ICM Controls ICM492C is a voltage monitor that protects single-phase systems against adverse line voltage conditions like over/under voltage and rapid short cycling. It constantly monitors and displays the line voltage on its backlit digital display. The device features adjustable voltage set points, time delay, over/under voltage percentage, control mode, and response time. It has a 5-fault memory storage and universal control voltage input. The heavy-duty SPDT relay output can be used to directly drive loads or control contactors and relays.

ICM Controls ICM492C is a voltage monitor that protects single-phase systems against adverse line voltage conditions like over/under voltage and rapid short cycling. It constantly monitors and displays the line voltage on its backlit digital display. The device features adjustable voltage set points, time delay, over/under voltage percentage, control mode, and response time. It has a 5-fault memory storage and universal control voltage input. The heavy-duty SPDT relay output can be used to directly drive loads or control contactors and relays.

ICM492
Single Phase Digital Line Voltage Monitor
Reliable protection of single phase systems against adverse line voltage conditions
SPECIFICATIONS
User Adjustable Settings:
•Voltage setpoint:95-280V
•Anti-short cycle time delay:0-720sec.
•Over voltage setting:5-25%
•Under voltage setting:5-25%
•Control mode:OnandOff
•Response time:0.1to10seconds
Inputs:
•Line voltage:80to300VAC
•Control voltage:24to240VAC
•Frequency:50/60Hz
•Accuracy:±2%
•Low power consumption:Max50mA@120V,
Max100mA@240V
Output:
•Type:dryrelaycontacts
•Form:SPDT
•Relay contact ratings:
–N.C. Contacts:10Aresistive@277VAC
–N.O. Contacts:10Aresistive@277VAC
•Connection Terminals:0.25”malefast-on
Mechanical:
•Case dimensions:3”Lx3.2”Wx1.35”H
•Unit weight:0.36lbs.
Environmental:
•Operating temp. range:-30°Cto+70°C
•Storage temp. range:-40°Cto+85°C
•Maximum operating/storage relative humidity:
95%non-condensing
7313 William Barry Blvd., North Syracuse, NY 13212
(Phone) 315-233-5266 (Toll Free) 800-365-5525
(Fax) 315-233-5276
www.icmcontrols.com
LII335-3
Constantly monitors and displays line
voltage. Protects against Over and Under
voltage, and Rapid Short Cycling caused by
Transient Faults and Power Interruptions
TheICM492isspecicallydesignedtomonitorline
voltageandguardsinglephaseequipmentagainst
damagecausedbyunderandoverlinevoltage
conditionsandrapidshortcycling.Recordslastve
faults.
DESCRIPTION
•UniversalLineVoltage
Input
•Easy-viewBacklitDigital
Display
•RMSVoltageMonitoring
•5-faultmemorystorage
•AdjustableVoltageSet
Point
•AdjustableOverVoltage
SetPoint
•AdjustableUnder
VoltageSetPoint
FEATURES
•AdjustableAnti-Short
CycleTimeDelay
•AdjustableResponseon
FaultTime
•ControlMode
•5-FaultMemory
•UniversalControl
VoltageInput
•HeavyDutySPDTRelay
Output
TheICM492continuouslymonitorsincominglinevoltage
forfaultsanddisplaysRMSvoltageonthedigital
display.Whenlinevoltageisappropriate,ICM492closes
theCOMandN.O.relaycontacts.Whenincomingline
voltageisoutsideofuserselectedparameters,ICM492
willclosetheCOMandN.C.relaycontactsandindicate
afaultconditionbyashingFAULTondisplay.Theunit
recordsthelastvefaults,storingthehighestandlowest
voltagereadingsthatcausedthefault.TheUP,DOWN
andSELECTbuttonsarepressedsimultaneouslyto
clearthefaultsfrommemory.TheSELECTmenuhas
thefollowinguseradjustablesettings:voltagesetpoint,
timedelay,overvoltagepercentage,undervoltage
percentage,controlmode,andresponsetime.Time
delaypreventsshortcyclingwhenfaultnolongeris
presentandrapidpowerinterruptions.Theresponse
timeonthefaultconditioncanbeadjustedtohelp
reducenuisancetripsfromtransientfaults.When
ControlModesettingisselectedONthenICM492will
closeCOMandN.O.relaycontactsonlywhencontrol
voltageispresentatControlVoltageterminalsandthe
linevoltageisgood.Therelaycontactscanbeused
todirectdrivetheloadaslongascurrentratingisnot
exceeded.
MODE OF OPERATION
!!! WARNING !!!
ElectricalShockHazard
• Verify power is disconnected by removing a fuse
or opening a circuit breaker before making any
connections.
This control should be installed by a trained technician.
• Incorrect installation can cause personal injuries,
property damage or death.
• Follow all local & national codes while installing control.
!!! DANGER !!!
Verify power is disconnected by removing a fuse or opening a circuit breaker before making
any connections or injury or death can result.
1. Disconnectpower.
2. MountICM492securelyagainstthemetalchaisesofthesysteminawaterproofenvironment.
3. Ifacontactororarelayisusedinthesystem(seeFig.1)tocontrolpowertotheloadthen:
 a. MakeL1andL2connections.
 b. Cutthewirethatpowersthecontactor/relaycoil,stripandplace1/4”femalespadeterminalsonthem.
 c. PlugfemalespadeterminalsonCOMandN.O.terminalsofICM492.
4. Shouldyouchoosetodrivetheloaddirectly(seeFig.2)usingrelaycontactsofICM492then:
 a. MakesurethatloadcurrentratingdoesnotexceedcurrentratingofICM492relaycontacts.
 b. Cutthelinethatpowerstheload,stripandplace1/4”femalespadeterminalsonthem.
 c. PlugfemalespadeterminalsonCOMandN.O.terminalsofICM492.
5. ShouldyouchoosetouseacontrolsignalatControlVoltageinputterminalsthen:
 a. Usetwowireswith1/4”femalespadeterminalsonthemtoplugonControlVoltageterminalsofICM492.
 b. Tapintocontrolsignalwiththeotherendofthewires.
6. PressSELECTbuttontoentertheselectmenu.
a. UseUpandDownarrowstoadjustfeaturesettings.
b. MakesurethattheControlModeisONifthecontrolsignalisusedatControlVoltageterminals.
INSTALLATION
WIRING DIAGRAMS
Figure 1 Figure 2
Motor
*Notnecessarybutrecommended1Ampfuse.
PressSELECTtoentermenusetup
• VOLTAGESETPOINTdisplays(95–280VAC)
• Adjustthistomatchthevoltageofyoursystem.
• Useupordownbuttontoadjust.
PressSELECTfornextscreen
• TIMEDELAY(Lockout)displays(1-720seconds)
• Thisistheamountoftimeyoursystemwillbelocked
outafterafault.
• Useupordownbuttontoadjust.
PressSELECTfornextscreen
• OVERVOLTPERCENTAGEdisplays(5-25%)
• Thisisthepercenttheactualvoltagemustbeabove
yourSetVoltageforanoverfaulttooccur.
• Useupordownbuttontoadjust.
PressSELECTfornextscreen
• UNDERVOLTPERCENTAGEdisplays(5-25%)
• Thisisthepercenttheactualvoltagemustbebelow
yourSetVoltageforanunderfaulttooccur.
• Useupordownbuttontoadjust.
SELECT MENU SETUP
PressSELECTfornextscreen
• CONTROLMODEdisplays(OFF-ON)
• WhensettoON,therelaycontactscloseonlywhen
linevoltageconditionsaregoodandvoltageis
presentattheControlVoltageterminals.
• Useupordownbuttontoadjust.
PressSELECTfornextscreen
• RESPONSETIMEdisplays(.01-10seconds)
• Thisistheamountoftimethefaultconditionmust
existbeforeyoursystemisturnedoff.
• Useupordownbuttontoadjust.
PressSELECTfornextscreen
• FAULT1-5displays
• Thisisthevoltageofthefaultthathasoccurred.
• –––Indicatesnofaultisinmemory
NOTE:Faults can be cleared by simultaneously
pressing the UP, DOWN and SELECT buttons
after exiting SELECT Menu Setup.
After15secondsofbuttoninactivity,thecontrolexits
SELECTMenuSetupscreen.
  • Page 1 1
  • Page 2 2

ICM Controls ICM492C Installation guide

Type
Installation guide

ICM Controls ICM492C is a voltage monitor that protects single-phase systems against adverse line voltage conditions like over/under voltage and rapid short cycling. It constantly monitors and displays the line voltage on its backlit digital display. The device features adjustable voltage set points, time delay, over/under voltage percentage, control mode, and response time. It has a 5-fault memory storage and universal control voltage input. The heavy-duty SPDT relay output can be used to directly drive loads or control contactors and relays.