9
SE80/185T & SE100/185T Ignition Protected thruster assembly 1.0 - 2007
• Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
• It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the
list below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
• A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power
for the thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed
in an easily accessible place and the boats instructions should include information that this should be turned off like the other main
switches of the boat.
• We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be
of a adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It
should be of the slow type and sized to take the amperage draw for atleast 5 minutes.
• Remember to use ignition protected fuses and switches if tted in areas that require this feature.
• A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
• The cable ends must be tted with terminals and these must be well isolated against contact with anything but the proper connection
point.
• If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
• The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
• The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Model Voltage Nominal
current
draw
Min. battery
CCA
>7m total + & - 7-14m total + & - 15-21m total + & - 22-28m total + & - 28-35m total + & - 36-45m total + & -
Min. Rec. Min. Rec. Min. Rec. Min. Rec. Min. Rec. Min. Rec.
SE80/185T 12 V 530 A DIN: 550
SAE:1045
mm2
AWG
60
2/0
70
2/0
95
3/0
2x 70
2x 2/0
2x 70
2x 2/0
2x 95
2x 2/0
2x 95
2x 3/0
270* 2x 120
2x 4/0
340* NA NA
24 V 260 A DIN: 300
SAE: 570
mm2
AWG
25
1
35
1
35
1
50
1/0
60
2/0
70
2/0
70
2/0
95
3/0
95
3/0
120
4/0
120
4/0
2x 95
2x 3/0
SE100/185T 12 V 740 A DIN: 750
SAE: 1425
mm2
AWG
95
3/0
95
3/0
2x 70
2x 2/0
2x 95
2x 3/0
2x 95
2x 3/0
280* 250* 375* NA NA NA NA
24 V 340 A DIN: 400
SAE: 760
mm2
AWG
35
1
50
1/0
50
1/0
70
2/0
60
2/0
95
3/0
95
3/0
120
4/0
120
4/0
2x 95
2x 3/0
2x95
2x 3/0
2x 120
2x 4/0
Minimum and recommended cable dimensions can be identical due to safety margins and cable heat considerations for short cable lenghts.
* Minimum or recommended cable cross section in mm2
Battery & cable recommendations:
9
SP75Ti / SP95Ti ignition protected thruster assembly
1.2.1 - 2007
•Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
•It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list
below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
•A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily
accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.
•We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should
be of the slow type and sized to take the amperage draw for atleast 5 minutes.
•Remember to use ignition protected fuses and switches if fitted in areas that require this feature.
•A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
•The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.
•If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
•The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
•The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Battery
12V or 24V
+-
*D
*C
Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer
50 mm2 95 mm2 120 mm2 150 mm2 N / A N / A
O OOO+ OOOO+ 2xOOO
N / A 50 mm2 70 mm2 95 mm2 120 mm2 150 mm2
O OO+ OOO+ OOOO+ 2xOOO
35 mm2 35 mm2 50 mm2 70 mm2 95 mm2 120 mm2
2 2 O OO+ OOO+ OOOO+
70 mm2 105 mm2 150 mm2 175 mm2 N / A N / A
OO+ OOOO 2x OOO 2xOOOO
N / A 70 mm2 95 mm2 120 mm2 150 mm2 180 mm2
OO+ OOO+ OOOO+ 2xOOO 2xOOOO
50 mm2 50 mm2 70 mm2 95 mm2 120 mm2 150 mm2
O O OO+ OOO+ OOOO+ 2xOOO
Table for s election of m ain cable,
battery, fuse and m ain-s witch
s ize s .
up to 7m total + & - 7 - 14m total + & - 14 - 21m total + & - 21 - 28m to tal + & - 28 - 35m total + & - 36 - 45m total + & -
M o de l V oltage Cur r e n t
dr aw
M in. Cable
dim e ns io n
M in.Batte ry
CCA b y DIN
M in. Cable
dim e ns io n
M in. Cable
dim e ns io n
M in. Cable
dim e ns io n
M in.Batte ry
CCA b y Din
M in.Batte ry
CCA b y DIN
M in. Cable
dim e ns io n
M in. Cable
dim e ns io n
M in.Batte r y
CCA b y DIN
M in.Batte r y
CCA b y Din
550 CCA Din
1045 CC A SA E
600 CCA Din
1140 CC A SA E
SP 75 Ti IP
12 V 480 A 550 CCA Din
1045 CCA SA E
24 V 240 A 300 CC A D in
570 CCA SA E
12V
Extr .batt * 300 A 300 CC A D in
570 C C A SA E
300 CC A D in
570 C C A SA E
350 CCA Din
665 CC A SA E
350 CCA Din
665 CC A SA E
350 CCA Din
665 CC A SA E
550 CCA Din
1045 CC A SA E
300 CC A D in
570 C C A SA E
300 CC A D in
570 C C A SA E
350 CCA Din
665 CC A SA E
350 CCA Din
665 CC A SA E
750 CCA Din
1425 CC A SA E
750 CCA Din
1425 CC A SA E
750 CCA Din
1425 CC A SA E
SP 95 Ti IP
12 V 680 A 750 CCA Din
1425 CCA SA E
12V
Extr .batt * 400 A 350 CC A D in
665 C C A SA E
24 V 340 A 400 CC A D in
760 CCA SA E
400 CC A D in
760 C C A SA E
M in.Batte r y
CCA b y Din
400 CC A D in
760 C C A SA E
400 CCA Din
760 CC A SA E
450 CCA Din
855 CC A SA E
450 CCA Din
855 CC A SA E
350 CC A D in
665 C C A SA E
350 CCA Din
665 CC A SA E
350 CCA Din
665 CC A SA E
350 CCA Din
665 CC A SA E
350 CCA Din
665 CC A SA E
9
SE 60/185S ignition protected thruster assembly 1.0 - 2007
• Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
• It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the
list below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
• A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power
for the thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed
in an easily accessible place and the boats instructions should include information that this should be turned off like the other main
switches of the boat.
• We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be
of a adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It
should be of the slow type and sized to take the amperage draw for atleast 5 minutes.
• Remember to use ignition protected fuses and switches if tted in areas that require this feature.
• A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
• The cable ends must be tted with terminals and these must be well isolated against contact with anything but the proper connection
point.
• If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
• The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
• The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Model Voltage Nominal
current
draw
Min. battery
CCA
>7m total + & - 7-14m total + & - 15-21m total + & - 22-28m total + & - 28-35m total + & - 36-45m total + & -
Min. Rec. Min. Rec. Min. Rec. Min. Rec. Min. Rec. Min. Rec.
SE60/185S 12 V 340 A DIN: 350
SAE:665
mm2
AWG
35
1
50
1/0
60
2/0
95
3/0
95
3/0
2x 70
2x 2/0
120
4/0
2x95
2x 3/0
2x 95
2x 3/0
2x120
2x 4/0
2x120
2x 4/0
280*
24 V 170 A DIN: 175
SAE: 332
mm2
AWG
25
1
35
1
25
1
35
1
25
1
35
1
35
1
50
1/0
50
1/0
60
2/0
60
2/0
70
2/0
Battery & cable recommendations:
Minimum and recommended cable dimensions can be identical due to safety margins and cable heat considerations for short cable lenghts.
* Minimum or recommended cable cross section in mm2
9
SP55S2i ignition protected thruster assembly
1.1 - 2006
•Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
•It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list
below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
•A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily
accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.
•We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should
be of the slow type and sized to take the amperage draw for atleast 5 minutes.
•Remember to use ignition protected fuses and switches if fitted in areas that require this feature.
•A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
•The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.
•If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
•The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
•The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Battery
12V or 24V
+-
*D
*C
Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer
35 mm2 60 mm2 95 mm2 95 mm2 120 mm2 120 mm2
AWG 1 AWG OO AWG OOO AWG OOOO AWG OOOO 2 x AWG OOOO
25 mm2 25 mm2 35 mm2 35 mm2 50 mm2 50 mm2
AWG 4 AWG 4 AWG 2 AWG 2 AWG 1 AWG 1
Min.Batte ry
CCA by Din
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
250 CCA Din
475 CCA SAE
200 CCA Din
380 CCA SA E
400 CCA Din
760 CCA SAE
350 CCA Din
665 CCA SAE
Min.Battery
CCA by Din
12 V 330 A Din
627 A SAE
350 CCA Din
665 CCA SAE
24 V 160 A Din
304 A SAE
200 CCA Din
380 CCA SAE
SP55S2i
IP
Min. Cable
dim e ns ion
Min.Battery
CCA by Din
350 CCA Din
665 CCA SAE
400 CCA Din
760 CCA SAE
400 CCA Din
760 CCA SA E
Min.Batte ry
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
16 - 19m total + & - 20 - 23m total + & - 24 - 27m total + & -
Model Voltage Curre nt
draw
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Table for selection of main cable,
battery, fuse and main-switch
sizes.
up to 7m total + & - 8 - 11m total + & - 12 - 15m total + & -
9
SP55S2i ignition protected thruster assembly
1.1 - 2006
•Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
•It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list
below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
•A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily
accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.
•We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should
be of the slow type and sized to take the amperage draw for atleast 5 minutes.
•Remember to use ignition protected fuses and switches if fitted in areas that require this feature.
•A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
•The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.
•If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
•The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
•The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Battery
12V or 24V
+-
*D
*C
Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer
35 mm2 60 mm2 95 mm2 95 mm2 120 mm2 120 mm2
AWG 1 AWG OO AWG OOO AWG OOOO AWG OOOO 2 x AWG OOOO
25 mm2 25 mm2 35 mm2 35 mm2 50 mm2 50 mm2
AWG 4 AWG 4 AWG 2 AWG 2 AWG 1 AWG 1
Min.Batte ry
CCA by Din
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
250 CCA Din
475 CCA SAE
200 CCA Din
380 CCA SA E
400 CCA Din
760 CCA SAE
350 CCA Din
665 CCA SAE
Min.Battery
CCA by Din
12 V 330 A Din
627 A SAE
350 CCA Din
665 CCA SAE
24 V 160 A Din
304 A SAE
200 CCA Din
380 CCA SAE
SP55S2i
IP
Min. Cable
dim e ns ion
Min.Battery
CCA by Din
350 CCA Din
665 CCA SAE
400 CCA Din
760 CCA SAE
400 CCA Din
760 CCA SA E
Min.Batte ry
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
16 - 19m total + & - 20 - 23m total + & - 24 - 27m total + & -
Model Voltage Curre nt
draw
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Table for selection of main cable,
battery, fuse and main-switch
sizes.
up to 7m total + & - 8 - 11m total + & - 12 - 15m total + & -
9
SP55S2i ignition protected thruster assembly
1.1 - 2006
•Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
•It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list
below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
•A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily
accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.
•We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should
be of the slow type and sized to take the amperage draw for atleast 5 minutes.
•Remember to use ignition protected fuses and switches if fitted in areas that require this feature.
•A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
•The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.
•If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
•The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
•The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Battery
12V or 24V
+-
*D
*C
Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer
35 mm2 60 mm2 95 mm2 95 mm2 120 mm2 120 mm2
AWG 1 AWG OO AWG OOO AWG OOOO AWG OOOO 2 x AWG OOOO
25 mm2 25 mm2 35 mm2 35 mm2 50 mm2 50 mm2
AWG 4 AWG 4 AWG 2 AWG 2 AWG 1 AWG 1
Min.Batte ry
CCA by Din
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
250 CCA Din
475 CCA SAE
200 CCA Din
380 CCA SA E
400 CCA Din
760 CCA SAE
350 CCA Din
665 CCA SAE
Min.Battery
CCA by Din
12 V 330 A Din
627 A SAE
350 CCA Din
665 CCA SAE
24 V 160 A Din
304 A SAE
200 CCA Din
380 CCA SAE
SP55S2i
IP
Min. Cable
dim e ns ion
Min.Battery
CCA by Din
350 CCA Din
665 CCA SAE
400 CCA Din
760 CCA SAE
400 CCA Din
760 CCA SA E
Min.Batte ry
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
16 - 19m total + & - 20 - 23m total + & - 24 - 27m total + & -
Model Voltage Curre nt
draw
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Table for selection of main cable,
battery, fuse and main-switch
sizes.
up to 7m total + & - 8 - 11m total + & - 12 - 15m total + & -
9
SP55S2i ignition protected thruster assembly
1.1 - 2006
•Explanation of electrical table
- All cable lengths are the total of + and - (to and from).
- Battery size is stated as minimum cold crank capacity, not Ah.
- Use slow fuse rated to hold stated Amp-Draw for min. 5 minutes.
* Cable size and main battery size when an extra bow battery with minimum the CCA mentioned as A is installed.
•It is important that you use a good cable size and batteries with a high cranking capacity to feed the thruster, because it is the actual
voltage at the motor while running the thruster that decides the output rpm of the motor and thereby the actual thrust. Please see the list
below for advised min. sizes of cables and batteries. You can of course use larger cables for even better results.
•A main switch (*C) that can take the load without noticable voltage drop must be installed in the main positive lead so the power for the
thruster can be turned off independently of the rest of the system when not on board or in emergencies. This should be placed in an easily
accessible place and the boats instructions should include information that this should be turned off like the other main switches of the boat.
•We also advice to install a fuse (*D) in the positive lead for protection agains short circuiting of the main cables. This fuse should be of a
adequate quality which normally means that it is physically large as these have less voltage drop than the simple / small ones. It should
be of the slow type and sized to take the amperage draw for atleast 5 minutes.
•Remember to use ignition protected fuses and switches if fitted in areas that require this feature.
•A circuit breaker can be used instead of the fuse and main power switch as long as the functionality is the same.
•The cable ends must be fitted with terminals and these must be well isolated against contact with anything but the proper connection point.
•If the main switch and fuse are installed in the same gas area they also have to be ignition protected.
•The negative / minus cable connects to the (-) terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
•The positive / plus cable connects to the "+" terminal. Bolt M10. Tighten with 25 Nm / 18,43 lb/ft.
Electrical installation
Battery
12V or 24V
+-
*D
*C
Counter Nut
Nut
Washer
Cable terminal
Washer
Counter Nut
Nut
Washer
35 mm2 60 mm2 95 mm2 95 mm2 120 mm2 120 mm2
AWG 1 AWG OO AWG OOO AWG OOOO AWG OOOO 2 x AWG OOOO
25 mm2 25 mm2 35 mm2 35 mm2 50 mm2 50 mm2
AWG 4 AWG 4 AWG 2 AWG 2 AWG 1 AWG 1
Min.Batte ry
CCA by Din
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
200 CCA Din
380 CCA SAE
250 CCA Din
475 CCA SAE
200 CCA Din
380 CCA SA E
400 CCA Din
760 CCA SAE
350 CCA Din
665 CCA SAE
Min.Battery
CCA by Din
12 V 330 A Din
627 A SAE
350 CCA Din
665 CCA SAE
24 V 160 A Din
304 A SAE
200 CCA Din
380 CCA SAE
SP55S2i
IP
Min. Cable
dim e ns ion
Min.Battery
CCA by Din
350 CCA Din
665 CCA SAE
400 CCA Din
760 CCA SAE
400 CCA Din
760 CCA SA E
Min.Batte ry
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
16 - 19m total + & - 20 - 23m total + & - 24 - 27m total + & -
Model Voltage Curre nt
draw
Min. Cable
dim e ns ion
Min.Battery
CCA by DIN
Min. Cable
dim e ns ion
Min. Cable
dim e ns ion
Table for selection of main cable,
battery, fuse and main-switch
sizes.
up to 7m total + & - 8 - 11m total + & - 12 - 15m total + & -
RED:
+
BLACK: -