page 11 of 12
P/N 0247-00 Rev G 10/18
*Applicable to millivolt systems only.
MAINTENANCE
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.
The Flue Sentinel® has been designed to provide years of maintenance free service. However, for continued
safe operation, the Flue Sentinel®, chimney and fi replace appliance should be examined once a year by a
qualifi ed service agency. It is also recommended that the homeowner examine these components at least every
six (6) months, with particular attention given to deterioration from corrosion or other source.
TROUBLESHOOTING CHART
PROBLEM POSSIBLE CAUSES ACTION
Damper won’t open
Signal voltage at Orange wire less than 100
mV*
Check connections, adjust pilot,
and/or replace thermopile
Obstruction in damper Remove obstruction
Insuffi cient power at damper
Check damper battery & replace if less than
2.8V. Check battery voltage at FSM Cable
plug, pin positions 1(+) and 4(-) (Remote
Battery Only). Check voltage on battery har-
ness wires: red (+) and black (-), and battery
connector.
Defective damper controller Replace controller
No Power
Battery test: With a good AA battery attach
to the Orange (Red on high temp harness)
and Black wire from the harness of the FSM.
If the damper opens check to see if there is
1.5 volts DC between the Yellow (Green on
high temp harness) and the black with the
battery is still attached to the Orange (Red on
high temp harness) and Black wires. If there
is 1.5 volts DC the FSM is operating properly
and the thermopile on the gas valve of the
log set would need to be checked. If there
in no voltage check to make sure the FSM
opened. If the damper open, but no power
replace controller. If damper did not open
check battery to FSM to see if there is 3.6
volts DC on the battery. If battery is below
2.8 volts DC replace battery. If battery has
good voltage replace controller.
Damper opens but
appliance main
burner(s) does not fi re
Signal voltage at Yellow wire less than 100 mV*
Check connections, adjust pilot, and/or
replace thermopile
Signal voltage at Yellow wire greater than 100
mV*
Make sure valve knob is On, if so replace
valve operator
Damper rotates con-
tinuously
Defective damper controller Replace controller
Reversed Battery Polarity
Check red wire terminal (+), black wire
terminal (-) for proper connections.
Damper won’t close,
main burner off
Signal voltage at Orange wire Check on/off switch
Thermopile polarity reversed* Re-connect thermopile leads per Figure 2
Obstruction in damper Remove obstruction
No power or insuffi cient power at damper
Check damper battery & replace if less than
2.8V. Check at battery conncetor & cable
plug.
Defective damper controller Replace controller