Haier AP482AKEAA User manual

Type
User manual
Commercial Air Conditioning
SERVICE MANUAL
Models
AU182AEEAA
AU242AGEAA
AU48NAIEAA
AU60NAIEAA
AP482AKEAA
zFeatures
zHigh energy efficiency
zFixed frequency
zOptional different side frame color
zQuiet operation
zAuxiliary electric heating function (optional)
zNew friendly refrigerant R410a, environment protection
zWeekly timer (standard)
zGroup control function
zAuto restart function
Manual code: SYJS-029-06REV.0 Edition: 2006-08-24
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
2
CONTENTS
Contents………………………………………………………...2
1. Description of products & features………………………..3
2. Specification…………………………………………………5
3. Safety precaution……………………………………………8
4. Net dimension……………………………………………….10
5. Installation instructions………..……………………………12
6. Parts and functions………………………………………….12
7. Controller functions………………………………………….13
8. Electrical control functions………………………………….14
9. Refrigerant circuit…………………………………………....23
10 . Electrical data…………………………………………........24
11. Troubleshooting...............................................................31
12. Performance curves........................................................41
13. Noise level charts...........................................................45
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
3
1.DESCRIPTION OF PRODUCTS & FEATURES
1.1. Products code explanation
Climate type: T1 (see table 1)
Design number (A-G stands for fixed frequency type, R-Z
stands for DC inverter frequency type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407C
E stands for heat pump type, refrigerant is R410a
Q stands for cool only type, refrigerant is R410A
Outlook appearance
Product series: A stands for 1 to 1
Applicable voltage: 2 stands for 220~230V/50Hz,
4 stands for 220V/60HzˈN stand for 380~400VAC/50Hz
Cooling / Heating capacity,18=18000BTU/h
Product type : “B” stands for cassette type, “C” stands for
convertible type, ”D” stands for duct, “S” stands for wall
mounted type, ”Q” stands for chiller system, "E" stands for
ceiling concealed type, “U” stands for outdoor unit
Air Conditioner
1.2 Brief Introduction for T1
ǃ
T2
ǃ
T3 working condition
1.3 Operating Range of Air Conditioners
Temp. Mode Rated Maximum Minimum
DB ć
27 32 15
Indoor
WB ć
19 23 14
DB ć
35 43 -5
Cooling
Outdoor
WB ć
24 26 6
DB ć
20 27 10
Indoor
WB ć
14.5 --- --
DB ć
7 23 -10
Heating
Outdoor
WB ć
6 18 ---
Climate type
Type of Air
Conditioner
T1 T2 T3
Cooling Only
18 ć~43ć 10ć~35ć 21ć~52ć
Heat pump
-7ć~43ć -7ć~35ć -7ć~52ć
Electricity Heating
~43ć ~35ć ~52ć
A U 18 2 A E E A A
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
4
1.4 Product features
Adopt the much friendlier refrigerant R410a
The air conditioner system adopts the greatly friendly refrigerant R410a, which is protective for the
ozone layer and is good to avoid the earth getting warmer. Benefit for the environment.
Universal outdoor unit
The outdoor unit has been uniformed which can be connected with different type indoor units with
identical capacity such as cassette type, duct type, convertible, cabinet type etc..
Flexible and easy installation
The outdoor can meet the higher request of installation. From the specifications, you will find for
each unit, how long and how high the piping will be, which will be convenient for design and installation.
Quiet operation
Adopting optimum designed blower & new designed insulation material, realizing indoor low noise
running, outdoor unit with well-known brand compressor, reducing the operation noise.
LCD display
Running status can be displayed on the screen, perfect design.
Auto-check function
The unit can display the malfunction codes on the control board by using advanced auto-check
technology, convenient for user find and dwell with the abnormal running.
Auto–restart function (optional)
All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will
automatically recover the previous running mode once the power supply is on.
Low temperature cooling realized, super low temperature heating
realized.
Multiple control type between by hand and the remote control.
Group control and Central control if connected with with a group
controller or a central controller
Weekly timing function, if connected with a weekly timer YCS-A001
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
5
2. SPECIFICATION
Function
cooling heating
Capacity kW
13.6 16.0
Sensible heat ratio
0.72
W
4500 5250
W
5500 6000
EER or COP
W/W 3.02˄B˅ 3.05˄D˅
Dehumidifying capacity
10ϋ³×m³/h
A / A
8.0A/9.5A 9.0A/10.5A
Start Current A
65 65
Unit model (color)
Type × Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Temp. scope
ć
External
˄L×W×H˅
mm×mm×mm
Package
˄L×W×H˅
mm×mm×mm
Control type (Remote /wired)
dB(A)
kg / kg
Dehumidifying capacity
10ϋ³×m³/h
Power cable section
Connecting cable section
Power source N, V, Hz
Start Current A
Max. operating pressure of heat side Mpa
4.5
Max. operating pressure of cold side Mpa
4.5
Unit model (color)
Model / Manufacture
Type
Type × Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Temp. scope
ć
External
˄L×W×H˅
mm×mm×mm
Package
˄L×W×H˅
mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Noise level dB(A)
material of reduce noise
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
H05RN-F 3G 2.5mm2
H05RN-F 3G 2.0mm2 +H05RN-F 1x0.75mm2
5.5
Max. power input
item Model
Total power input
AP482AKEAA
Indoor unit
AP482AKEAA˄white)
Fan
centrifugal fan X1
460/430/400±40
0.06
1750/-/-m³/h
TP2M/7.0
2-7
51/48/44
1850×600×350
1980×660×420
Weight (Net / Shipping)
59/70
Remote
Running /Max.Running current
Noise level (H-M-L)
Dimension
Heat exchanger
flared
Between I.D &O.D
MAX.Drop 10
MAX.Piping length 20
XPE
Weight (Net / Shipping)
42/45
PIPING
Refrigerant
R410A/1500
20
Pipe
6.35
12.7
Capillary tube
Defrosting
controlled by coil temp.
56
Dimension
775x640x245
901x341x712
/
35
2300
Heat exchanger
TP2M/7X0.5
43-60
50
Outdoor unit
AU182AEEAA (WHITE)
Compressor
PA200X2CS-4KU1/Meizhi
Rotary
Fan
Axial X 1
860±40
AU182AEEAA
1.8
1 PH 220-230 V 50 Hz
item Model
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
6
Power cable
Power source N, V, Hz
Unit model (color)
Model / Manufacture
Oil model
VG74
Oil charging
950ML
Type
Type × Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Row / Fin pitch
Temp. scope
ć
External
˄L×W×H˅
mm×mm×mm
Package
˄L×W×H˅
mm×mm×mm
RefrigEAAnt control method mm/mm
Volume of Accumulator L
Noise level dB(A)
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
Power cable
Power source N, V, Hz
Unit model (color)
Model / Manufacture
Oil model
Oil type
Oil charging
Type
Type × Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Row / Fin pitch
Temp. scope
ć
External
˄L×W×H˅
mm×mm×mm
Package
˄L×W×H˅
mm×mm×mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
7000
FVC68D
H07RN-F 5G 4.0mm2
OU:380-400V,3N,50HZ IU:1PH,220-230V,50HZ
860±40
0.08
15
MAX.Piping length 30
PIPING
RefrigEAAnt
R410A/2100
50
Pipe
9.52
15.88
flare
Between I.D &O.D
MAX.Drop
37
Weight (Net / Shipping)
57/60.5
Dimension
948*340*1250
1050*440*1375
Heat exchanger
TP2M/9.52
3/1.55
43-60
axial×2
DAPHNE
AU48NAIEAA
WHITE
Compressor
JT160G-P8Y1˄DAIKIN˅
SHF-4-10A
1500CM3
Rotary
item Model
Outdoor unit
Fan
Type of Four way valve
PIPING
3
60
Type of Four way valve
SHF-4-10A
Refrigerant
R410A/3700
65
Pipe
9.52
19.05
flare
Between I.D &O.D
MAX.Drop 30
MAX.Piping length 50
55
Weight (Net / Shipping)
106/111
capillary 2.4*150
Defrosting
AUTO
Defrosting
AUTO
3
57
Dimension
865*335*732
995*420*815
ĭ1.8*300 capillary
Heat exchanger
TP2M/ij7
3/1.46
43-60
Outdoor unit
WHITE
Compressor
PA290X3CS-4MU1˄TOSHIBA˅
Rotary
Fan
axial×1
1000±50
0.06
3000
item Model
AU242AGEAA
H05RN-F 3G 4.0mm2
1PH,220-230VAC,50HZ
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
7
Power source N, V, Hz
Unit model (color)
Model / Manufacture
Oil model DAPHNE
Oil type
FVC68D
Oil charging
1500CM3
Type
Type × Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Row / Fin pitch
Temp. scope
ć
External
˄L×W×H˅
mm×mm×mm
Package
˄L×W×H˅
mm×mm×mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
Note: Ĵ is the real
time analyser position
capillary ĭ2.4*150
Dimension
948*340*1250
1050*440*1375
Norminal condition: indoor temperature (cooling): 27 ćDB/19ćWB, indoor temperature (heating): 20 ćDB
Outdoor temperature(cooling): 35ćDB/24ćWB, outdoor temperature(heating): 7ćDB/6ćWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level. The detailed method please refer to the following information:
Power cable
H07RN-F 5G 4.0mm2
Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction.
Testing method:
s
t
an
di
ng-on-
fl
oor un
it
:
If th
e un
it
coo
li
ng capac
ity
is over 28000W, the noise level should be
measured at the front, left, right directions
respectively.
outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level
measured from front, left, right directions.
2.air outlet from top: the noise level is the average sound pressure level
measured from front, back, left, right directions.
measured point:
H ( height to the ground) = (h (unit height) + 1m) /2
and, it is 1m to each side.
connectting cable
H05RN-F 4G 0.75mm2
OU: 380-400V, 3N, 50HZ IU:1PH, 220-230V, 50HZ
0.08
7000
item Model
AU60NAIEAA
Heat exchanger
TP2M/9.52
3/1.5
43-60
Outdoor unit
WHITE
Compressor
JT170G-P8Y1˄DAIKIN˅
Rotary
Fan
axial×2
860±40
Type of Four way valve
SHF-4-10A
55
Defrosting
AUTO
3
60
Weight (Net / Shipping)
106/111
PIPING
Refrigerant
R410A/4050
65
Pipe
9.52
19.05
flare
Between I.D &O.D
MAX.Drop 30
MAX.Piping length 50
1m
1m
h
1m
1m
1m
1m
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
8
3. Safety precaution
Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING!
CAUTION!
Incorrect operations may result in injuries or machine damages; in some cases may
cause serious consequences.
Incorrect operations may result in severe consequences of death or serious injuries.
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
WARNING!
If any abnormal phenomena is found
(e. g.smell of firing), please cut off the
power supply immediately, and contact
the dealer to find out the handling
method.
Don't dismantle the outlet of the
outdoor unit.
The exposed fan is very dangerous
which may harm human beings.
switch
off
In such case, to continue using the
conditioner will damage the conditioner,
and may cause electrical shock or fire
hazard.
Incorrect maintenance and repairment
may cause water leak, electrical shock
and fire hazard.
When the unit needs maintenance and
repairment, please call dealer to handle it.
After the unit being used for a long time,
the base should be checked for any
damages.
If the damaged base is not repaired, the
unit may fall down and cause accidents.
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
9
Air-conditioner can't be installed in
the environment with inflammable
gases because the inflammable gases
near to air-conditioner may cause fire
hazard.
Connect earthing wire.
Use discharge pipe correctly to ensure
efficient discharge.
Earthing wire should not be con-
nected to the gas pipe, water pipe,
lightning rod or phone line, in-correct
earthing may cause shock.
Incorrect pipe use may cause water
leaking.
Earthing
WARNING!
Installed electrical-leaking circuit
breaker.
It easily cause electrical shock without
circuit breaker.
Please let the dealer be responsible for
installing the conditioner.
Incorrect installation may cause water
leak, electrical shock and fire hazard.
Call the dealer to take measures to
prevent the refrigerant from leaking.
If conditioner is installed in a small
room be sure to take every measure in
order to prevent suffocation accident
even in case of refrigerant leakage.
When conditioner is deinstalled or
reinstalleddealer should be responsible
for them.
Incorrect installation may cause water
leaking, electrical shock and fire hazard.
No goods or nobody is permitted to
placed on or stand on outdoor unit.
The falling of goods and people may
cause accidents.
Don't operate the air-conditioner with
damp hands.
Otherwise will be shocked.
Only use correctly-typed fuse.
May not use wire or any other materials
replacing fuse, other-wise may cause
faults or fire accidents.
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
10
4. Net dimension
350
350
336
500
1851
600
AU182AEAA
6AF;B 8=B=@< 7;B?=@9>
6AF;B 8=B=@<
4=CDB=:ED=A@ 5A>;
-0
23+
1/+
0++
-2+
AP482AKEAA
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
11
AU242AGEAA
AU48NAIEAA, AU60NAIEAA
948
1250
25
Power wiring Terminal
184 184
55
Screw Hole
580
70
380
18
340
18
(4xM10)
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
12
5. Installation Instructions
For outdoor unit, Please reference to the ROOM AIR CONDITIONER OUTDOOR UNIT
INSTALLATION INSTRUCTIONS 0010577959A.
As for the cabinet indoor unit, Please reference to the
CABINET TYPE AIR CONDITIONER
Operation & Installation Manual 0010578212.
**+
**
**-
1
2
3
4
2
1
2
3
4
I n d o o r u n i t
Outlet grill
Operation panel
Inlet grill
Air filter [inside the unit]
SLEEP
ON/OFF
MODE
FAN
TEMP +
TEMP -
HEALTH
SET
HUMI
TEMP
HEALTH
TIMER
SLEEP
TEMP
HUMI
SET
SLEEP
TIMER
HEALTH
ON/OFF
MODE
FAN
SET
TEMP
HUMI
HEALTH
TIMER
6. Parts and Functions
FNW NSQJY
FNW TZYQJY LWNQQJ
XYTU [FQ[J
HTRUWJXXTWnNSXNIJ TK ZSNYo
AU182AEEAA
AP482AKEAA
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
13
7. Controller functions
For cabinet type, the indoor unit can be controlled by remote controller YR-H49.
FNW NSQJY
FNW TZYQJY
HTRUWJXXTWnNSXNIJ TK ZSNYo
YTU HT[JW
XYTU [FQ[J
\NWNSL GT] HT[JW
FNW TZYQJY LWNQQJ
GTYYTR UQFYJ
KWTSY UFSJQ
AU242AGEAA
XYTU [FQ[J
FNW NSQJY
FNW TZYQJY
HTRUWJXXTWnNSXNIJ TK ZSNYo
AU48NAIEAA, AU60NAIEAA
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
14
1.Indoor AUTO FAN control
A. During cooling program.
If the unit enters AUTO FAN for the first time, when Tr˚Ts+2, select high speed; when TrİTs,
select low speed; or it will select med speed; If the present fan speed is AUTO HIGH, when Tr˘
Ts+2, fan speed will change to AUTO MED. If the present fan speed is AUTO MED, when Tr˘Ts,
fan speed will change to AUTO LOW; when Tr˚Ts+3, fan speed will change to AUTO HIGH. If the
present fan speed is AUTO LOW, when Tr˚Ts+1, fan speed will chenge to AUTO MED. Fan speed
conversion in AUTO FAN mode: the conversion will delay for 3 minutes from HIGH to LOW, and no
delay from LOW to HIGH.
B. During heating program.
If the unit enters AUTO FAN for the first time, when Tr˚Ts-1, select low speed; when TrİTs-3,
select high speed; or it will select med speed; If the present fan speed is AUTO LOW, when Tr˘
Ts-1, fan speed will change to AUTO MED. If the present fan speed is AUTO MED, when Tr˚Ts,
fan speed will change to AUTO LOW; when Tr˘Ts-3, fan speed will change to AUTO HIGH. If the
present fan speed is AUTO HIGH, when Tr>Ts-2, fan speed will chenge to AUTO MED (Ts means
setting temperature on the wired controller). Fan speed conversion in AUTO FAN mode: the
conversion will delay for 3 minutes from HIGH to LOW, and no delay from LOW to HIGH.
2. Automatic run
1). Cooling-heating type
After the machine being started and running mode changes to AUTO, the system will decide
running mode according to difference between the present room temperature and setting
temperature, then runs as the decided mode. In the following selections, Tr means room
Ts 2
Ts 1
Medium speed
Low speed
High speed
Ts 3
Ts
Low speed
Medium speed
High speed
temperature
falling
temperature
rising
Ts 1
Ts 2
Ts
Ts
3
High speed
High speed
Medium speed
Medium speed
Low speed
Low speed
temperature
falling
temperature
rising
8.1 For cabinet indoor unit
8. Electrical Control Functions
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
15
temperature and Ts means setting temperature.
Select running mode according to the following conditions at the first time to enter Auto mode:
TrıTs -3ć to select cooling mode (with setting temperature being Ts +3)
Tr˘Ts -3ć to select heating mode (with setting temperature being Ts)
After the system entering auto run mode, the running mode can convert automatically
according to variation of room temperature between cooling and heating. If the unit is in cooling
mode, when the temperature arrives stop value, the compressor stops; the system will measure the
temperature after compressor stops for 3 minutes. At this time, if Tr˘Ts-3ć, the unit will enter
heating mode, or it will still be cooling mode. If the unit is in heating mode, when the temperature
arrives stop value, the compressor stops; the system will measure the temperature after
compressor stops for 3 minutes. At this time, if Tr˘Ts+3ć, the unit will enter cooling mode, or it will
still be heating mode.
If the unit is in heating mode, when indoor heat exchanger temperature is over 63ć, the unit
will turn into cooling mode automatically, in 1 hour, the indoor heat exchanger temperature will not
be limited, and heating operation will stop temporarily, 1 hour later, the system will adjust the
working mode due to the above conditions.
If the unit is in heating mode for the first time, compressor motor will start up, within 8 minutes the
system will not measure indoor ambient temperature, the remote controller will be off.
2). Single Cooling type
Select running mode according to the following conditions at the first time to enter Auto mode:
TrıTs +3ć to select cooling mode
Tr˘Ts -3ć to select blowing mode
After entering Auto mode, the operation mode can be changed between cooling mode and fan
mode according to indoor ambient temperature: if the unit now is in cooling mode, when Tr˘Ts-3,
the mode will be changed to Fan; if the unit is in Fan mode, when TrıTs+3, the mode will be
changed to cooling mode.
3. COOL mode control
4-way valve being powered off, compressor run/stop will depends on the temperature
difference between the room temperature and the set temperature.
TrıTs+1 compressor will run;
TrİTs-1 compressor will stop;
Ts-1<Tr<Ts+1 compressor will stay in original state
Anti-freezed protection
When the unit has run for over 6 minutes after compressor starts up, if indoor coil temperature
Tg<1ć last 1 minute, the compressor and the outdoor motor will stop; 9 minutes later after
compressor stops and when indoor coil temperature rises to 10ć, the compressor and the outdoor
motor will run again.
run
stop
1
ˉ1
run
stop
7
7
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
16
Current peak value protection
Controlled by outdoor unit.
4. DRY mode control (in the following selections, Tr means room temperature and Ts means setting
temperature.)
When the uint enters DRY mode for the first time, the compressor, outdoor motor and indoor
motor will perform according to the below conditions:
Tr> Tsˇˎć the compressor and the outdoor motor will run continuously, indoor motor will run
at the set speed, this area is defined as Area A;
TsİTrİTsˇˎć, the compressor and the outdoor motor will always run for 10 minutes and
then stop for 6 minutes, indoor motor will be LOW speed, this area is defined as Area B;
Tr < Ts, the compressor and the outdoor motor will stop, indoor motor will run at Low speed,
this area is defined as Area C.
After the unit is running in DRY mode, the system will change over among Area A, Area B, and
Area C. If the system is in Area A, when Tr˘Ts+2, change to Area B; If the system is in Area C,
when Tr > Ts, change to Area B; If the system is in Area B, when Tr> Tsˇˏ, change to Area A;
When Tr˘Ts ˉˍ, change to Area C.
Anti-freezed protection: When the unit has run for over 6 minutes after compressor starts up, if
indoor coil temperature Tg<1ć last 1 minute, the compressor and the outdoor motor will stop; 9
minutes later after compressor stops and when indoor coil temperature rises to 10ć , the
compressor and the outdoor motor will run again.
5. Fan mode control
Compressor and outdoor motor stop working, indoor motor can set High, Med and Low speed, the
fan blade can swing or be fixed on a position. In this mode, you can set TIMER function, but there is
no SLEEP function. Also, you can set high voltage dirt collecting or fresh air function.
6. HEAT mode control (in the following selections, Tr means room temperature and Ts means setting
temperature.)
4-way valve control: When entering heating mode for the first time, compressor starts up,
4-way valve will be on 3 minutes later; in heating mode, 4-way valve will not be off. If the unit
changes from heating to other modes, 4-way valve will be off immediately.
compressor control: the compressor and outdoor fan motor will depends on the temperature
difference between the room temperature and the set temperature.
TrıTs + 1 compressor stops
TrİTs- 1 compressor running
Area B
Area B
Area C
Ts
Area A
Area A
Ts 3
Ts 1
Ts 1
Area C
Room
temperature
rising
Room
temperature
falling
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
17
Ts-1<Tr<Ts + 1 compressor retains original state
Outdoor motor and the compressor runs or stops simultaneously (except for overheat
protection), indoor fan speed can be set at High, Med, Low or Auto speed, and the fan blade can
swing or be fixed on one position. You can set TIMER or SLEEP mode.
Overheat protection
In heating mode, compressor has started up and indoor motor has run for over 30 seconds, if
indoor coil temperature Tg>56ć, outdoor motor will chenge to LOW; if Tg<52ć, and outdoor motor
has stop for 45s, outdoor motor will run again; if indoor coil temperature Tg>60ć, outdoor motor will
stop; if Tg<56ć, and outdoor motor has stop for 45s, outdoor motor will run again; if Tg>68ć, the
compressor will stop and indoor motor will run according to the thermostat OFF state. After the
compressor stops for 9 minutes and Tg reduces to 48ć, the unit will resume to heating mode, and
the compressor and the outdoor motor will run again.
Anti-cold air function in heating mode
When the uint enters heating mode for the first time, or last defrosting is over, if Tg˘28ć,
indoor motor will stop; if 38ć>Tgı28ć, indoor motor will run at low speed; if Tgı38ć or the
compressor has run for over 4 minutes, indoor motor will run at the set speed.
Blowing remaining heat function
In heating mode, the thermostat is OFF, the compressor stops, indoor motor will run at low
speed at least 50 seconds.
Auxiliary electric heating function
Enter condition:
1) TrİTs -2 ć
2) compressor ON and running for 1 minute
3) Trİ23ć
4) Indoor motor running
5) Electric heating function start signal available (cancelled)
If the above conditions can all be met, the electric heating function will work.
If one of the below conditions can be met, the electric heater will stop:
1) TrıTs -1 ć
2) compressor OFF or indoor motor stops
3) Trı25ć
4) Electric heating function start signal not available (cancelled)
Manual defrost:
In heating mode, the set temperature 30ć and in high speed, in 5 seconds, press SLEEP
button 6 times continuously, then the buzzer will sound 3 times, you can enter the manual
run
stop
Ts+1
Ts-1
Room
temperature
falling
Room
temperature
rising
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
18
defrosting.
For the unit with auxiliary electric heating function, If the auxiliary electric heating function is
working when the defrosting condition is met, please stop electric heater firstly, 3 seconds later,
defrosting can begin.
7. SLEEP function
Sleep function can be setted in COOLING, DRY and HEATING mode. in cooling or dry mode,
after running at SLEEP mode for 1 hour, the set temperature will rise 1ć, another 1 hour later, the
set temperature will rise another 1ć; the unit continues running for 6 hours, then the unit will stop.
Setting temperture
SLEEP time
1 2 8
In heating mode, after running at SLEEP mode for 1 hour, the set temperature reduces 2ć,
another 1 hour later, the set temperature will reduce 2ć, and another 3 hours later, the set
temperature rises 1ć; the unit continues running for 3 hours, then the unit will stop.
Setting temperture
SLEEP time
1 2 5 8
8. Compulsory cooling operation
After the panel receives the compulsory cooling signal, the unit enters the compulsory cooling state.
and indoor/outdoor motors are in high speed; in the 5 minutes, the system will not adjust the
protection and not be limited by the ambient temperature, but the compressor will be limited by
3-minute protection. 5 minutes later, the unit will enter the normal cooling state.
9. System protection
9.1 3-minute protection for compressor startup
After the compressor stops, at least 3 minutes later, the compressor can restart up; if the unit
is powered off in running less than 3 minutes, after being electrified, 3 minutes later, the compressor
can restart up. Being electrifed for the first time, there is no 3-minute delay protection.
9.2 Sensor failure protection
9.3 Communication failure protection
10. Panel selection
Select the panel according to the 2 dip switch
Style of panel 1 2
Cabinet V panel OFF ON
Cabinet Z panel ON OFF
Wired controller ON ON
T
s
Ts+ 1
Ts+ 2
Ts
Ts- 2
Ts- 3
Ts- 4
8.2 For outdoor unit
1. Outdoor motor control
When the system does not occur overcooling, overheating, and over current protections, the
outdoor motor will occur the below changes according to the outdoor ambient temperature and
indoor coil temperature.
1.1 General information
Outdoor motor is 2-speed type: high, low and stop.
The fan speed will change unless every step has been run for 45 seconds.
1.2 Cooling mode
1.2.1 Indoor coil temp.ı15ć, outdoor motor runs at high speed.
1.2.2 Indoor coil temp.˘5ć, outdoor motor runs at low speed.
1.2.3 5ćİIndoor coil temp.˘15ć, outdoor motor will change due to the outdoor ambient temp.
Outdoor ambient temp. ˚28ć, enter high speed; outdoor ambient temp.˘26ć, enter high speed;
26İoutdoor ambient temp.İ28ć, keep the current speed.
In running, the system will be controlled as 2ć temperature tolerance; if outdoor ambient temp. ˘
26ć, enter low speed; if outdoor ambient temp.˚28ć, enter high speed.
1.3 Heating mode (heat pump model)
1.3.1 Indoor coil temp.ı50ć, outdoor motor will run at low speed.
1.3.2 Indoor coil temp. ˘40ć, outdoor motor will run at high speed.
1.3.3 40ćİindoor coil temp.˘50ć, outdoor motor will change with outdoor ambient temp.
Outdoor ambient temp.˘13ć, enter high speed; Outdoor ambient temp.˚15ć, enter low speed;
13İOutdoor ambient temp.İ15ć, keep the current speed;
In running, the system will be controlled as 2ć temperature tolerance; if outdoor ambient temp. ˘
13ć, enter high speed; if outdoor ambient temp.˚15ć, enter low speed.
Every step will run at least 45 seconds, and the motor will start up 2 seconds earlier than
compressor.
2. Defrost control
2.1 Defrosting condition
In heating mode, the compressor will run for 30 minutes continuously or run for 45 minutes in all
and for over 5 minutes contineously, outdoor motor at least runs for 2 minutes; If the outdoor
ambient temperature and outdoor coil temperature can comply with the shadow area in the figure
and keep for 1 minute, the defrost will work and send defrost signal to indoor unit, then indoor unit
will control indoor motor accordingly.
2.2 Quit condition
Outdoor coil temp. arrives the defrost-end temp. 14ć or the defrost time is over 12 minutes, the
defrost will finish and send signal to indoor unit.
2.3 Defrost operation
Compressor and outdoor motor stop, indoor motor stops meanwhile; 55 seconds later, the
reversing valve will close. Another 5 seconds later, compressor starts up.
After defrost is over, compressor stops, outdoor motor runs at high speed; 55 seconds later, the
reversing valve will open. Another 5 seconds later, compressor starts up and indoor motor runs at
anti-code mode.
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
19
Type 1: Standard defrost
1) If Trı-2ć, when Tpİ-6ć, enter defrost.
2) If -12ćİTr˘-2ć, when Tpİ-6ć, please refer to the following chart.
3) No matter the ambient temperature, when Tpİ-16ć, enter defrost.
Type 2: Non-standard defrost (rectify defrost data by the device)
1) If Trı6ć, when Tpİ-6ć, enter defrost.
2) If -18ćİTr˘-6ć, when Tpİ-6ć, please refer to the following chart.
3) No matter the ambient temperature, when Tpİ-18ć, enter defrost.
2.4 Manual defrost
Indoor sends defrost signal to outdoor, and the outdoor will receive the defrost signal when
compressor is running in heating mode, then enter the defrost process. When outdoor coil
temperature arrives the defrost-end point and the defrost time is over 5 minutes, outdoor will send
the defrost-end signal to finish the defrost.
3. Compressor crankcase heater working condition
By the N.C. (normal close) auxiliary point of AC contactor to control, when compressor stops, the
heater will work; when compressor works, the heater will stop.
4. System protection function
4.1 Anti-freezed protection
-6ć
A
mbient
Coil tem
p
.
(
ć
)
6ć-18ć
-6ć
-
18
A
mbient
Coil tem
p
.
(
ć
)
-
2
-
12
-16ć
Commercial Air Conditioner Model: AP*****EAA AU*****EAA
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47

Haier AP482AKEAA User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI