Magnetek IMPULSE G+/VG+ Series 4 Quick start guide

Type
Quick start guide

Magnetek IMPULSE G+/VG+ Series 4 variable frequency drive (VFD) offers precise speed control for various applications, including hoisting machines, cranes, and lifting devices. With Flux Vector control, it ensures accurate torque control and smooth operation, especially for hoist applications without load brakes. Its built-in Auto-Tuning feature simplifies setup by automatically adjusting to your motor's characteristics. The VFD also provides multiple speed reference options and supports various motion control modes, such as traverse and hoist, for added versatility.

Magnetek IMPULSE G+/VG+ Series 4 variable frequency drive (VFD) offers precise speed control for various applications, including hoisting machines, cranes, and lifting devices. With Flux Vector control, it ensures accurate torque control and smooth operation, especially for hoist applications without load brakes. Its built-in Auto-Tuning feature simplifies setup by automatically adjusting to your motor's characteristics. The VFD also provides multiple speed reference options and supports various motion control modes, such as traverse and hoist, for added versatility.

OVERVIEW
The following procedure is a supplement to other documentation
available for the IMPULSE•G+/VG+ Series 4 variable frequency
drive (VFD). This will guide the user in proper installation and setup
of the system.
Before using the VFD-controlled equipment, the operator shall
read the operating manual of the hoisting machine, shall be
trained, and has to know all hazards by operating of cranes, hoists,
or lifting devices.
When installing the system, be sure to follow good wiring practices
and all applicable codes. Ensure that the mounting of components
is secure and that the environment, such as extreme dampness,
poor ventilation, etc., will not cause system degradation.
Read this document thoroughly before attempting installation.
Refer to the technical manual available at:
www.columbusmckinnon.com/magnetek.
Step 1
Connect Motor and Line Power
The following figure shows the electrical connections for the input
power and motor terminals on IMPULSE•G+/VG+ Series 4 VFD.
Make the appropriate connections with power turned off. Follow
good wiring practices and follow all applicable electrical codes.
Ensure the equipment is properly grounded, as shown.
DANGER! DANGEROUS VOLTAGES ARE PRESENT
WHEN VFD IS ON. Improper wiring can cause bodily
harm and damage to the equipment. Before applying
power to the IMPULSE•G+/VG+ Series 4, ensure that all
protective covers are fastened and all wiring connec-
tions are secure. After power has been turned OFF, wait
at least 5 minutes until the charge indicator extin-
guishes completely before touching any wiring, circuit
boards, or components.
WARNING: DO NOT CONNECT ANY OF THE FOLLOWING
TERMINALS TO EARTH GROUND.
WARNING DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
B1 B2
-
+1 +2 +3
Use L1, L2, L3 for
3Ø Input Power
To change
direction of
motor rotation
swap any two
of the three
motor leads
(See Step 2)
Use L1, L2 for
1Ø Input Power
3Ø Induction
motor
Connect
frame to
ground
Input
Protection
(Fuse or Circuit
Breaker)
L1
L2
L3
(R/L1)
(S/L2)
(T/L3)
(U/T1)
(V/T2)
(W/T3)
Connect to
chassis ground
*
DC Bus terminals
location varies by
model.
Step 2
Typical Connection Diagram
This step shows a typical wiring diagram and connection points for the IMPULSE•G+/VG+
Series 4 VFD. Wiring connections should only be made by trained and authorized
personnel when power to the VFD is turned off.
Dynamic Braking**
+1 +2 +3 - B1 B2
R/L1
U/T1
V/T2
W/T3
S/L2
T/L3
3-Phase
Power Supply
50/60Hz
Load Reactor
(Oponal)
Motor
IM
PG
T1
T2
T3
A+
A-
B+
B-
Z+
Z-
IP
IG
FE
a+
a-
b+
b-
z+
z-
PG-X3 (VG+ Series 4 only)
MA
MB
MC
M0
M1
M2
M3
M5
M6
Mul-Funcon Analog Output 1 FM
Mul-Funcon Analog Output 2 AM
Mul-Funcon Pulse Train Output MP
AC
DM+
DM-
E(G)
X1A X1 X2
250VAC/30VDC, 30A
Brake Contactor
Brake Contactor
Alarm Contactor
+
+
-
-
Mul-Funcon
Digital Outputs 2-4
Mul-Funcon
Analog Outputs 1-2
0 to +/-10 VDC, 2mA
4-20 mA (FM only)
Mul-Funcon Pulse Output
0 to 32kHz, 9 VDC @ 3kΩ
+/-5% Accuracy
