Factory Checkout
AK-CC 550A
Service Guide
ADAP-KOOL® Refrigeration Control System
Service Guide | Factory Checkout, AK-CC 550A
© Danfoss | ADAP-KOOL® | 2018.08
2 | AX278851874155en-000101
Sensor Checks
Physical check of each sensor.
1. Hold each sensor at probe to create a rise in reading. At case
controller. verify reading has risen for expected sensor input as
follows:
Sensor Location 550A Sensor Designation Parameter
Coil Outlet S2 U20
Return Air S3 U12
Discharge Air S4 U16
Defrost Termination S5 U09
2. Allow sensor to return to ambient temperature. Repeat process
for all sensors on case controller, testing only one sensor at a
time.
Relay Checks
Change of state check via controller menus.
1. Change parameter r12 to ‘-1-‘
2. Cycle parameters to on’ as shown below for each function
(where used), and confirm component is operational.
Function Parameter
Fans U59
Defrost Heaters U60
Door Heaters U61
Case Lights U63
3. To test EEV relay and wiring (DO1, terminals 5&6), change
parameter U23 to 50%. Operation can then be verified via a coil
tester or through an audible clicking’ noise heard in 3 second
intervals.
4. Return parameter r12 to ‘0’ when complete.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
  • Page 1 1
  • Page 2 2

Danfoss 084B8030 User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI