Trane ADAMO MCW 5247BA00 Installation guide

Category
Split-system air conditioners
Type
Installation guide
ADAMO
Installation Manual
Split System
Wall Type
MCW Series 50 Hz
MS-SVN003-EN
January 2003
2
MS-SVN003-EN© American Standard Inc. 2003
General Information
General Information
This Installation Manual is given as a
guide to good practice in the
installation by the installer of MCW
mini-split system. Installation
procedures should be performed in
the sequence that they appear in this
manual.
For installing the unit to operate
properly and reliably, it must be
installed in accordance with these
instructions. Also, the services of a
qualified service technician should be
employed, through the maintenance
contract with a reputable service
company.
Read this Installation Manual
completely before installing the
air conditioning system.
About This Manual
Cautions appear at appropriate
places in this Installation Manual.
Your personal safety and the proper
operation of this machine require that
you follow them carefully.
The Trane Company assumes no
liability for installations or servicing
performed by unqualified personnel.
All phases of the installation of this air
conditioning system must conform to
all national, provincial, state and local
codes.
About The Unit
These MCW units are assembled,
pressure tested, dehydrated, charged
and run tested before shipment. The
information contained in this manual
applies to MCW units are designed to
operate in cooling mode only.
Trane MCW series offer wall mounted
installation to leave the floor space
uncluttered, and equipped with LCD
wireless remote control.
Reception
On arrival, inspect the unit before
signing the delivery note. Specify any
damage of the unit on the delivery
note, and send a registered letter of
protest to the last carrier of the goods
within 72 hours of delivery. Notify the
dealer at the same time.
The unit should be totally inspected
within 7 days of delivery. If any
concealed damage is discovered,
send a registered letter of protest to
the carrier within 7 days of delivery
and notify the dealer.
Warning
Warnings are provided at appropriate
places in this manual to indicate to
installers, operators and service
personnel of potentially hazardous
situations which, if not avoided,
COULD result in death or serious
injury.
Caution
Cautions are provided at appropriate
places in this manual to indicate to
installers, operators, and service
personnel of potentially hazardous
situations which, if not avoided, MAY
result in minor or moderate injury or
malfunction of the unit.
Your personal safety and the proper
operation of this unit require that you
follow them carefully. The Trane
Company assumes no liability for
installations or servicing performed by
unqualified personnel.
Warranty
Warranty is based on the general
terms and conditions by country. The
warranty is void if the equipment is
modified or repaired without the
written approval of The Trane
Company, if the operating limits are
exceeded or if the control system or
the electrical wiring is modified.
Damage due to inappropriate
installation, lack of knowledge or
failure to comply with the
manufacturer’s instructions, is not
covered by the warranty obligation.
If the installation does not conform to
the rules described in Installation
Manual, it may entail cancellation of
warranty and liabilities by The Trane
Company.
Important
This document is customer property
and is to remain with unit. Please
place in service information pack upon
completion of work.
These instructions do not cover all
variations in systems, nor do they
provide for every possible contingency
to be met in connection with
installation.
Should further information be desired
or should particular problems arise
which are not covered sufficiently in
this manual, the matter should be
referred to your authorized Trane
dealer.
MS-SVN003-EN
3
Contents
General Information 2
Typical Installation 4
Location and Preparation of Unit 5
Unit Installation 6
Wiring Diagram 12
Dimensional Data 13
Notes 14
4
MS-SVN003-EN
Typical Installation
Figure 1
Insulation
Tube
Tapping Screw
Remote Control Holder
Vinyl Tape
Two AAA batteries are used in this remote control unit
Wireless Remote Control
Air Filter
Water
Condensated
Drain Tube
Installation Items
The following items are supplied with the
indoor unit to provide proper system
installation:
1Wall Bracket : For indoor unit
installation
4Tapping Screw (Large) : For wall
bracket installation
2Tapping Screw (Small) : For remote
control mounting bracket installation
1 Remote Control Holder : For remote
control unit holder
O
N
O
F
F
MS-SVN003-EN
5
Location and Preparation of Unit
Figure 2
100 mm.
50 mm.
100 mm.
500 mm.
Figure 3
25 cm. or more
60 cm. or more
25 cm. or more
120 cm. or more
30 cm. or more
Selecting the Mounting
Locations
Determine the mounting location with
the customer as follows:
Indoor Unit
Install the indoor unit level on a
strong wall which is not subject
to vibration.
The inlet and outlet ports should
not be obstructed. The air should
be able to blow throughout the
room.
Install the indoor unit where
connection to the outdoor unit
can be made easily.
Install the unit where the drain pipe
can be easily installed.
•Take servicing into consideration
and leave the spacing shown in
Figure 2. Also, install the unit where
the filter can be easily removed.
Do not install the unit near a source
of heat, steam, or flammable gas.
Do not install the unit where it will
be exposed to direct sunlight.
Outdoor Unit
Leave the spacing shown in
Figure 3 for required air flow.
If possible, do not install the unit
where it will be exposed to direct
sunlight.
Do not install the unit near a source
of heat, steam, or flammable gas.
Do not install the unit where a
strong wind consistently blows or
where it is extremely dusty.
Do not install the unit where people
pass in front of the fan discharge
grille.
General Instructions
All phases of the installation of this
air conditioning system must
conform to all national, provincial,
state and local codes.
Read these instructions carefully
and completely before attempting
to install the air conditioning
system.
For the air conditioning system to
operate properly and reliably, it
must be installed in accordance
with these instructions.
The maximum length of the piping
is to10 meters. If the units are
further apart than this, correct
operation can not be guaranteed.
6
MS-SVN003-EN
Unit Installation
Figure 4
2.Left rear
outlet
3.Left
outlet
4.Right
outlet
(Rear)
1.Rear outlet
5.Bottom
outlet
Figure 6
Figure 5
Counter Weight
Type A Screw
Marking-off Line
Indoor Unit Installation
The piping can be connected in the
five directions indicated by 1, 2, 3, 4
and 5 in Figure 4. When the piping is
connected in direction 3, 4 or 5 cut
along the piping groove in the side or
bottom of the front cover with a saw.
1. Installing the Wall Bracket
1. Install the wall bracket so that it
is level from side to side. If the
wall bracket is tilted, condensate
water will drip to the floor.
2. Install the wall bracket so that it
is strong enough to withstand a
weight of 50 kilograms or more.
3. Fasten the wall bracket to the
wall with 6 or more screws
through the holes near the outer
edge of the bracket.
4. Check to insure that there is no
rattle of the wall bracket against
the wall.
Caution
Always cut the wall hole uniformly
and straight when the wall pipe is
not used. If the hold center is not
aligned, condensate leakage can
occur.
If the wall pipe is not used, the
wiring cable connecting the indoor
and outdoor units may become
frayed and cause electric current
leakage to earth.
3. Forming the Indoor Drain
Hose and Refrigerant Pipes
1. For 3 Left piping. 4 Right piping,
5 Bottom piping: Perform.
“Indoor Unit Wiring” before
performing the following steps
3.2 through 3.6.
2. Wrap the pipes of the indoor unit
that are visible from the inside
with decorative tape (Figure 7).
3. Insert the indoor unit piping into
the wall hole and bind the drain
hose and pipe together with
vinyl tape (Figure 8).
2. Cutting the Hole in the Wall
for the Connecting Piping
1. Cut a 65 mm. diameter hole in
the wall at the desired position
shown in Figure 6.
2. Cut the hole so that the outside
end is lower (5-10 mm.) than the
inside end.
3. Cut the wall pipe length to match
the wall thickness, insert it into
an accessory wall cap, fasten the
cap with vinyl tape, and insert the
pipe through the wall hole. (Wall
pipe and wall cap are procured
at the site).
