Vacon VACON® NXP GridConvGGC ARFIF106V103 User guide

Type
User guide

This manual is also suitable for

vacon
Ā®
nx
ac drives
arfif106
Grid Converter
with General Grid Codes
Application manual
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 3
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Table of contents
Document: DPD01978A
Software code: ARFIF106V107
Version release date: 3.10.2019
1. General .......................................................................................................................... 8
1.1 AFE Control ............................................................................................................................... 8
1.2 Island (Static Power Supply) .................................................................................................... 8
1.3 Micro Grid.................................................................................................................................. 9
1.3.1 Operation principle: Droop Speed Control Mode ..................................................... 10
1.3.2 Operation principle: Isochronous Speed Control Mode .......................................... 10
1.4 Commissioning ....................................................................................................................... 11
1.4.1 Quick start instructions ............................................................................................. 11
1.4.2 In case of parallel AFE: .............................................................................................. 11
1.5 Pre-Charging of DC ................................................................................................................ 13
1.6 Main circuit breaker control (MCB) ....................................................................................... 14
1.7 Start Sequence ....................................................................................................................... 15
1.8 Stop sequence ........................................................................................................................ 16
1.9 Start Stop timing diagram ..................................................................................................... 17
1.10 Start Stop Timing Diagram with Grid Codes......................................................................... 18
1.11 Voltage compensation ............................................................................................................ 19
1.12 OPT-D7 .................................................................................................................................... 20
1.13 Compatibility issues in parameters between versions ........................................................ 21
2. Control I/O .................................................................................................................... 22
3. Monitoring signals ......................................................................................................... 23
3.1 Monitoring value tables.......................................................................................................... 23
3.1.1 Monitoring values 1 (Control panel: menu M1.1) ..................................................... 23
3.1.2 Monitoring values 2 (Control panel: menu M1.2) ..................................................... 24
3.1.3 Fieldbus monitoring values (Control panel: menu M1.3) ...................................... 24
3.1.4 I/O monitoring values (Control panel: menu M1.4) ................................................ 25
3.1.5 Licence key activation ................................................................................................ 25
3.1.6 Grid Code .................................................................................................................... 25
3.1.7 PI Power Controller ................................................................................................... 25
3.1.8 Active Limits ............................................................................................................... 26
3.1.9 Line Monitoring .......................................................................................................... 26
3.2 Description of monitoring values .......................................................................................... 27
3.2.1 Monitoring 1 values .................................................................................................... 27
3.2.2 Monitoring 2 values .................................................................................................... 30
3.2.3 Fieldbus monitoring values ....................................................................................... 33
3.2.4 I/O monitoring values ................................................................................................. 39
3.2.5 Activation status ......................................................................................................... 41
3.2.6 Grid Code .................................................................................................................... 42
3.2.7 PI Power Controller ................................................................................................... 45
3.2.8 Active Limits ............................................................................................................... 45
3.2.9 Line Monitoring .......................................................................................................... 45
4 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4. Parameter list ............................................................................................................... 46
4.1 Basic parameters ................................................................................................................... 46
4.2 Reference handling ................................................................................................................ 46
4.2.1 DC Reference ............................................................................................................. 47
4.2.2 Power / Frequency reference ................................................................................... 47
4.2.3 PID Power Controller for AFE ................................................................................... 47
4.2.4 Reference adjust ........................................................................................................ 48
4.2.5 AC voltage reference ................................................................................................. 48
4.3 Ramp control .......................................................................................................................... 48
4.4 Input signals ........................................................................................................................... 49
4.4.1 Basic settings ............................................................................................................. 49
4.4.2 Digital inputs .............................................................................................................. 50
4.4.3 Analogue input 1 ........................................................................................................ 51
4.4.4 Analogue input 2 ........................................................................................................ 51
4.4.5 Analogue input 3 ........................................................................................................ 52
4.4.6 Analogue input 4 ........................................................................................................ 52
4.5 Output signals ......................................................................................................................... 53
4.5.1 Digital output signals ................................................................................................. 53
4.5.2 Delayed DO 1 .............................................................................................................. 54
4.5.3 Delayed DO 2 .............................................................................................................. 54
4.5.4 Analogue output 1 ...................................................................................................... 55
4.5.5 Analogue output 2 ...................................................................................................... 56
4.5.6 Analogue output 3 ...................................................................................................... 57
4.5.7 Options ........................................................................................................................ 57
4.6 Limit settings .......................................................................................................................... 58
4.6.1 Current limit ............................................................................................................... 58
4.6.2 Power limit ................................................................................................................. 58
4.6.3 Frequency limit .......................................................................................................... 58
4.6.4 Micro Grid ................................................................................................................... 58
4.6.5 DC voltage ................................................................................................................... 59
4.7 Drive control ........................................................................................................................... 59
4.7.1 AFE control ................................................................................................................. 59
4.7.2 Identification ............................................................................................................... 59
4.8 Protections .............................................................................................................................. 61
4.8.1 General ....................................................................................................................... 61
4.8.2 PT-100 ......................................................................................................................... 61
4.8.3 Earth fault ................................................................................................................... 62
4.8.4 Fieldbus fault .............................................................................................................. 62
4.8.5 External fault .............................................................................................................. 62
4.8.6 Grid voltage D7 ........................................................................................................... 63
4.8.7 Grid frequency ............................................................................................................ 63
4.8.8 Supply Voltage ............................................................................................................ 63
4.8.9 Over Load .................................................................................................................... 64
4.8.10 opt-d7 protections ...................................................................................................... 64
4.8.11 Extra ............................................................................................................................ 64
4.9 Fieldbus ................................................................................................................................... 65
4.10 Micro Grid................................................................................................................................ 67
4.11 Synchronisation to external grid ........................................................................................... 68
4.12 Reserved ................................................................................................................................. 68
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 5
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4.13 ID control functions ................................................................................................................ 69
4.13.1 Value control .............................................................................................................. 69
4.13.2 DIN ID control 1 .......................................................................................................... 69
4.13.3 DIN ID control 2 .......................................................................................................... 69
4.13.4 DIN ID control 3 .......................................................................................................... 70
4.13.5 DIN ID control 4 .......................................................................................................... 70
4.13.6 ID Controlled Digital Output 1 ................................................................................... 70
4.13.7 ID Controlled Digital Output 1 ................................................................................... 70
4.14 Auto reset ................................................................................................................................ 70
4.15 Grid voltage PI ........................................................................................................................ 71
4.16 Grid Code parameters ............................................................................................................ 72
4.16.1 Anti-islanding ............................................................................................................. 72
4.16.2 FRT .............................................................................................................................. 72
4.16.3 Reconnection .............................................................................................................. 72
4.16.4 Line Voltage ................................................................................................................ 73
4.16.5 Line Frequency ........................................................................................................... 73
4.16.6 FRT Timer ................................................................................................................... 74
4.16.7 Line OK Limits ............................................................................................................ 74
4.16.8 Reactive Injection ....................................................................................................... 75
4.16.8.1 Linear UV ................................................................................................................................... 75
4.16.8.2 Linear OV ................................................................................................................................... 75
4.16.8.3 Power Lock UV ........................................................................................................................... 75
4.16.8.4 Power Lock OV ........................................................................................................................... 75
4.16.8.5 Q(U) Power ................................................................................................................................ 76
4.16.8.6 Q(U) Curve ................................................................................................................................. 76
4.16.9 Power Limit/Reference.............................................................................................. 76
4.16.9.1 High Frequency .......................................................................................................................... 76
4.16.9.2 High Voltage............................................................................................................................... 77
4.16.9.3 Low Voltage Charge Limit ........................................................................................................... 77
4.16.9.4 Low Frequency Charge Limit ....................................................................................................... 77
4.16.9.5 Low Frequency Power Increase .................................................................................................. 77
4.16.10 Cos Phii Control.......................................................................................................... 78
4.16.10.1 Voltage Log In Log Out................................................................................................................ 78
4.16.10.2 Active Current ............................................................................................................................ 78
4.16.11 External Input ............................................................................................................. 78
4.16.12 Options ........................................................................................................................ 78
4.17 Keypad control (Control panel: menu M3) ............................................................................ 79
4.18 System menu (Control panel: menu M6) .............................................................................. 79
4.19 Expander boards (Control panel: menu M7) ........................................................................ 79
5. Description of parameters ............................................................................................. 80
5.1 Basic parameters ................................................................................................................... 80
5.1.1 Transformer parameters .......................................................................................... 82
5.2 Reference handling ................................................................................................................ 83
5.2.1 DC Reference Tuning ................................................................................................. 84
5.2.2 Power /frequency reference ..................................................................................... 85
5.2.3 PID Power Controller ................................................................................................. 89
5.2.4 Reference adjust functions........................................................................................ 90
5.2.5 AC Voltage Reference ................................................................................................ 91
5.3 Ramp control .......................................................................................................................... 95
6 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.4 Input signals ........................................................................................................................... 96
5.4.1 Basic settings ............................................................................................................. 96
5.4.2 Digital input signals ................................................................................................... 98
5.4.2.1 Synchronization to external grid ................................................................................................. 99
5.4.2.2 Forced control place ................................................................................................................. 101
5.4.3 Analogue inputs 1-4 ................................................................................................. 103
5.4.3.1 Analogue input to any parameter ............................................................................................. 105
5.5 Output signals ....................................................................................................................... 106
5.5.1 Digital output signals ............................................................................................... 106
5.5.1.1 Fieldbus digital inputs connection............................................................................................. 107
5.5.2 Delayed digital output 1 & 2 .................................................................................... 108
5.5.3 Analogue output 1 & 2 & 3 ....................................................................................... 109
5.5.4 Options ...................................................................................................................... 112
5.6 Limit settings ........................................................................................................................ 114
5.6.1 Current limits ........................................................................................................... 114
5.6.2 Power limits.............................................................................................................. 117
5.6.3 Frequency limits....................................................................................................... 118
5.6.4 Micro Grid limits ....................................................................................................... 119
5.6.5 DC voltage regulators .............................................................................................. 120
5.7 Drive control ......................................................................................................................... 122
5.7.1 AFE Control .............................................................................................................. 125
5.7.2 Identification ............................................................................................................. 126
5.7.3 DC-Link Compensation ............................................................................................ 126
5.8 Protections ............................................................................................................................ 127
5.8.1 General settings ....................................................................................................... 127
5.8.2 PT-100 ....................................................................................................................... 130
5.8.2.1 Individual channel monitoring .................................................................................................. 131
5.8.3 Earth fault ................................................................................................................. 132
5.8.4 Fieldbus .................................................................................................................... 132
5.8.5 External fault ............................................................................................................ 132
5.8.6 Grid voltage D7 ......................................................................................................... 133
5.8.7 Grid frequency .......................................................................................................... 135
5.8.8 Supply voltage .......................................................................................................... 136
5.8.9 Over Load Protection ............................................................................................... 138
5.8.10 D7 protections .......................................................................................................... 139
5.8.11 Extra .......................................................................................................................... 140
5.9 Fieldbus ................................................................................................................................. 141
5.10 Micro Grid.............................................................................................................................. 144
5.10.1.1 Generator Simulation ............................................................................................................... 146
5.10.1.2 AFE operation mode selection .................................................................................................. 147
5.11 Synch to external grid .......................................................................................................... 148
5.12 Reserved ............................................................................................................................... 149
5.13 ID functions ........................................................................................................................... 150
5.13.1 Value control ............................................................................................................ 150
5.13.2 DIN ID control ........................................................................................................... 152
5.13.3 ID Controlled Digital Output .................................................................................... 153
5.14 Auto Reset ............................................................................................................................. 154
5.15 Grid voltage PI controller ..................................................................................................... 155
5.15.1 Grid voltage PI OPT-D7 limits ................................................................................. 155
5.16 Grid Code parameters .......................................................................................................... 156
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 7
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5.16.1 Anti-Islanding ........................................................................................................... 157
5.16.2 FRT ............................................................................................................................ 158
5.16.3 Reconnection ............................................................................................................ 159
5.16.4 Line Voltage .............................................................................................................. 160
5.16.5 Line Frequency ......................................................................................................... 164
5.16.6 FRT Timer ................................................................................................................. 167
5.16.7 Line OK Limits .......................................................................................................... 168
5.16.8 Reactive Injection ..................................................................................................... 169
5.16.8.1 Linear reference under voltage ................................................................................................. 170
5.16.8.2 Linear reference over voltage ................................................................................................... 171
5.16.8.3 Power Lock In and Out Reference under voltage. ...................................................................... 172
5.16.8.4 Power Lock In and Out Reference over voltage. ........................................................................ 174
5.16.8.5 Q(U) Power .............................................................................................................................. 176
5.16.8.6 Q(U) Curve ............................................................................................................................... 177
5.16.9 Power Limit/Reference............................................................................................ 178
5.16.9.1 High Frequency Power Limit ..................................................................................................... 179
5.16.9.2 High Voltage Power Limit ......................................................................................................... 182
5.16.9.3 Low Voltage Charge Limit ......................................................................................................... 184
5.16.9.4 Low Frequency Charge Limit ..................................................................................................... 185
5.16.9.5 Low Frequency Power Reserve ................................................................................................. 187
5.16.10 Cos Phii Control........................................................................................................ 188
5.16.10.1 Lock In and Out control ............................................................................................................ 189
5.16.10.2 Cos Phii Active Current Control ................................................................................................. 190
5.16.11 External Input ........................................................................................................... 191
5.16.12 Grid Code Options .................................................................................................... 192
6. Keypad control parameters ......................................................................................... 194
7. FB Status and control in detail ..................................................................................... 195
7.1 FB DC Reference .................................................................................................................. 195
7.2 State machine: Basic............................................................................................................ 195
7.2.1 FB Control Word Basic ............................................................................................ 195
7.3 State Machine: Standard ...................................................................................................... 196
7.3.1 Control Word: Standard ........................................................................................... 196
7.4 State machine: Vacon AFE 1 ................................................................................................ 197
7.4.1 Control Word: Vacon AFE 1 ..................................................................................... 197
7.5 FB Status Word ..................................................................................................................... 198
8. Problem solving .......................................................................................................... 200
9. Fault codes ................................................................................................................. 201
8 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1. General
This application is not kept backwards compatible. See chapter Compatibility issues before you
update the application. The Grid Converter application is used to make AC grids with a possibility to
operate in parallel with other power sources. The Grid Converter application has 3 different
operation modes:
- Standard AFE mode.
- Island mode.
- Micro Grid mode.
1.1 AFE Control
AFE function keeps constant DC voltage. AFE mode transfers power between DC and AC. AFE cannot
create grid by itself, it needs to be connected to existing grid.
U2
=
~
Filter
G1
U1
Q2
UDC
Figure 1.
1.2 Island (Static Power Supply)
Island mode generates constant voltage and frequency. In island mode DC Voltage is not controlled.
Island mode cannot operate in parallel with other power sources in AC side, because the drive will
not balance reactive or active power with other power sources.
DC voltage level needs to be considered to have correct voltage on AC side in different load
situations, considering voltage losses in LCL filter and in transformer.
Q1
T2
Grid
U4
U3
U5
=
~
Filter
U4 = Transf. GC Side
U5 = Transf. Grid Side
D7
T1
Q3
Figure 2.
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 9
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.3 Micro Grid
Micro Grid mode controls the grid voltage and frequency. It functions like an ordinary generator.
Micro Grid mode does not control DC Voltage.
With the help of voltage droop and frequency droop, more than one Micro Grid and/or Generators
can work together.
Q1
T2
Ship Grid
=
~
Filter
U4 = Transf. GC Side
U5 = Transf. Grid Side
T1
Q3
Q1
T2
Ship Grid
U4
U3
U5
=
~
Filter
U4 = Transf. GC Side
U5 = Transf. Grid Side
D7
Q3
G1
Q2
U4
U5
U3
T1
D7
Figure 3.
10 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.3.1 Operation principle: Droop Speed Control Mode
When the power demand increases, all generators on the grid allow frequency to droop. This will
balance the load between all the generators on the grid. Then the power management system gives
all generators a command to increase frequency so that the grid frequency is maintained at its
nominal value.
When the load is reducing on the grid, the frequency of the generators will increase, and the power
management system gives a command to decrease frequency.
+1%
+2%
+3%
+4%
-1%
-2%
-3%
-4%
50,5 Hz
51,0 Hz
51,5 Hz
52,0 Hz
48,0 Hz
48,5 Hz
49,0 Hz
49,5 Hz
50,0 Hz
Loading
Un-loading
Drooping
Freq. Change
25% 50% 75% 100%
Related
Load
Figure 4.
1.3.2 Operation principle: Isochronous Speed Control Mode
In the isochronous speed control mode, the Micro Grid frequency reference is kept the same as the
grid frequency with help of OPT-D7. This will keep power at zero regardless of grid frequency. While
drive operates in drooping mode, the actual power is controlled by base current reference. This
reference needs to be controller by power management system (PMS) that will handle power
sharing between different machines on the grid.
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 11
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.4 Commissioning
NOTE! Before you start the commissioning, read the safety instructions in the user manual of your
product.
To use the Island, Micro Grid, or Shaft generator operation, you need a licence key. The AFE mode is
available without a licence.
This application requires an NXP3 control board VB761 or newer.
The control place (P3.1) of the Grid Converter drive is Keypad as a default.
The basic I/O configuration of the Grid Converter drive consists of OPT-A1, OPT-A2, and OPT-D7
option boards. The basic I/O configuration is described in Table 1.
OPT-D7 is required when the Grid Converter unit is needed to start with zero power to the grid. If
grid frequency is not monitored with OPT-D7, the unit may go generator side or directly to full power
because different reference frequency and grid frequency.
The Grid Converter is utilised by using AFE hardware with special software. An external LC(L)-filter
and charging circuit is needed. This unit is selected when low harmonics are required. The principle
connection of AFE drive has been described in Figure 5.
The external 24 Vdc is recommended for control board(s). It enables the setting of parameters even
when the power unit itself is not powered. This is important also when software updates are made.
Some default I/O configuration of the application can cause unexpected DO operation. When the
control board is powered, the drive can give information from the status of the system if, for
example, the drive I/O is used for an overall system monitoring.
The external 24 Vdc is required for the drives in cases where the start command starts the control
board-controlled precharging operation.
1.4.1 Quick start instructions
1. Connect the unit according to the Figure 5.
2. Power up the control unit with 24 Vdc.
3. Set the basic parameters (G2.1)
4. Check that the digital input parameters (G2.4.2) have been set according to the connections.
5. Change the control place according to the system requirements.
6. Charge the unit.
1.4.2 In case of parallel AFE:
1. Set P2.1.5 Parallel AFE to
Yes
. This will also set DC Drooping to 3.00% (Default).
12 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 5.
Connection
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 13
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.5 Pre-Charging of DC
This AFE application has its own charging control, P2.5.1.13 DC Charge (24 Vdc required for control
board) and charging protection in case the external charging cannot get DC voltage to required level
within set time P2.9.1.6 Charge Max Time (provided that the DC Voltage reaches the under voltage
fault level).
The charging function is activated when P2.5.1.13 DC Charge is A.1 or higher. When the control place
is IO, Keypad or NCDrive, charging is started from the start command.
Charging is not started if:
- Drive is in fault state.
- P2.4.2.26 Enable CB Close is FALSE
- P2.4.2.8 Run Enable is FALSE
- P2.4.2.19 Quick Stop is FALSE
Charging is also stopped if above conditions occur during charging or if the start command is
removed.
For fieldbus control, charging is started with B0 of FB Control Word on the supporting FB profiles.
Charging is also stopped if B0 goes low. Also MCB is opened if already closed.
DC Charge (F80) is given if 85 % of DC Nominal is not reached within P2.9.1.6 Charge Max Time and
charging is stopped.
DC Charging is stopped when the drive receives feedback from P2.4.2.4 MCB Feedback.
NOTE! Use suitably sized DC Charging resistor. To select the correct size, check Pulse loadability
for time duration set in for Max Charge Time parameter.
14 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.6 Main circuit breaker control (MCB)
The Micro Grid application controls the circuit breaker of the system with the relay output RO2.
When the DC bus is charged, the MCB will be closed. The status of the MCB is monitored via a digital
input. The digital input used for monitoring is selected with parameter P2.3.1.3. Faults can be set to
open the MCB by selecting a response to a fault to be
3=Fault, DC OFF
.
An external charging circuit is necessary to charge the DC bus but drive can control this circuit if 24
Vdc is provided for the control board.
Closing limit is 85% of the nominal DC Voltage.
Opening limit is 75% of the nominal DC Voltage.
Nominal DC Voltage = Grid Nom Voltage (P2.1.1) * 1.35.
Over Current (F1), Hardware IGBT (F31) and Software IGBT (F41) faults will open MCB immediately
to protect the drive.
NOTE! The MCB feedback is necessary for the correct operation of the Grid Converter application.
NOTE! Only the drive controls its own MCB. If additional interlocks or opening commands are
needed, these commands must go through the drive.
NOTE! UPS may be needed during short circuit situation to keep MCB closed if control voltage is
taken from the grid where the short circuit occurs.
NOTE! Missing feedback signal prevent drive going to ready state.
NOTE! If feedback is not used there will be three second forced delay on internally generated MCB
feedback signal.
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.7 Start Sequence
Ready to switch
on
Charge
DC-Link
DC-Link
> 85 %
NO
Close Main
Contactor
YES
Main Contactor
Closed
YES
NO
MCC Fault
Fault
Reset
Run Enable
Ready To Run
NO
Start Signal
YES
NO
Synchronize with
mains
Synch OK
NO
YES
Line Synch Fault
F10
Running
Start
Figure 6.
AFE start sequence
16 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.8 Stop sequence
Figure 7.
Stop sequence
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 17
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.9 Start Stop timing diagram
DC Voltage
Charge Control
MCB Feedback
MCB Close Control
MCB Close level
Stable DC
Ready
IO Start
Run
FB CW.B00
Control in
FB Control
FB CW.B03
Contro in
IO Control
P. Start Delay
IO MCB Open
Command
ta
is like in IO Control.
18 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.10 Start Stop Timing Diagram with Grid Codes
Main Circuit Breaker
Feedback
Main Circuit Breaker
Close Control
Ready State of
Inverter
Start Request
To Inverter
Run
(Modulating)
Line Frequency
and Voltage OK
P. Line OK Delay
P. Start Delay
Grid Code Trip
P. ReConnect
Time
Start
Synchronization
Start
Synchronization
arfif106 Grid Converter + Grid Codes VACONĀ® Ā· 19
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.11 Voltage compensation
Grid Converter system will have voltage losses. Depending on the system, the losses may be more
than 50 Vac when operating close to Grid Converter nominal currents with low power factor between
points U3 and U5. This voltage loss needs to be compensated so that the grid voltage stays at
nominal. This also sets requirements for the needed DC link voltage.
Q1
T2
Ship Grid
U4
U3
U5
UDCU2
=
~
=
~
Filter
Filter
SG
U1
Q2
U4 = Transf. GC Side
U5 = Transf. Grid Side
D7
T1
Q3
Figure 8.
Voltage compensation
The normal operation voltage range in a land-based grid is usually between 80% and 115% of the
grid nominal voltage.
The voltage losses compensation is handled separately for Active power (kW) and Reactive power
(kVar), the latter being more significant. The Active power voltage losses are compensated with
Inductor Losses parameter (P2.2.6.6) and Reactive power voltage losses are compensated with
Inductor Size parameter (P2.2.6.5).
Uncompensated system may result in unnecessary reactive power circulation in a grid between the
different power sources and wrong grid voltage.
OPT-D7 can be used to compensate the voltage losses (closed loop voltage compensation) but it is
recommended to do an open loop voltage compensation tuning in case of OPT-D7 failure. When the
OPT-D7 measurements exceed the set limit values, the voltage compensation falls back to open loop
control.
Inductor Size and Losses affect
Grid Nom. Voltage: 400 Vac, Reactive Current: 30%, Active Current 50%, Inductor
Size: 15%, Inductor Losses: 15%, Voltage Correction: 0 Vac.
Reactive Increase: 400 VacƗ30%Ɨ15%=18 Vac
Active Increase: 400 VacIncrease:ī—·or Losses: 15% 400 VacƗ50%Ɨ15%Ɨ15%=4.5 Vac
Total increase: 18 Vac+4.5 Vac =22.5 Vac
See also document: Voltage Compensation Vxxx.pdf.
20 Ā· VACONĀ® arfif106 Grid Converter + Grid Codes
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1.12 OPT-D7
OPTD7 is an AC sinusoidal voltage measurement board. Using this board, the drive measures the
line voltage, the frequency and the voltage angle information.
The drive can compare this information with its output voltage angle when it runs. This feature can
be used to make synchronisations to a grid that is measured. For example, for line synchronisation
purposes you can use APFIFF44 LineSynch II Application. That will work as a smooth starter.
In Micro Grid application this can be used:
- To synchronise to existing external grid while the drive is running to enable bumpless
transfer from a generator operation to a shore powered operation in a ship.
- To control the grid voltage (Voltage losses compensation).
- To enable a zero power connection to an existing grid.
- To help in the commissioning of drive active power and reactive power voltage losses
compensation when the actual grid voltage is visible in NCDrive.
The OPT-D7 board is delivered with the transformer which is suitable for a voltage range up to 690
Vac. The transformer cannot be used with a pulse width modulated (PWM) voltage input.
It is possible to use a customised transformer when the input voltage to be measured is not within
the OPT-D7 transformer voltage range. The transformation ratio parameter can be adjusted
according to the transformer primary to secondary ratio. See details in the OPT-D7 user manual.
Synchronisation to the grid can be made without the OPT-D7 when the drive operates in the AFE or
the Micro Grid mode. This requires that the output terminals of the drive are connected to the
existing grid when the drive is in the STOP state. When a start command has been given in AFE or
Micro Grid mode, the drive will make standard AFE synchronisation. Depending on the operation
mode, the drive will start to keep constant DC voltage (AFE) or start to share power based on grid
frequency (Micro Grid). Using OPT-D7 for synchronisation will make the start of the drive smoother.
If the drive does not detect an existing line voltage or frequency in Micro Grid mode, the output
voltage is raised defined time (VoltageRiseTime). In the Island mode, the detection of the grid is not
made and the voltage is raised from zero in the set time (VoltageRiseTime).
NOTE: The OPT-D7 board (in slot C) is mandatory for the Grid Converter unit.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216

Vacon VACON® NXP GridConvGGC ARFIF106V103 User guide

Type
User guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI