

Category
Gateways/controllers
Type
Quick Start

Eaton Network Card-MS is a powerful networking device that seamlessly integrates with your ATS to provide remote monitoring, control, and configuration capabilities over an Ethernet network. With its SNMP and HTTP abilities, you can effortlessly manage your ATS from anywhere using a web browser or integrate it into your existing SNMP-based NMS, such as HP OpenView, IBM Tivoli Netview, or Computer Associates Unicenter. Additionally, it facilitates communication with IPM (Intelligent Power Manager) and allows for email notifications and comprehensive environment sensor monitoring.

Eaton Network Card-MS is a powerful networking device that seamlessly integrates with your ATS to provide remote monitoring, control, and configuration capabilities over an Ethernet network. With its SNMP and HTTP abilities, you can effortlessly manage your ATS from anywhere using a web browser or integrate it into your existing SNMP-based NMS, such as HP OpenView, IBM Tivoli Netview, or Computer Associates Unicenter. Additionally, it facilitates communication with IPM (Intelligent Power Manager) and allows for email notifications and comprehensive environment sensor monitoring.

3. INSTALLATION
• Use the provided MAC address label to identify the card.
• Connect the ETHERNET cable.
• Check the ETHERNET port indications.
• Wait until the Data LED flashes regularly (approx. three minutes), indicating that card start-up has terminated correctly.
Note: You can set the parameters via Service port even if the network is not connected. At connection, the card will restart keeping the settings.
4. IP SETTINGS
Once the card has started, proceed as indicated below:
• Connect the serial cable to card’s service port and PC’s COM port (shipped with the card)
• Use a terminal emulator such as PuTTY with these settings:
"Echo typed characters locally" option: disabled
• Type admin.
The main configuration menu is displayed:
Your network is equipped with a BOOTP/DHCP server (default)
The card is configured by default with this service enabled. No manual configuration is required. The IP parameters are
automatically collected by the card.
From the main configuration menu: (see above)
• Press the 2 key (Network configuration).
• Press the 1 key (Read Network settings).
The settings supplied by the server are displayed:
• Note the IP address.
• Press the 0 key (Exit).
Press the 0 key (Exit).
-------------------------------------------------------------------------------------
EATON NETWORK MANAGEMENT CARD
-------------------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
Network configuration :
MAC address : 00:20:85:FD:1C:07
Mode : DHCP
IP address : xxx.xxx.xxx.18
Subnet mask : 255.255.248.0
Gateway : xxx.xxx.xxx.1
1 : Read Network settings
2 : Modify Network settings
3 : Set ethernet speed
0 : Exit
For each of the following questions, you can press "Return" to select the value
shown in braces, or you can enter a new value.
Should this target obtain IP settings from the network?[N] N
Static IP address [192.168.1.2]?192.168.1.82
Subnet mask IP address [255.255.0.0]? 255.255.255.0
Gateway address IP address [0.0.0.0]? 192.168.1.1
Done
Bits per second Data bits Stop bits Parity Flow control
9600 8 1 None None
Your network is not equipped with a BOOTP/DHCP server (manual configuration is required)
To set the network configuration, use terminal emulation (see above)
From the main configuration menu:
• Press the 2 key (Network configuration).
• Press the 2 key (Modify Network settings).
• Follow the instructions and enter the IP parameters:
Wait until "Done" is displayed, indicating that the IP parameters have been saved.
• Press the 0 key (Exit).
• Press the 1 key (Reset).
• Press the 2 key (Restart).
The card restarts with the new IP settings (after approx. one minute).
5. ACCESS TO SUPERVISION
To check whether the Network Card-MS is operational after installation and IP settings, please proceed as follows.
• Run a browser
• Enter in the address bar: http://IP address/ (e.g. http://192.168.1.82)
• The home page is displayed
• Set the time by clicking the Settings >> Time command.
• Continue configuration via the sections in the Settings menu.
Network Card-MS
Quick Start
www.eaton.com
www.eaton.com
614-20616-00
1. INTRODUCTION
The Network Card-MS card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface . It connects to Ethernet
network. In addition, an Environmental Monitoring Probe can be attached to obtain humidity, temperature, smoke alarm, and security information.
With the card, the ATS has its own IP address and uses the local computer capabilities to:
• Supply web pages (http or https (SSL)) with information on status conditions and measurements/settings/alarms,
• Integrate an SNMP-based NMS such as hp OpenView, IBM Tivoli Netview and Computer Associates Unicenter.
• Communicate with IPM (Intelligent Power Manager).
• Send e-mail
• Monitor the Environment Sensor (EMP).
This manual provides all the information required to configure the Network Card-MS.
For more information on the supervision, control and configuration functions offered by the Network Management Card, see the user manual available
at http://powerquality.eaton.com.
2. OVERVIEW
ETHERNET PORT
LED Color
Status Description
ACT
Green
OFF
Card not connected to network
ON
Card connected to network, but no activity
Flashing
Port is sending/receiving
100M
Orange
OFF
Port operating at 10 Mbits/s
ON
Port operating at 100 Mbits/s
Service port (Settings/Sensor)
LED Color Status Description
Data
Green
OFF Card starting
ON Communicating with ATS
Flashing Normal operation, communication with ATS is
operational
RS232
Orange
OFF Configuration menu activated
ON
Normal operation, configuration menu not activated
Flashing
Communication with Environment Sensor (option)
6. SENSOR CONNECTION (option)
The Environment sensor is a Network Card-MS option.
For more information, see the user manual of the Network Card-MS.
The sensor remotely monitors the ATS environment by periodically measuring the
temperature and humidity, and checking the states of two external contacts. It can also
send alarms (e-mail, SNMP trap) tripped by pre-set thresholds. Connection is made via
the Service port (Settings/Sensor) on the Network Card-MS. The sensor is detected
automatically. Configuration and supervision use a menu that may be accessed directly
from the home page.
ETHERNET 10/100BT port
Service port (Settings/Sensor)
Orange LED: RS232 activity
Green LED: communication
with the UPS
MAC address
Orange LED: 10/100M
Green LED: connection +
activity
  • Page 1 1
  • Page 2 2

Eaton Network Card-MS Quick Start

Category
Gateways/controllers
Type
Quick Start

Eaton Network Card-MS is a powerful networking device that seamlessly integrates with your ATS to provide remote monitoring, control, and configuration capabilities over an Ethernet network. With its SNMP and HTTP abilities, you can effortlessly manage your ATS from anywhere using a web browser or integrate it into your existing SNMP-based NMS, such as HP OpenView, IBM Tivoli Netview, or Computer Associates Unicenter. Additionally, it facilitates communication with IPM (Intelligent Power Manager) and allows for email notifications and comprehensive environment sensor monitoring.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI