Condair CDC-NA is a duct humidity sensor designed to measure and control humidity levels in various applications. It can be configured for humidity control or as a high limit safety device. The sensor features a capacitive measuring element with high accuracy and stability. It has analog outputs for humidity and temperature, and can be easily integrated into building management systems. The Condair CDC-NA is suitable for use in a wide range of applications, including data centers, museums, and industrial facilities.

Condair CDC-NA is a duct humidity sensor designed to measure and control humidity levels in various applications. It can be configured for humidity control or as a high limit safety device. The sensor features a capacitive measuring element with high accuracy and stability. It has analog outputs for humidity and temperature, and can be easily integrated into building management systems. The Condair CDC-NA is suitable for use in a wide range of applications, including data centers, museums, and industrial facilities.

CDC-NA - 2-10V Duct Humidity Sensor
2605769-A EN 2304
Page 1
2-10V Duct Humidity Sensor Installation Instructions
This document covers the operation and installation instructions for the following Condair duct humidity sensor:
Kit No. Component No. Description
2597926 1509857 2-10V Duct Humidity Sensor
The humidistat can be congured for either humidity control or as a high limit safety device.
1 – Mounting and Installation
Location:
The Condair CDC-NA is installed directly on the duct.
Mounting in the extract air duct (recommended):
Mount the CDC-NA in the extract air duct close to the air outlet of the room but downstream from an extract
air fan if one is present.
Mounting in the supply air duct:
Mount the CDC-NA in the supply air duct at least 3 meters downstream from the nearest fan and coil and with
a minimum distance of 5x the humidication distance to the steam distribution.
Installation:
Refer to installation overview in section 2.
1. At the place of location drill a hole with a diameter of 16 mm (5/8”) as well as 4 holes for the self-tapping
screws into the duct.
2. Loosen the screw on the housing cover and open cover.
3. Lead connecting cable through the cable gland and connect wires to the terminate according to the wiring
diagram.
4. Stick gasket on the sensor side centrally on the housing (self-adhesive).
5. Insert the probe into the hole in the duct, then x the housing to the duct using the 4 self-tapping screws provided.
6. Close the cover and x it with the screw (do not tighten the screw too much).
Note: We recommend using 18-gauge wire, and maximum <100 ft distance from the unit.
Page 2
3 – Installation overview
1: 0V
2: 24V
3: RH
GND
AC 24 V 50-60 Hz, 24 VDC ±10%
0(2)...10VDC, 0(4)...20mA
2
1
i
1
2
AB
C
D
mm (inch)
75 (2.9)
54 (2.1)
16 (0.6)
70-000251/20201202
©Condair Group AG, Switzerland
4
3
Sensor Connect App
Get the Condair
For Wiring Schematic:
CDC-NA
2597926/1509857
91 (3.6)
68 (2.7)
47 (1.9)
0.55x6.2)
(
14x157
1
JP3
LED
OPA-S
OPC-S
2 3
JP3
3
2
1
U... 0...10 V
I... 0...20 mA
U... 2...10 V
I... 4...20 mA
3
2
1
6 (0.02)
OPC-S OPA-S
Page 3
8 – Product Specication
Power Supply
Operating Voltage
Power Consumption
Terminal Connections
24 V AC 50/60 Hz ± 10 %
Max. 2 VA
For wires 0.34…2.5 mm2 (AWG 24…12)
Sensor Probe
(Humidity Sensor)
Measuring element
Range
Accuracy
Hysteresis
Repeatability
Stability
Capacitive measuring element
0…100 % RH
± 3.0 % at 25 °C
± 1%
± 0.1%
< 0.5% / Year
Signal Outputs
Analog Outputs
Analog Signal
Resolution
Maximum Load
0-10V / 2-10V
10 Bit
20 mA, 500Ω
Environment
Operation
Temperature
Humidity
IEC 721-3-3
-40…70°C (-40…158°F)
˂95 %rH not condensing
General Housing Materials
Filter material
PC and ABS
PTFE coated 1µm pores
Page 4
9 – Wiring Diagrams
Wiring diagram CDC-NA for RS, EL, GS, US and SE
24VAC
Safety Loop
GND
CH1
CH2
GND
1211
10
9
8
76
54321
EL / RS / GS / US / SE
0V/GND
24V AC/DC
2-10 VDC
CDC-NA
2-10V Duct Humidity Sensor
1509857
1 2 3
Wiring diagram CDC-NA for DL and ME
SC2
SC1
X1
X16
24/10 V
TMP
GND
HUM
24V E
Enable
Driver board
ME / DL
CDC-NA
2-10V Duct Humidity Sensor
1509857
0V/GND
24V AC/DC
2-10 VDC
1 2 3
ME / DL
JP5: 10V
JP4: 24V
Wiring diagram CDC-NA with CHD-NA and APS for RS, EL, GS, US and SE
24VAC
Safety Loop
GND
CH1
CH2
GND
1211
10
9
8
76
54321
EL / RS / GS / US / SE
Com
NO
NC
APS
Air Proofing Switch
2598427
0V/GND
24V AC/DC
2-10 VDC
CDC-NA
2-10V Duct Humidity Sensor
1509857
1 2 3
CHD-NA
On/Off Duct Humidistat / High Limit
2548732
0V / GND
24V AC/DC
DO1
DO1
DO2
DO2
RT
RT
1 2 3 4 5 6 7 8
Wiring diagram CDC-NA with CHD-NA for DL and ME
SC2
SC1
X1
X16
24/10 V
TMP
GND
HUM
24V E
Enable
Driver board
ME / DL
CDC-NA
2-10V Duct Humidity Sensor
1509857
CHD-NA
On/Off Duct Humidistat / High Limit
2548732
0V / GND
24V AC/DC
DO1
DO1
DO2
DO2
RT
RT
1 2 3 4 5 6 7 8
0V/GND
24V AC/DC
2-10 VDC
1 2 3
ME / DL
JP5: 10V
JP4: 24V
Page 5
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

Condair CDC-NA User manual

Type
User manual

Condair CDC-NA is a duct humidity sensor designed to measure and control humidity levels in various applications. It can be configured for humidity control or as a high limit safety device. The sensor features a capacitive measuring element with high accuracy and stability. It has analog outputs for humidity and temperature, and can be easily integrated into building management systems. The Condair CDC-NA is suitable for use in a wide range of applications, including data centers, museums, and industrial facilities.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI