Lightolier MDCGWSVA2SB4SB User manual

Type
User manual

Lightolier MDCGWSVA2SB4SB is a multi-function patient lighting system that provides indirect ambient light, direct reading light, examination light, and optional night light. It can be installed as a recessed or surface-mounted unit and meets NYC Code requirements. The unit has six twin tube T5 lamps that are accessible for relamping without tools. The optional low voltage electronic sequential switch can be mounted in the fixture for ambient and reading light controlled with a pillow speaker (optional by others). The optional night light is a 7/9 watt PL.

The ambient light provides indirect illumination from twin tube T5 lamps shielded by a perforated mesh shield with a white acrylic overlay. It provides no direct glare to the patient, their visitors, or adjacent patients.

Lightolier MDCGWSVA2SB4SB is a multi-function patient lighting system that provides indirect ambient light, direct reading light, examination light, and optional night light. It can be installed as a recessed or surface-mounted unit and meets NYC Code requirements. The unit has six twin tube T5 lamps that are accessible for relamping without tools. The optional low voltage electronic sequential switch can be mounted in the fixture for ambient and reading light controlled with a pillow speaker (optional by others). The optional night light is a 7/9 watt PL.

The ambient light provides indirect illumination from twin tube T5 lamps shielded by a perforated mesh shield with a white acrylic overlay. It provides no direct glare to the patient, their visitors, or adjacent patients.

Features
Four integral lighting functions: indirect ambient, direct reading,
examination and optional night light.
Precise light control for glare free patient environment.
Installs as a one-piece unit.
Recessed or surface mounted to ceiling which eliminates damage to
fixture from hospital equipment attached to bed.
6-7/8" deep.
All lamps are shielded.
All twin tube T5 lamps are accessible for relamping without tools.
All ballasts accessible thru louver compartment.
Optional low voltage electronic sequential switch mounted in fixture
for ambient and reading light controlled with pillow speaker
(optional by others).
Optional night light.
Meets NYC Code requirements. Chicago Plenum requirements
available.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
6/07
MD
*
Coffer 2' x 4' Recessed or Surface MDCGWSVA2SB4SB
Page 1 of 4 Multi-Function Patient Lighting
Indirect Ambient Light with Perforated Mesh Shield
Lightolier a Genlyte company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2007 a Genlyte company
Section 8/Folio R40-21 Rev. A
Wall
12" - 18"
from wall
Ceiling
9'6" max.
mounting
height
S
surface
Mount
G
Exposed T-grid ceiling
12" - 18"
from wall
Wall angle
or T-bar
(by others)
Wall
Accoustical tile
(by others)
T-bar
(by others)
48"
9'-6" max.
ceiling
height
Secure fixture
(4 places)
Accoustical tile
(by others)
Mount
Mounting Methods Dimensions
1. Reading light with low iridescence anodized semi-specular aluminum reflector.
2. Perforated mesh lamp shield with white acrylic overlay.
3. Ambient light with flat white reflector (flat white interior).
4. Examination light with 36 (6x6) cell flat white baked enamel louver.
5. Prismatic virgin acrylic overlay.
6. Twin tube T5 lamps (6).
7. Optional night light 7/9 watt PL.
8. Ballast compartment accessible by opening louver and reflector.
2" x 3" access plate with (2) 7/8"
dia. K.O.s (Ambient/Reading)
2" x 3" access plate with (2) 7/8"
dia. K.O.s (Examination)
Tabs for wire
supports
(4 places)
Mounting holes (8)
11-7/8"
11-7/8"
14"
4-7/8"
2-1/32"
19-11/16" 19-11/16"
4-5/16"
47-3/4"
2-1/32"
23-3/4"
12-3/4"
4"
1
2
3
4
5
6
7
48" (1219mm)
6-7/8"
(175mm)
8
MD
*
Coffer 2' x 4' Recessed or Surface MDCGWSVA2SB4SB
Page 2 of 4 Multi-Function Patient Lighting
Indirect Ambient Light with Perforated Mesh Shield
3"
6"
12"
Wall
Bed
FOOTCANDLES ON BED
FOOTCANDLES ON BED
12"
Ambient Light
Indirect illumination from twin tube T5 shielded by perforated mesh shield with white acrylic overlay.
No direct glare to patient.
No direct glare to patient's visitor.
No direct glare to adjacent patients.
Lighted
Zone
14 15 15 14 12 12 7
14 16 16 14 12 12 8
14 15 15 14 12 12 7
3"
6"
12"
Wall
Bed
12"
Reading Light
Eliminates reflected glare from reading material (over shoulder illumination).
No direct glare to patient or visitors.
Controls light directly onto patient's bed.
17 21 23 28 33 6 5
18 22 24 29 35 6 5
17 21 23 28 33 6 5
3"
6"
12"
Wall
Bed
12"
Lighted
Zone
68 85 93 99 100 65 49
(31) (36) (38) (42) (45) (18) (12)
73 89 99 104 106 68 53
(32) (38) (40) (43) (47) (18) (13)
68 85 93 99 100 65 49
(31) (36) (38) (42) (45) (18) (12)
Lighted
Zone
Illumination at the
reading task ranges
45-50 footcandles.
F
OOTCANDLES ON BED
Totals of ambient, reading and examination lights.
Numbers in parenthesis ( ) are total footcandle level of ambient and reading lights only.
Examination Light
Excellent color rendition.
Wired for independent switching (1 or 2 circuit).
Optional louver or lens frame.
Concealed hinging and latching.
MD
*
Coffer 2' x 4' Recessed or Surface MDCGWSVA2SB4SB
Page 3 of 4 Multi-Function Patient Lighting
Indirect Ambient Light with Perforated Mesh Shield
3"
6"
12"
Wall
Bed
12"
Night Light (Optional)
Indirect 9 or 7 watt PL lamp shielded by perforated mesh
with internal white acrylic overlay
.
No glare to any patient.
Wired for independent switching.
Options
3433221
3433221
3433221
Pillow speaker (by others)
FOOTCANDLES ON BED
PL9 or PL7 Night Light. Suffix: PL
(Lamps not included)
Night Light
MD
*
Coffer’s optional low voltage (1-3 volts) sequential switch mounted in the fixture is listed in
compliance with UL 544 for medical and dental equipment. Two red wires coming from the fixture
can be wired to a wall receptacle (by others) for use with that manufacturer's pillow speaker. The
pillow speaker is used to control the television, call the nurse and control the lighting. To control
the lighting it should be specified to have a normally open contact switch.
Pressing this switch on the pillow speaker the first time, turns the ambient light on; pressed a
second time, turns the reading light on and the ambient light off; pressed a third time, turns both
the ambient and reading lights on; pressed a fourth time turns both lights off. Pressing the button
again repeats the cycle.
Should the patient's bed be rolled away from the wall, the pillow speaker will simply pull free
from the wall receptacle avoiding any damage.
TAMPER RESISTANT/GERM SHIELD
Germ Shield: Ideal for psychiatric war
ds and
germ free environments. Fits lay-in grid
ceiling systems with 15/16" maximum ceiling tee
face. The heavy duty welded extruded aluminum
frame with clear 1/8" thick polycarbonate lens is
fixture to ceiling system sealed with a heavy duty
gasket. Request Folio R40-15 REV. A.
Ballast Compartment accessible by opening
Louver and reflector
Tamper Resistant/Germ Shield
Sequential Switch. Suffix: SW
MD
*
Coffer 2' x 4' Recessed or Surface MDCGWSVA2SB4SB
Page 4 of 4 Multi-Function Patient Lighting
Indirect Ambient Light with Perforated Mesh Shield
Job Information Type:
Lightolier a Genlyte company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2007 a Genlyte company
Section 8/Folio R40-21 Rev. A
ORDERING INFORMATION
Explanation of Catalog Number. Example: MDCGWSVA2SB4SB120SW
MDC
MD*C
Indirect/
Direct
Recessed or
Surface,
Multi-function
Patient Light
with Perforated
Mesh Shield
G
Ceiling
Type:
Same Unit
May Be Used
For: Grid (lay-in)
Or: Surface
Mounted
2
Lamp
Quantity:
(Ambient/
Reading)
2 Lamps
(Total)
Specifications:
Materials: Chassis parts are die-formed 20 gauge steel. Louver (examination
light) – aluminum post painted white acrylic.
Reading light low iridescence anodized 95% reflective, semi-specular
reflector.
Ambient light flat white acrylic contoured steel reflector and perforated
steel mesh shield with white acrylic overlay.
Finish: Cavity (examination/reading/ambient lights) — flat white acrylic
interior, minimum reflectance 86%. Phosphate undercoating. Chassis
exterior post painted white baked polyester powder. Louver (examination
light) W=flat white baked enamel 36 cell louver with a virgin acrylic overlay to
enclose all lamps. VA=.095" nominal thickness prismatic virgin acrylic overlay.
VI=.125" nominal thickness, pattern 12 acrylic lens.
Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If
K.O. is within 3" of ballast, use wire suitable for at least 90°.
Specifications (continued):
Labels: I.B.E.W. UL and ULc Listed.
This product may have a mercury containing lamp. Manage in accord with
Disposal Laws. See: www.lamprecycle.org
Options/Accessories
Access Plates: Top wiring access plate is shipped with fixture as standard.
When access plates are required in advance for wiring convenience, specify
separately. Catalog Number: ACP.
Drywall Kit: Order Catalog Number: FK92X4.
Request Folio OA30-10 Rev. A.
Electronic Sequential Switch (Low Voltage): Switch factory mounted in fix-
ture for ambient and reading light convenience (controlled by pillow switch, by
others). Suffix: SW.
Individual Switching (Low Voltage): Switches mounted to patient's bed for
use with manufacturer's control system (such as Hill-Rom Side Com).
Suffix: DP.
9/7 Watt Night Light: Suffix: PL (Lamp not included).
Fusing: Internal fast-blow fusing. Suffix: GLR.
Internal slow-blow fusing. Suffix: GMF.
Radio Interference Filter:
To order one RIF per fixture; Suffix: R. To order one RIF
per ballast; Suffix: B.
Germ Shield. Order Catalog Number: MD4CLGS24.
Electrical/Wiring Options: Consult factory
.
Louver
Overlay/Lens:
VA = Virgin Acrylic
.095" Nominal
Thickness
Overlay
(standard)
V
I = .125" Thick
Pattern 12
Acrylic Lens.
Ballast Type:
(Ambient Reading)
<20THD <10THD
1-2 Lamp Elec. TT5 SB* IB**
(40 Watt)
1-2 Lamp Elec. TT5
PR**
(40 Watt)
LOL Dimming TT5 PB
**Instant Start Standard
**Program Start
NOTE:
For TT5 UNV, you must use IB Ballast
Code
Louver/
Lens Frame:
WS = White Louver
RF = Regressed
Floating Extruded
Aluminum Door
Frame
Lamp
Quantity
3 = 3 Lamp
4 = 4 Lamp
Options:
Add appropriate
Suffix to Catalog
No. i.e. (GLR)
Ballast Type:
(Examination)
<20THD <10THD
1-3 Lamp Elec. TT5 X3* I3**
2-2 Lamp Elec. TT5 SB* IB**
2-2 Lamp Elec. TT5 PR**
(40 Watt)*
LOL Dimming TT5 PB*
**Instant Start Standar
d
**Program Start
NOTE:
For TT5 UNV, you must use IB Ballast
Code
Voltage:
120 or 277
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Lightolier MDCGWSVA2SB4SB User manual

Type
User manual

Lightolier MDCGWSVA2SB4SB is a multi-function patient lighting system that provides indirect ambient light, direct reading light, examination light, and optional night light. It can be installed as a recessed or surface-mounted unit and meets NYC Code requirements. The unit has six twin tube T5 lamps that are accessible for relamping without tools. The optional low voltage electronic sequential switch can be mounted in the fixture for ambient and reading light controlled with a pillow speaker (optional by others). The optional night light is a 7/9 watt PL.