Safety Electronic Device Monitor
* Requires oponal 120 VAC, 42-48 VAC, or 24 VAC interface board. 24 VDC is also available.
** Set L08-55 to 0 when using an external dynamic braking opon.
Resistor is connected to B1 and B2. CDBR is connected to – and +3.
*** 24VDC interface board has terminals SN, SC, and SP instead of X2.
Safety Controller
(Oponal)
HC
H1
H2
IG
S-
S+
R-
R+
AC
RP Mul-funcon Pulse Input
0 to 32 kHz
A3 Mul-funcon Analog Input 3
-10 to +10 VDC, 0 to +10 VDC (20kΩ) PTC
A2 Mul-Funcon Analog Input 2
-10 to +10 VDC, 0 to +10 VDC (20kΩ)
4 to 20 mA (250Ω)
A1 Mul-Funcon Analog Input 1
-10 to +10 VDC, 0 to +10 VDC (20kΩ)
-V -10.5 VDC +/-10%, 20 mA
+V +10.5 VDC +/-10%, 20mA
E(G)
S8 MFDI 8
S7 MFDI 7
S6 MFDI 6
S5 MFDI 5
S4 MFDI 4
S3 MFDI 3
S2 MFDI 2
S1 MFDI 1
X2 Common***
X2 Common***
X2 Common***
X2 Common***
120Ω
Terminang
Resistor
DIP Switch S2
Modbus RTU
Communicaons
RS-485/422
115.2 kbps Max.
2kΩ
Digital Inputs
X2X1
L1
L2
L3
EXT FAULT
MICROSPEED
SPEED 5
SPEED 4
SPEED 3
SPEED 2
REV/DOWN
FWD/UP
ULS2
LLS2
120 VAC*
24 VAC*
42-48 VAC*
Branch
Circuit
Protecon &
Disconnect
Line Reactor
(Oponal)
Inputs Outputs
Step 3
PG-X3 Encoder Feedback Card and Encoder Wiring
(IMPULSE•VG+ Series 4 Only)
In this step the PG-X3 encoder feedback card is installed. WITH POWER OFF,
install the PG-X3 card as shown below. Make sure to follow good wiring
practices and follow all applicable codes. Ensure that the feedback card is
grounded properly as shown in item H below.
Option Card Installation
This option card can be inserted into the CN5-C (top) connector located on the
drive’s control board.
Encoder Power Supply Encoder Connection
(Max. 200mA)
Select Encoder Power
Supply (IP + IG TB2)
with Jumper CN3.
It is required to use a differential quadrature
encoder in Flux Vector control mode
(A01-02 = 3).
PG-X3 Encoder Wiring
Ground Lead
A – Connector CN5-C
B – Connector CN5-B
C – Connector CN5-A
D Drive grounding terminal (FE)
E Insert connector CN5 here
F Option card
G Mounting screw
H Lead line ground
I Use wire cutters to create an
opening for cable lines
J Front cover
K Digital operator
L Terminal cover
A – Terminal block TB1
B – Ground terminal (installation hole)
C – Jumper for PG power supply voltage (CN3)
D – Terminal block TB2
E – Model number
F – Installation hole
G – Connector (CN5)
PG-X3 Option Card
Default
IMPORTANT: Verify Encoder
Power Supply Rating
B+ Z+ Z- SD FEA- B-A+
PG-X3 Terminals
a+ a- b- z+IG SGIP
b+
z+
TB1
TB2
+
-
Encoder
Power
Encoder Signals
PG
(Required for Flux Vector Operation)
IMPULSE
®
•G+/VG+ Series 4 Variable Frequency Drive
Quick Start Guide
N49 W13650 Campbell Drive
Menomonee Falls, WI 53051
Phone: 262.783.3500
Fax: 262.783.3510
Toll-Free Phone: 800.288.8178
Toll-Free Fax: 800.298.3503
For questions regarding service or technical information contact:
1.833.SVC.CMCO (1.833.782.2626)
International Service
Outside the U.S. & Canada call 1.262.783.3500, press 3
www.columbusmckinnon.com/magnetek
IMPULSE•G+/VG+ Series 4 Quick Start Guide
144-27514 R1
August 2020 © Copyright 2020 Magnetek
Step 4
Changing Parameters and Monitoring
This step shows how to access and modify a parameter as well as how to
monitor signals such as output frequency and motor current.
Make sure all protective covers have been re-attached and power is turned
on. DO NOT RUN THE MOTOR.
Access Parameter Menu and Change Parameters
Press until the digital operator shows the parameter menu.
Monitor Motor Frequency and Motor Current
Output Frequency and Motor Current can be monitored simultaneously.
To monitor output frequency and motor current or other signals individually,
press once, then press .
Next press to select monitor.
Use to select monitor signal.
NOTE: Refer to the technical manual on how to access other drive monitors.
Digital Operator power-up state
Digits
Flashing
U1-02 Output Frequency
Step 5
Select a Control Method
This step explains the available Control Method settings.
V/f:
Set parameter A01-02 = 0 (V/f).
This setting is only available for IMPULSE•G+ Series 4 drives and is
recommended for most Traverse and Mechanical Load Brake hoist applications.
Open Loop Vector:
Set parameter A01-02 = 1 (Open Loop Vector).
This setting is only available for IMPULSE•G+ Series 4 drives and is
recommended for Traverse and Mechanical Load Brake hoist applications that
require finer speed control or torque limiting.
Flux Vector:
Set parameter A01-02 = 3 (Flux Vector).
This setting is only available for IMPULSE•VG+ Series 4 drives and is locked to
this setting. It is recommended for Hoist applications with no load brake and
requires encoder feedback.
NOTE: An Auto-Tune is recommended when using the Open Loop Vector or Flux
Vector control methods.
Step 6
Select a Motion
This step explains how to configure the VFD for a Hoist or Traverse application.
Traverse:
Set parameter A01-03 = 0 (Traverse).
Hoist (with Mechanical Load Brake):
Set parameter A01-03 = 1 (Standard Hoist).
This setting is not available for IMPULSE•VG+ Series 4 drives.
Hoist (with No Load Brake):
Set parameter A01-03 = 2 (NLB Hoist).
This setting is not available for IMPULSE•G+ Series 4 drives.
NOTE: An Auto-Tune is recommended when using a No Load Brake Hoist motion.
Step 7
Select a Speed Reference
This step lists the speed reference settings.
NOTE: Default speed settings will be automatically applied via X-Press
Programming™. See technical manual for more details and wiring instructions.
2-Speed Multi-Step: A01-04 = 0 Uni-Polar Analog: A01-04 = 5
3-Speed Multi-Step: A01-04 = 1 Bi-Polar Analog: A01-04 = 6
5-Speed Multi-Step: A01-04 = 2 Industrial Communication: A01-04 = 7
2-Step Infinitely Variable: A01-04 = 3 RS485 Communication: A01-04 = 8
3-Step Infinitely Variable: A01-04 = 4
Step 8
Auto-Tuning with Motor
In this step the IMPULSE•G+/VG+ Series 4 drive is set up for
use with the motor. Make sure all protective covers have been
re-attached and then apply power to the VFD. DO NOT RUN
THE MOTOR.
Press until the Digital Operator shows the Auto-Tuning
menu. Then press .
V/f:
Set T01-01 = 2 (Term Resistance)
Open Loop Vector and Flux Vector:
Decouple motor from load and disengage brake.
Set T01-01 = 0 (Standard Tuning)
Press until the Digital Operator shows parameter T01-02 Mtr Rated Power.
Then press .
Press to select the digit you would like to change and use to adjust
value, then press to save.
Press to select the next parameter and follow the same procedure described
above to adjust its value.
T01-03 Rated Voltage (e.g., 230 V, 460 V)
T01-04 Rated Current (e.g., 22.0 A)
T01-05 Rated Frequency (e.g., 60.0 Hz)
T01-06 Number of Poles (e.g., 4 Poles)
T01-07 Rated Speed (e.g., 1750 rpm)
T01-08 Encoder Pulses per Rev (e.g., 1024 PPR)
T01-09 No-Load Current (e.g., 5.0 A)
T01-10 Motor Rated Slip (e.g., 2.90 Hz)
Press the RUN key to start the Auto-Tune.
For Europe: Enter Motor Power in kW
For USA: Enter Motor Power in HP
WARNING! SUDDEN MOVEMENT HAZARD. The motor will spin
during a standard Auto-Tune.
WARNING! ELECTRIC SHOCK HAZARD. High voltage will be
supplied to the motor when Auto-Tuning is performed. Do not
touch the motor during Auto-Tuning.
Digit Flashing
IMPULSE
®
•G+/VG+ Series 4 Variable Frequency Drive
Quick Start Guide
www.columbusmckinnon.com/magnetek
IMPULSE•G+/VG+ Series 4 Quick Start Guide
144-27514 R1
August 2020 © Copyright 2020 Magnetek
N49 W13650 Campbell Drive
Menomonee Falls, WI 53051
Phone: 262.783.3500
Fax: 262.783.3510
Toll-Free Phone: 800.288.8178
Toll-Free Fax: 800.298.3503
For questions regarding service or technical information contact:
1.833.SVC.CMCO (1.833.782.2626)
International Service
Outside the U.S. & Canada call 1.262.783.3500, press 3
Next, press on the Digital Operator. The IMPULSE•G+/VG+ Series 4 will
now start the Auto-Tuning procedure. The display will show message “Tune
Successful” when the Auto-Tuning procedure has been successfully completed.
Please reference the technical manual or repeat the procedure again if the
display shows an error message.
Encoder Direction
Check the motor speed monitor U01-05
while turning the motor manually in forward
direction (CW). If the sign displayed is
negative, power down the drive, wait at
least five minutes until the charge
indicator extinguishes completely, then
swap encoder wires A+ with A- on the
PG-X3 card. Next, power up the drive and
repeat this test. Or, reverse the encoder
direction with parameter F01-02.
Frequently Asked Questions
Question: How do I reset the drive back to factory
default settings?
Answer: Go to parameter A01-05 and enter 1110.
Question: How do I adjust the time it takes the motion to
speed up or slow down?
Answer: Adjust the acceleration time parameter B05-01
and deceleration time parameter B05-02.
Question: How do I prevent my drive from tripping on an
OV fault (overvoltage) while my motor is ramping down?
Answer:
Increase deceleration time parameter B05-02
and check braking resistor.
Question: How do I prevent my drive from tripping on an
OL1 fault (overload) while my motor is ramping down?
Answer: Verify motor rated current parameter E02-01
and motor overload protection time parameter L01-02.
Question: How can I run my motor above the base
motor speed?
Answer: Increase the value of parameter E01-04
Maximum Frequency.
Verify that the motor and system allow for this.
Question: How can I change motor direction without
changing the motor leads?
Answer: Set parameter B03-04 to 1 (exchange phases).
Question: What should I do when the drive detects a
brake failure and displays a BE6 or BE8 fault?
Answer: Do not turn off power! Lower the load to the
ground and inspect the brakes.
Question: On an IMPULSE•VG+ Series 4 hoist
application, why does the brake stay open temporarily at
the end of a run?
Answer: This feature is called Load Float and reduces
wear on the brakes. See parameter C08-10 to adjust the
time.
Question: Where can I find troubleshooting information
regarding faults and alarms?
Answer: Reference the technical manual.
Step 9
Quick Start Parameters
The following table lists commonly used parameters as well as frequently asked questions.
Refer to Step 4 for a detailed explanation on how to change parameters.
Parameter Description Settings Comments
A01-01 Access Level 0 = Operation
1 = User
2 = Advanced
A01-02 Control Method 0 = V/f
2 = Open Loop Vector*
3 = Flux Vector*
* Auto-Tune Recommended
A01-03 Motion 0 = Traverse
1 = Hoist w/ Load Brake (G+ only)
2 = Hoist w/o Load Brake (VG+ only)
4 = Braketronic
A01-04 Speed Reference 0 = Two-Speed Multi-Step
1 = Three-Speed Multi-Step
2 = Five-Speed Multi-Step
3 = Two-Step Infinitely Variable
4 = Three-Step Infinitely Variable
5 = Uni-Polar Analog (0-10VDC, 4-20mA)
6 = Bi-Polar Analog (-10 – +10VDC)
7 = Industrial Communication
8 = RS485 Communication
B01-01 – B01-16 Speed References 0.00 - 150.00 Hz Limited by E01-04
B05-01 Acceleration Time 0.0 - 25.5 Seconds
B05-02 Deceleration Time 0.0 - 25.5 Seconds
E01-01 Input Voltage 155 - 255 VAC (230 VAC Models)
310 - 510 VAC (460 VAC Models)
446 - 733 VAC (575 VAC Models)
Line Voltage
E02-01 Motor Rated FLA Dependent on O02-04 Setting See Motor Nameplate
H01-xx Digital Inputs
See Technical Manual for Options
Terminals S1 - S8
H02-xx Digital Outputs Terminals M0-M1, M2-M3, M5-M6
H03-xx Analog Inputs Terminals A1, A2, A3
H04-xx Analog Outputs Terminals AM, FM
IMPULSE
®
•G+/VG+ Series 4 Variable Frequency Drive
Quick Start Guide
www.columbusmckinnon.com/magnetek
IMPULSE•G+/VG+ Series 4 Quick Start Guide
144-27514 R1
August 2020 © Copyright 2020 Magnetek
N49 W13650 Campbell Drive
Menomonee Falls, WI 53051
Phone: 262.783.3500
Fax: 262.783.3510
Toll-Free Phone: 800.288.8178
Toll-Free Fax: 800.298.3503
For questions regarding service or technical information contact:
1.833.SVC.CMCO (1.833.782.2626)
International Service
Outside the U.S. & Canada call 1.262.783.3500, press 3
  • Page 1 1
  • Page 2 2
  • Page 3 3

Magnetek IMPULSE G+/VG+ Series 4 Quick start guide

Type
Quick start guide

Magnetek IMPULSE G+/VG+ Series 4 variable frequency drive (VFD) offers precise speed control for various applications, including hoisting machines, cranes, and lifting devices. With Flux Vector control, it ensures accurate torque control and smooth operation, especially for hoist applications without load brakes. Its built-in Auto-Tuning feature simplifies setup by automatically adjusting to your motor's characteristics. The VFD also provides multiple speed reference options and supports various motion control modes, such as traverse and hoist, for added versatility.