  • Hello! I've analyzed the provided installation instructions for the Siemens Electrical Finish Plate 192-731 designed for pneumatic/electronic sensors. This document describes different mounting methods and the steps needed for installation, including connecting pneumatic tubing. I'm here to answer any questions you might have about its installation and usage.
  • What is the minimum depth of electrical box for pneumatic switches?
    What three methods could be used to install the finish plates?
    Are screws or anchors included with finish plate?
Installation Instructions
Document No. 129-103
March 16, 2022
Powers® Controls Electrical Finish Plate
Installation Template for
Pneumatic/Electronic Sensors
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and
models as design improvements are introduced. Powers is a trademark of Siemens Industry, Inc. © 2012-2022 Siemens Industry, Inc.
Siemens Industry, Inc.
Smart Infrastructure
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
+1 847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them
to SBT_technical.editor.us.sbt@siemens.com
Document No. 129-103
Printed in the USA
Page 1 of 2
Product Numbers Table 1.
Description
Finish
Electrical Rough-In Box
Size
Reference*
1 Sensor
Stainless Steel
2 Gang 2-1/2 inch deep
Appleton M2-250
* Or other manufacturer's equivalent
Installation
1. Use this wall cutout template (see Page 2) if an
electrical wall-box is not required. Refer to and
follow local or National Electrical Code
requirements.
2. Finish plates may be installed using one of the
following three methods:
a. Electrical rough-in box, see Table 1. No
other hardware is required (screws are
included with finish plate).
b. Plastic anchors for use with No. 6 × 1-1/4
inch flat-head screws (anchors and screws
not included with finish plate).
c. Finished drywall mounting clips and screws
(mounting clips and screws not included).
Order Product Number 182-685 (package of
20 clips each).
Item Number: 129-103, Rev. EA
3. After wall cutout is made and tubing/wiring is
pulled into position, follow these procedures:
a. Remove sensor cover from sensor chassis
(not applicable to pneumatic switches or
pneumatic thermostats).
b. Mount sensor wallplate to finish wallplate.
c. Mount pneumatic switch to finish wallplate.
d. Wire electrical switch, mount to wallbox or to
wall when required.
e. Attach pneumatic tubing to sensor chassis
or wallplate plug-in adaptors. (Do not forget
the restrictor on applicable sensors).
f. Attach finish plate to wallbox or to wall
(plastic anchors or mounting clips), being
careful not to bend or kink the pneumatic
tubing.
4. When using an electrical wallbox for pneumatic
switches, provide a box with a minimum depth of
3-1/2 inch (89 mm) for clearance of fittings,
tubing, and the switch body.
The installation is now complete.
/