4. For 3 left piping and 4 right
piping, cut the hole sligthly lower
so that the condensate water will
flow freely.
Installation Plate
Thread
MCW509-512
MCW518-524
MS-SVN003-EN
7
Figure 10
Drain hose
Wall hole
pipe
Pipe
Connection
cable
Figure 7
Connection
cable
Drain hose
Decorative tape
Left piping
Left rear piping
Bottom piping
Right piping
Cut the piping groove
with a hacksaw
Cut the piping groove
with a hacksaw
(Rear)
Indoor unit
piping
For left outlet, house the connection cord
and piping at the position shown in the above
figure with the drain hose at the bottom.
Figure 11
4. Install the piping so that the drain
hose is at the bottom (Figure 7).
Caution
•To prevent breaking of the pipe,
avoid sharp bends. Bend the
pipe with a radius of curveture of
100 mm. or more.
If the pipe is bent repeatedly at the
same place, it will break.
Do not remove the flare nuts
from the indoor unit pipe until
immediately before connecting
the outdoor connection piping.
5. After passing the indoor piping
and drain hose through the wall
hole, hang the indoor unit on the
hooks at the top and bottom of
the wall bracket.
6. Check to insure that: (Ref.
Figure 10).
The top and bottom hooks are
hooked firmly and the indoor unit
does not move to the front and
rear or left and right.
The indoor unit is accurately
positioned horizontally and
vertically.
The drain hose is at the bottom
of the wall hole pipe.
Indoor Unit Wiring
Both of the cable wires should be
connect from the terminal block
of indoor unit (Figure 11).
The appliance shall be installed in
accordance with national wiring
regulation.
Means for disconnection from the
supply having a contact separation
of at least 3 mm. in all poles must
be incorporated in the field wiring.
Figure 9
After hooking the indoor unit to the top
hook, hook the fitting of the indoor unit to
the two bottom hooks while lowering the
unit and pushing it against the wall.
Wall hook
bracket
Indoor unit
(Rear)
(Fitting)
Bottom hooks
Top
hooks
Figure 8
Drain hose
(bottom)
Bind with
vinyl tape
Pipe (top)
(Rear)
8
MS-SVN003-EN
A good flare should have the
following characteristics:
- Inside surface is glossy and
smooth.
- Edge is smooth.
-Tapered sides are of uniform
length.
Bending
5. When bending the tube, be careful
not to crush it. To prevent crushing
of the tube, bend it gently and do
not bend the tube at a radius
curvature of less than 100 mm.
3. Remove the flare nut from the
unit and be sure to mount it on
the copper tube.
4. Make a flare at the end of copper
tube with a flare tool (Figure 14,15).
Outdoor Unit Installation
1. Install the unit mounting pads
(4 places) into the bottom channels
by tapping gently with a plastic or
rubber tipped hammer.
2. Set the unit on a strong surface
such as one made of concrete to
minimize shock and vibration and
to locate the unit securely.
3. Do not set the unit directly on the
ground.
Connecting the Unit with
Flaring Procedure.
Flaring (If piping is procured or cut at
the site).
1. Cut the copper tube to the
required length with a tube cutter.
It is recommended to cut approx.
30-50 cm. longer than the tubing
length you estimate.
2. Hold each pipe downward when
cutting and remove burrs at the
end of the copper tube with a tube
reamer or file. This process is
important and should be done
carefully to make a good flare
(Figure 12 and Figure 13).
Flare nut
Copper tubing
Flare tool
Figure 14
Figure 15
L
Check if (L) is flared uniform
and is not cracked or scratched.
L Dimension:
1.4 to 1.7 mm (6.35 mm dia)
1.8 to 2.0 mm (9.53 mm dia)
1.9 to 2.2 mm (12.7 mm dia)
2.1 to 2.4 mm (15.88 mm dia)
Figure 12
Copper
tubing
Reamer
Figure 13
Deburring
Before After
6. If the copper tube is bent or pulled
too often, it will become stiff. Do
not bend the pipe more than three
times at one place.
Cautions before Connecting
Tubes Tightly
7. Be sure to apply a sealing cap
or water-proof tape to prevent
dust or water from getting into
the tubes before they are used.
8. Be sure to apply refrigerant
lubricant to the matching
surfaces of the flare and union
before connecting them together.
This is effective for reducing gas
leaks (Figure 16).
Figure 16
Apply refrigerant lubricant here
Figure 17
Union Flare nut
Connection
9. For proper connection, align the
union tube and flare tube straight
with each other, then screw in the
flare nut lightly at first to obtain a
smooth match (Figure 17).
When reaming, hold the tube end
downward and be sure that no
copper scraps fall into the tube.
10. Tighten the flare nut to the
specified tightening torque with
torque wrench and adjustable
wrench (Figure 18).
11. Repeat the process above for the
remaining line.
MS-SVN003-EN
9
Indoor unit pipe
Torque wrench
Flare nut
Connection pipe
Wrench
(adjustable).
Figure 18
Flare Nut Tightening Torque
Flare nut/Piping size Tightening torque
kg
f
, - cm lb
f
-in
6.35 mm (1/4”) dia. 150~200 130~170
9.53 mm (3/8”) dia. 350~400 300~340
12.7 mm (1/2”) dia. 500~550 430~470
15.88 mm (5/8”) dia. 600~650 520~570
Remote Control Installation
Locate and attach the wireless
remote control as follows:
1. Do not place the control and the
remote control near heat sources
or expose to the direct rays of the
sun.
2. Do not expose the control to the
indoor unit’s supply air stream.
3. Do not place in a confined space.
4. Attach the remote control holder
as shown in Figure 19.
Evacuation and Refrigerant
Charge
1. Air Evacuation and Charging
1. Remove the cap and connect the
gauge manifold and the vacuum
pump to the charging port using
the service hoses (Figure 20).
2. Pump the indoor unit and the
connecting pipes until the
pressure in them lowers to below
1.5 mmHg of vacuum.
3. Stop the vacuum pump and close
the gauge manifold valve.
4. Remove the blanking caps and
fully open the service valves with
a hexagon wrench (Torque: 70
to 90 kg
f
- cm).
Remote
Control
Unit
ON OFF
Remote Control Holder
Tapping Screw
(small)
Wireless Remote Control
Figure 19
10
MS-SVN003-EN
Figure 22
Pipe length 16ft 23ft 33ft
(5m) (7m) (10m)
Additional refrigerant None 1.1 oz 2.8 oz
(R22) (32g) (80g)
5. Reinstall the blanking caps of the
service valves.
6. Disconnect the service hoses and
reinstall the cap on the charging
port. (Tightening torque: 70 to
90 kg
f
- cm).
2. Additional Charge
Refrigerant suitable for a piping length
of 3.5 to 5.0 meters is charged in the
outdoor unit from the factory. When the
piping is longer than 5 m, additional
charging is necessary. For the
additional amount, see table below.
Outdoor Unit
Figure 20
Refrigerant pipe
Blank cap
Charging port
Cap
Service hose
with valve core
Service valve
Gauge manifold
Vacuum
pump
Service hose
Between 5 m and 10 m, when using
connection pipe lengths other than
that in the table, charge additional
refrigerant with 0.56 oz (16g)/3.3ft.
Caution
FREON GAS “R22” ONLY
Always evacuate air from the piping
before adding refrigerant.
Add refrigerant through the
charging valve after the completion
of removing the blanking caps and
fully open the service valves.
Gas Leakage Inspection
After charging with refrigerant, check
the joints for gas leakage with gas leak
detector or a soap bubble solution.
Figure 21
Outdoor Unit Wiring
1. Remove the outdoor unit terminal
cover (Figure 21).
2. Route the connection cable through
the cable entry brushing and up to
the terminal block.
3. Insert the end of the cable wires
into the terminal block connectors
as shown on the unit wiring
diagram (Figure 11).
4. Tighten the terminal block
connector screws.
(Torque: 7-12 kgf-cm).
The appliance shall be installed in
accordance with national wiring
regulation.
Caution
The connector cable wires must be
connected such that terminal
numbers on the indoor unit match
those on the terminal block of the
outdoor unit (Figure 11).
Insert the connection cable wires
into the terminal block firmly.
Incorrect insertion may cause a
safety problem.
5. Replace the outdoor unit terminal
cover.
Drain hose
MS-SVN003-EN
11
Figure 23
Pipe
Clamp
Wall
Outside wall
cap sealer
(Outdoor)
End in water
Figure 24
Check the following:
Drain hose
Clamp
Lifted up
Wave
Finishing
1. Securely wrap the connection
cable along the refrigerant pipes
with vinyl tape. (Starting at the
lowest end of the pipes, each
wrap should be about 1/3 of the
tape width so that water does
not enter).(Figure 22)
2. Fasten the cable/piping to the
outside wall with clamps, etc.
3. Fill the gap between the outside
wall cap and the pipe with sealer
so that rain water and wind cannot
blow in.
4. Fasten the drain hose to the outside
wall, etc (Figure 23 & Figure 24).
Run Test
1. Start the system and check items 1
through 7 below.
2. For the system start procedure,
refer to the Owner Manual.
Indoor Unit
1. Is operation of the on and off button
and fan button normal?
2. Does each indicator on the remote
control display panel light normally?
3. Does the air deflection louver
operate normally?
4. Is the condensate drain normal and
freely flowing water?
Outdoor Unit
5. Is there any abnormal noise and
vibration during operation?
6. Will noise, air flow, or drain water
from the unit disturb the neighbors?
7. Is there any refrigerant gas
leakage?
Customer Guidance
Explain the following to the customer
in accordance with the Owner Manual.
1. Starting and stopping procedures,
mode switching, temperature
adjustment, timer and air flow
adjustment, and other remote
control operations.
2. Filter removal and cleaning and
how to use the air louvers.
3. Give the operating and installation
manuals to the customer.
Front Panel Assemble
Removal and Replacement
1. Removal
Side out the plastic screw cap (3
pieces as shown in the picture.)
Remove the front panel screws (3
pieces.)
Remove the horizontal vane to the
position as shown in the picture.
Open the front panel by lifting the
lower side of the panel carefully
2. Replacement
After securing the front panel tabs
into the holes in the body, fasten
the bottom of the front panel with
the three screws removed in step 1.
Front panel
Mounting screw
Horizontal vane
Figure 25
12
MS-SVN003-EN
Wiring Diagram
MS-SVN003-EN
13
Dimensional Data
MODEL DIMENSIONS (MM.) CLEARANCE (MM.) WEIGHT (KG.)
ABCDEF
MCW 5097BA00 900.00 180.00 265.00 10.00
MCW 5127BA00 900.00 180.00 265.00 100.00 50.00 500.00 10.00
MCW 5187BA00 1,165.00 180.00 310.00 14.00
MCW 5247BA00 1,165.00 180.00 310.00 14.00
A
D
F
D
B
C
E
14
MS-SVN003-EN
Notes
MS-SVN003-EN
15
Notes
Since The Trane Company has a policy of continuous product and product data improvement,
it reserves the right to change design and specifications without notice.
Literature Order Number: MS-SVN003-EN 0103
Supersedes: MS-SVN003-EN 1200
Stocking Location: Bangkok, Thailand
Trane Thailand
7th Floor, Ploenchit Center Building
2 Sukhumvit Road, Klongtoey
Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road
Samrong Tai, Samutprakarn 10130
http://www.trane.com
An American Standard Company
∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“¡‘ßæ√“¬ µ.”‚√ß„µâ Õ.æ√–ª√–·¥ß ®.¡ÿ∑√ª√“°“√ 10130
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Trane ADAMO MCW 5247BA00 Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI