Honeywell VE4000, VE5000 SERIES Operating instructions

Type
Operating instructions
Honeywell
VE4000 & VE5000 SERIES
CLASS "A" GAS VALVES
INSTRUCTION SHEET
ISTR0018 1711RA-NE
1
APPLICATION
These series class A gas valves are used for control and
regulation of gaseous fluids in gas power burners, atmospheric
gas boilers, melting furnaces, incinerators and other gas
consuming appliances
GENERAL
DESCRIPTION
VE4000 Series Gas Valve
The VE series gas valves offer a series of functionalities:
Gas valves, Normally Closed.
CPI switch optional
Gas valves for use with Honeywell V4055, V4062 and
V9055 fluid power actuators.
Relief valves Normally Open.
Adjustable opening characteristics optional
FEATURES
The VExxxxX1xxx series gas valves have a wrench boss
as well on inlet side as on outlet side for pipe fitting
incorporated in the valve housing.
The VExxxxXXX3xxx and VE5xxxXXX3xxx series gas
valves are equipped at both sides with mounting holes to
adapt a pilot solenoid valve combination, to allow either
internal or external pilot gas. Furthermore these valves
are equipped with two M6 mounting holes to adapt an
A4020A electronic leak test The VExxxxBXX series gas
valves have an adjustable flow rate regulator on top of the
coil.
For the VE series gas valves a series of field replaceable
connection boxes (including circuits) are available
The VExxxxCXX series gas valves have adjustments for
step pressure flow rate and opening speed in hydraulic
damper unit on top of the coil.
The VExxxxSXX series gas valves normally open relief
valves have no option for mounting a CPI switch
The VE5xxxX3xxx series gas valves can be equipped with
a wide range of Honeywell fluid power actuators. These
fluid power actuators are field replaceable.
Subject to change without notice. All rights reserved.
Honeywell
ISTR0018 1711RA-NE
2
MODEL CHART
Options 1000/2000 series internal thread 3000/4000 series flange connection
DN10 / 3/8” VExx10
DN15 / 1/2” VExx15
DN20 / 3/4” VExx20
DN25 / 1” VExx25
DN32 / 1 1/4” VExx32
DN40 / 1 1/2” VExx40
DN50 / 2” VExx50
DN65 / 2 1/2” VExx65 VExx65
DN80 / 3” VExx80 VExx80
DN100 / 4” VEx100
Non adjustable ON/OFF (VExxxxAXX) Standard Standard
Flow regulator (VExxxxBXX) Optional Optional 2)
Adjustable opening and flow regulator
(VExxxxCXX) Optional 1) Not available
Motorized opening: ON/OFF
(VE5xxxAxxxx) Not available VE5065A3xxx
VE5085A3xxx
VE5100A3xxx
Motorized opening: characterized
(VE5xxxCxxxx) Not available VE5065C3xxx
VE5085C3xxx
VE5100C3xxx
Safety relief valve, ON/OFF, Normally
Open, with or without position
indication switch (VExxxxSxxxx)
Optional for:
VE..20
VE..25
Not available
1) Except VExx65/VExx80
2) Except VE4100
TECHNICAL
SPECIFICATIONS
VE series solenoid gas valves
VExx10 (DN 10)
VExx15 (DN 15)
VExx20 (DN 20)
VExx25 (DN 25)
VExx32 (DN 32)
VExx40 (DN 40)
VExx50 (DN 50)
VExx65 (DN 65)
VExx80 (DN 80)
VEx100 (DN 100)
VE series suitable for fluid power actuators
VE5065 (DN 65)
VE5080 (DN 80)
VE5100 (DN 100)
Pipe sizes 1000/2000 series
Inlet and outlet G3/8" up to G21/2" internal parallel pipe thread according ISO 7-1
Pipe sizes 3000/4000 series
Flanged connection DN 65, DN 80 and DN100 according to DN 16 UNI 2223.
Torsion and bending stress
Pipe connections meet Group 2 according EN 161 requirements.
Honeywell
ISTR0018 1711RA-NE
3
Ambient temperature
-15 °C ... 60 °C
Supply voltage
24 V, 50/60 Hz 1)*
100-120 V, 50/60 Hz
200-240 V, 50/60 Hz
The applicable voltage is led to the solenoid coil via a rectified circuit.
1): only for DN10 up to DN50
Operational voltage range
The gas valve will function between 85% and 110% of the rated voltage
Electrical connection VE4xxx/VE6xxx/VE8xxx
Option 1: Wiring on terminal block on circuit cables entering box via M20 Cable Gland
Option 2: Connection by means of DIN plug on DIN faced connection located on front cover according to
ISO4400 / DIN EN 175301-803
Electrical connection VE5xxx series
See product literature fluid power actuators
Enclosure VE4xxx/VE6xxx/ VE8xxx
IP 65 when using supplied M20 gland and cable
diameter 7 – 13 mm for M20 version or using suitable DIN plug with gasket.
Capacity
See page 7 and 8
Maximum operating pressure
Inlet Maximum operating pressure
(mbar)
VE4010
VE6010
VE8010
200 or 360
360
200
VE4015
VE6015
VE8015
200 or 360
360
200
VE4020
VE6020
VE8020
200 or 360
360
200
VE4025
VE6025
VE8025
200 or 360
360
200
VE4032
VE6032
VE8032
200 or 360
360
200
VE4040
VE6040
VE8040
200 or 360
360
200
VE4050
VE6050
VE8050
200 or 360
360
200
VE4065/VE6065
VE8065
VE5065
200 or 360
200
VE4080/VE6080
VE8080
VE5080
200 or 360
200
500
VE4100
VE6100
VE5100
200 or 360
360
360
Honeywell
ISTR0018 1711RA-NE
4
POWER CONSUMPTION (VA)
Power consumption (VA) 200 mbar versions
V
ExxxxXXL
versions
Shut off valves
Model
number
24 V 50/60
Hz
Nominal
24 V 50/60 Hz
110% Nominal 200-240 V
50/60 Hz Nominal
200-240 V
50/60 Hz
110% Nominal
VExx10 15 16.5 11-16 12-17,5
VExx15 15 16.5 11-16 12-17,5
VExx20 21 23 17-24 19-26,5
VExx25 21 23 17-24 19-26,5
VExx32 50 55 31-44 34-48,5
VExx40 50 55 31-44 34-48,5
VExx50 49 54 35-51 38,5-53,5
VExx65 88 97 68-98 75-108
VExx80 88 97 68-98 75-108
VEx100 Start up - - 112-162 123-178
Cont. - - 28-40 31-44
Power consumption (VA) 360 mbar versions VExxxxXXH
versions
Shut off valves
Model
number
100-120 V
50/60 Hz
Nominal
100-120 V
50/60 Hz
110% Nominal
200-240 V
50/60 Hz Nominal 200-240 V
50/60 Hz
110% Nominal
VExx10 13-19 14-21 11-16 12-17,5
VExx15 13-19 14-21 11-16 12-17,5
VExx20 17-24 19-26,5 17-24 19-26,5
VExx25 17-24 19-26,5 17-24 19-26,5
VExx32 41-59 45-65 35-51 38,5-53,5
VExx40 41-59 45-65 35-51 38,5-53,5
VExx50 53-76 58-84 48-70 53-77
VExx65 Start up 205-295 225-325 191-274 210-301
Cont. 51-74 56-81 48-69 53-76
VExx80 Start up 205-295 225-325 191-274 210-301
Cont. 51-74 56-81 48-69 53-76
VEx100 Start up 180-259 198-285 456-657 501-723
Cont. 45-65 50-72 115-164 127-180
Honeywell
ISTR0018 1711RA-NE
5
Power consumption (VA) 360 mbar versions
V
ExxxxSGH
versions
Safety relief valves
Model
number
24 V 50/60
Hz
Nominal
24 V 50/60 Hz
110% Nominal
100-120 V
50/60 Hz
Nominal
100-120 V 50/60
Hz 110% Nominal 200-240 V
50/60 Hz
Nominal
200-240 V
50/60 Hz
110%
Nominal
VExx20S 16 19 14 17 16 19
PERFORMANCE CHARACTERISTICS
Opening time (except VE5xxx series)
VExxxxAXX &,BXXX versions: less than 1 second
VExxxxCXX version: adjustable from 1 up to 30 seconds at rated capacity
Closing time
VExxxxAXX, BXX, CXX and S series (except VE5xxx series)
Less than 1 second
Maximum working cycles/minute
S versions: 20
DN10–DN 25 AXX & BXX versions: 20
DN10-DN25 C versions: 1
DN32-DN100: 1
VE5... series: 1 cycle per 2 minutes
Duty cycle
Coil suitable for permanent energization
Honeywell
ISTR0018 1711RA-NE
6
INSTALLATION
WARNING
Take care that installer is a trained experienced
service man.
Turn off gas supply before starting installation.
Disconnect power supply to prevent electrical shock
and/or equipment damage.
Mounting position
The gas valve can be mounted plus or minus 90 degrees from
the vertical.
Mounting location
The distance between the gas valve and the wall/ground, must
be at least 30 cm.
WARNING
The outlet of a pressure relief valve (VE4000S series)
must always be connected to open atmosphere.
Main gas connection threaded valves
Take care that dirt cannot enter the gas valve during
handling.
Ensure the gas flows in the same direction as the arrow
on the housing of the gas valve.
Use a sound taper fitting with thread according to ISO 7-1
(BS 21, DIN2999) or a piece of new, properly reamed
pipe, free from swarf
Do not thread or tighten the pipe or pipe fitting too far.
Otherwise valve distortion and malfunction could result.
Apply a moderate amount of good quality thread
compound to the pipe or fitting only, leaving the two end
threads bare. PTFE tape may be used as an alternative.
In order to tighten the pipe in the valve, do not use the
actuator as a lever but use a suitable wrench operating on
the wrench bosses.
Main gas connection flanged valves
Take care that dirt cannot enter the gas valve during
handling.
Ensure the gas flows in the same direction as the arrow
on the housing of the gas valve.
Ensure that inlet and outlet flanges are in line and
separated from each other enough to allow the valve to be
mounted between them without damaging the gasket.
Place gasket. If necessary grease it slightly to keep it in
place.
Mount gas valve between flanges using the bolts for each
flange.
WARNING
Tightness test after installation
Paint all pipe connections and gaskets with a strong
soap and water solution..
Start the appliance and check for bubbles. If a leak is
found in a pipe connection, remake the joint. A gasket
leak can usually be stopped by tightening the
mounting screws. Otherwise, replace the gas valve.
Electrical connection
CAUTION
Switch off power supply before making electrical
connections.
Take care that wiring is in accordance with local
regulations.
Use lead wire which can withstand 105 °C ambient.
The electric on/off operator is provided with a terminal block
for electrical connections.
Wiring
Follow the instructions supplied by the appliance
manufacturer.
Honeywell
7 ISTR0018 1711RA-NE
Instructions Electrical connections
Connection instructions with PG gland
On each side of the connection box there are break out
area’s. See Fig 1. After removing the central part of one of
these break outs, the PG gland (supplied with the valve) can
be fitted.
Fig 1
After removing the nut from the gland, the gland can be
placed in the break out. The nut needs to turned onto the
gland inside the box and tightened as shown in Fig 2.
Specified torque for the nut: 4 Nm. Mounted PG gland
shown in Fig 3. Specified torque PG gland: 3 Nm.
Fig 2
Fig 3
After connecting wires ( L, N & PE) to dedicated connectors
on connector block, the connection needs to closed by
mounting the front cover. Before placing the cover, please
check the correct position of seal as shown in Fig 4. The
cover can only be mounted in one orientation. This is shown
in Fig 5.
Specified torque for cover screw: 0.5 Nm.
Specified cable diameter for gland: 7 – 13 mm.
Fig 4
Fig 5
Connection instructions DIN plug
Specified torque for DIN connector screw: 0.2 Nm.
Fig 6
Honeywell
ISTR0018 1711RA-NE
8
ADJUSTMENT AND FINAL CHECKOUT
WARNING
Adjustments must be made by qualified persons only
CAUTION
To ensure a safe closing of the valves, it is essential
that voltage over the terminals of operators is
reduced to 0 Volt.
IMPORTANT
To ensure a satisfactory setting of the valve the
pressure drop over the valve should be at least 10%
of the supply pressure or 2.5 mbar which ever is the
greatest.
VExxxxB SERIES
(see fig 7.)
Flow rate adjustment
Remove the cap screw from top of the coil.
Place a socket head wrench into the adjustment nut.
Turn wrench counter--clockwise to increase or clockwise
to decrease flow rate.
Replace cap screw.
Flow adjustment fig 7
VExxxxC SERIES
(see fig. 8, 9 and 10)
The following characteristics can be adjusted:
flow rate
step pressure
opening speed
Step pressure adjustment
Remove the cap from top of the coil by loosening both
screws.
Place a screw driver in the slot of adjustment screw which
is situated in center of the valve.
Turn screw driver counter--clockwise to increase or
clockwise to decrease step pressure.
Replace cap on top of the coil.
Step pressure adjustment. Fig 8
Opening speed adjustment
Remove the cap from top of the coil by loosening both
screws.
Place screw driver in the slot of adjustment screw which is
of center line.
Turn screw driver counter--clockwise to increase the
opening speed and therefore the time till full opening will
decrease.
Turn screw driver clockwise to decrease the opening
speed and therefore the time till full opening will increase.
Replace cap on top of the coil.
Opening speed adjustment. Fig 9
)
Flow rate adjustment
Remove the cap screw from top of the coil by loosening
both screws
Place a wrench onto the adjustment nut.
Turn wrench counter--clockwise to increase or clockwise
to decrease flow rate.
Replace cap screw.
Flow rate adjustment. Fig 10
Final checkout of the installation
Set appliance in operation after any adjustment and observe
several complete cycles to ensure that all burner components
function correctly.
Honeywell
9 ISTR0018 1711RA-NE
STANDARDS AND APPROVALS
Honeywell
ISTR0018 1711RA-NE
10
REPLACEMENT PARTS AND ACCESSORIES
WARNING
Take care that only qualified persons carry out the installation of parts, accessories, and add on components.
Follow the installation instructions included in the package.
Check that the selected part, accessory or add on component is the correct one for the application in question.
Specification of data is given in the instruction leaflet in the package .Replace the old gaskets with the new ones
supplied in the package and check for leakage when the supply is switched on again. After installation and/or
replacement has been completed, a gas leak test must be carried out. Also check the gas valve for satisfactory operation
after fitting accessories.
SPARE CONNECTION BOXES
Valve type Voltage Connect. Ordering
number
VExx10/VExx15 24 M20 KTBBE00-115
100-120 M20 KTBBE00-115
200-240 M20 KTBBE00-115
VExx10/VExx15 24 DIN KTBBE00-215
100-120 DIN KTBBE00-215
200-240 DIN KTBBE00-215
VExx20/VExx25 24 M20 KTBBE00-120
100-120 M20 KTBBE00-120
200-240 M20 KTBBE00-120
VExx20/VExx25 24 DIN KTBBE00-220
100-120 DIN KTBBE00-220
200-240 DIN KTBBE00-220
VExx32XXL
/
VExx40XXL
24 M20 KTBBE00-141
100-120 M20 KTBBE00-140
200-240 M20 KTBBE00-140
VExx32XXH
/
VExx40XXH
24 M20 -
100-120 M20 KTBBE00-150
200-240 M20 KTBBE00-150
VExx32XXL
/
VExx40XXL
24 DIN KTBBE00-241
100-120 DIN KTBBE00-240
200-240 DIN KTBBE00-240
VExx32XXH
/
VExx40XXH
24 DIN -
100-120 DIN KTBBE00-250
200-240 DIN KTBBE00-250
Valve type Voltage Connect. Ordering
number
VExx50 24 M20 KTBBE00-150
100-120 M20 KTBBE00-150
200-240 M20 KTBBE00-150
VExx50 24 DIN KTBBE00-250
100-120 DIN KTBBE00-250
200-240 DIN KTBBE00-250
VExx65XXL
/
VExx80XXL
24 M20 KTBBE00-182
100-120 M20 KTBBE00-180
200-240 M20 KTBBE00-180
VExx65XXH
/
VExx80XXH
24 M20 -
100-120 M20 KTBBE00-181
200-240 M20 KTBBE00-181
VExx65XXL
/
VExx80XXL
24 DIN KTBBE00-280
100-120 DIN KTBBE00-280
200-240 DIN KTBBE00-280
VExx65XXH
/
VExx80XXH
24 DIN -
100-120 DIN KTBBE00-281
200-240 DIN KTBBE00-281
VEx100 100-120 M20 KTBBE00-100
200-240 M20 KTBBE00-100
VEx100 100-120 DIN KTBBE00-200
200-240 DIN KTBBE00-200
Honeywell
Europe:
Honeywell Technologies Sàrl
Z.A. La Pièce 16
1180 Rolle
Switzerland
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Honeywell VE4000, VE5000 SERIES Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI