Danfoss Termix Compact 28 VX-FI Operating instructions

Type
Operating instructions
OperatingGuide
TermixCompact28VX-FI/HWP/HWS
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1MountingtheCompactstation..................................5
4.2Start-up..............................................................12
4.3Electricalconnections.............................................13
5.0Design.............................................................14
5.1Design...............................................................14
5.2Schematicdiagram................................................15
6.0Controls..........................................................17
6.1Heatingcircuit......................................................17
6.2Other.................................................................20
6.3Maintenance........................................................22
7.0Troubleshooting..............................................23
7.1Troubleshootingingeneral......................................23
7.2TroubleshootingHE...............................................23
7.3Disposal.............................................................24
8.0Declaration......................................................27
8.1Declarationofconformity........................................27
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
1
OperatingGuideTermixCompact28VX-FI/HWP/HWS
2
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
2.0Functionaldescription
Districtheatingsubstationforindirectheating.
Spaceheating
TheTermixCompact28VX-FIisaheatexchangerunitforthe
productionofheatinginlargebuildingssuchassportscentres,
schools,blocksofatsetc.Itcanbeusedforconnectiontoindirect
districtheatinginplaceswherethedistrictheatingplantrequiresa
hydraulicbreakontheplantside.Itisalsosuitableforconversion
todistrictheatingwhenthesecondaryheatingsystemissuitable
tobeingconnectedtodirectdistrictheatingorwhenaparticularly
effectivesecurityagainstleakageintheheatingsystemisrequired.
Itispossibletoconnectahot-watertank.
Efcientheatexchanger
Thesubstationisttedwithanefcientplateheatexchanger,
whichensuresthemostfavourableheatextractionandachieves
optimumcomfortandoperatingeconomy.
Severalvariants
TermixCompact28VX-FIisbuiltwithaheatexchangerforspace
heating,owcontroller,pump,electronicregulationoftheheating
circuitaswellasadirectoutletforahotwatertank.Theelectronic
controllerisfactorypre-set.Electricalcomponentsarepre-wired,
andtheunitisequippedwithaplugfor230Va.c.
Itisrecommendedthatdynamicbalancingvalvesareinstalledin
thebuildingsrisersintheheatsupplyandontheheatingsystems
returnlineimmediatelybeforetheunit.
TermixCompact28VX-FIisproducedinstandardconstructions:
VXwithheatexchangerforindirectheating.
VXwithheatexchangerforindirectheatingandintegrated
tankregulation.
Flexiblesolution
Pipeconnectioncanbemadefromeitherthetoporbottom,which
makesthissolutionhighlyexible.Atthesametime,bothspace
andtimearesavedwheninstalling.
Minimalheatloss
Completeinsulationoftheunitensuresminimalheatloss.
Reliableandeasytoinstall
TermixCompact28VX-FIisoperationallyreliable.Aqualityproduct
manufacturedinDenmark,whichiseasytoinstallandquickly
commissioned.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
3
OperatingGuideTermixCompact28VX-FI/HWP/HWS
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
110°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.0Mounting
4.1MountingtheCompactstation
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Tankowline(TFL)
6.Tankreturnline(TRL)
Connectionsizes:
DH+HE:
G1”(int.thread)
TFL+TRL:
G¾”(int.thread)
Dimensions(mm):
Withinsulation:
H890xW905xD400
Weight(approx.):60kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
5
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Removethefront.
Removeotherblocks.
Attachthemountingrailtothewall.
Liftthestation.
6
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Mountthestationonthemountingrail.
Attachthestationtothewallintheholesonthemountingplate.
Installthesafetyvalve.
Installballvalves.
MountblockA(CifitistheMagnapump)ontheleft-handsideof
thepump.AttachblockEtoblockA/C,andattachittothepipe
abovethepumpbyclickingitinplace.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
7
OperatingGuideTermixCompact28VX-FI/HWP/HWS
MountblockB(DifitistheMagnapump)ontheright-handsideof
thepump.
MountblockF(GforVM2valve).Theblockishingedandcanbe
drawnaroundthevalve.AttachtheblocktoblockB/DandE.
MountblockJandHaroundthevalveforthetankcontrol.
Mountthefrontcover.
8
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.1.1InstallingtheCompactstation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
9
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.1.2Pipeconnectionsup
Removethetopblock.
Removethepipeplugsatthetopofthestation.
RemoveU-clamps.
Removepipes.Anglesandteesareturnedsothatpipescanbe
installedfromabove.
Installthepipes.Districtheatingsupplypipestobeinterchanged.
10
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
FitU-clamps.
Fitthepipeplugsatthebottomofthestation.
Fitthetopblock.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
11
OperatingGuideTermixCompact28VX-FI/HWP/HWS
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstll
Whencarryingoutrstll,theheatexchangermustbeslowlylled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tollthe
system,theballvalvemustrstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
llcancommence.
4:Pre-pressure
Whenllingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Height(m)Pressure(bar)
050,5
5101,0
1015
1,5
15202,0
12
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
13
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
10
Circulatorpump
26
Pressuregauge,HE
F
Electroniccontroller
14
Sensorpocket,energymeter
27AActuator,HE
4
Safetyvalve,HE
20
Filling/drainvalve
48
Airvent,manual
9
Strainer
25
Pressuregaugewithballvalve
14
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.2Schematicdiagram
5.2.1SchematicdiagramTermixCompact28VX-FI
DH
Supply
HE
Supply
DH
Return
HE
Return
TRL
TFL
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
E
Hotwatertankwithcoil
14
Sensorpocket,energymeter
26
Pressuregauge
F
Electroniccontroller
16
Outdoorsensor
27
Actuator
L
Borderofdelivery
18
Thermometer
29
2-waymotorizedvalve
1
Ballvalve
19
Surfacesensor
30
Flowcontrollerwithintegratedcontrolvalve
2
Singlecheckvalve
20
Filling/drainvalve
31
Differentialpressurecontroller
4
Safetyvalve
23
Ballvalve
44
Immersionsensor
9
Strainer
24
Deliveredloosewithunit
48
Airvent,manual
10
Circulatorpump
5.2.2SchematicdiagramTermixCompact28VX-FIHWP
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
HWC
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
15
OperatingGuideTermixCompact28VX-FI/HWP/HWS
5.2.3SchematicdiagramTermixCompact28VX-FIHWS
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
HWC
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
E
Hotwatertankwithcoil
13
Chargingpump
26
Pressuregauge
F
Electroniccontroller
14
Sensorpocket,energymeter
27
Actuator
L
Borderofdelivery
16
Outdoorsensor
29
2-waymotorizedvalve
1
Ballvalve
18
Thermometer
30
Flowcontrollerwithintegratedcontrolvalve
2
Singlecheckvalve
19
Surfacesensor
44
Immersionsensor
4
Safetyvalve
20
Filling/drainvalve
48
Airvent,manual
9
Strainer
24
Deliveredloosewithunit
69
On/offvalve
10
Circulatorpump
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
TFL:
Tankowline
TRL:
Tankreturnline
DHW:
Domestichotwater
HWC:
Hotwatercirculation
DCW:
Domesticcoldwater
5.2.4Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
110°C
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
16
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
17
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.1.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
6.1.5Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
18
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.1.6Circulatorpump
TheUPML,UPMXLcirculatorpumpsaredesignedforcirculating
liquidsinheatingsystemswithvariableows,internallycontrolled
withthreeproportionalpressurecurvesandthreeconstant
pressure/powercurvestobeselectedviauserinterface.
EuP2015Ready.
TheMAGNA3circulatorpumpsaredesignedforcirculatingliquids
inheatingsystemswithvariableowswhereyouwanttooptimise
thesettingofthepumpdutypoint,thusreducingenergycosts.
EuP2015Ready.
6.1.7GrundfosUPML/UPMXLinstructions
PP=Proportionalpressure(fastash)
CP=Constantpressure(slowash)
DanfossDistrictEnergy
VI.LZ.J1.02/LUK42365
DEN-GT
19
OperatingGuideTermixCompact28VX-FI/HWP/HWS
6.1.8HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
6.2Other
6.2.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
6.2.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
20
DEN-GT
VI.LZ.J1.02/LUK42365
DanfossDistrictEnergy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Danfoss Termix Compact 28 VX-FI Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI